| 1 | SCHEDULE \"A\" PART-I : BOQ OF WORKS FOR EXTERNAL ELECTRIFIACTION WORKS. |
| 2 | Replacement of old unserviceable/ damaged LT XLPE cable with new XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 95.0 Sqmm, 3.50-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and as directed. |
| 3 | Descriptionall as per serial item No- 1.01 here-in-before but for cable ofsize 50 Sqmm 3.5 core |
| 4 | Descriptionall as per serial item No- 1.01 here-in-before but for cable ofsize 35 Sqmm 3.5 core |
| 5 | Descriptionall as per serial item No- 1.01 here-in-before but for cable ofsize 25 Sqmm 4.0 core |
| 6 | Descriptionall as per serial item No- 1.01 here-in-before but for cable ofsize 16 Sqmm 4.0 core |
| 7 | Double wall corrugated HDPE pipe, orange colour, ISI marked, nominal size 50 mm dia with 38 mm inner dia, conforming to IS: 16205 Part-24, including connecting accessories i.e couplers, connectors, bends, sockets, for protection of electric cable, laying in trenches, duct or fixed to walls/ poles as required, complete all as specified and as directed.Make: Prince/ Finolex/ Astral/ RC Plasto/ Supreme. |
| 8 | Supply installation, commissioning, new LT feeder pillar box/ panel, in-replacement of old unserviceable LT panel/ feeder pillar box, complete all as specified and as directed by Engineer-In-Charge.Note: Detailed description and accessories/ equipments shall be as mentioned on serial page No- 21 of tender (CA) here-in-after. |
| 9 | Sheet metal enclosures for Single Pole and Neutral distribution boxes with double door glazed for incorporating MCBs, IP-65, 8-way with 200 amps rated busbar, 240 volts, as per IS-8623, fixing in repairs, complete all as specified and as directed. |
| 10 | Replacement of old unserviceable sub main wiring with new sub main wiring in PVC conduit of 25mm dia for circuits/ submain wiring along with earth wire with two run of 6.0 Sqmm of fire resistance, PVC insulated copper conductor, single core cable, multi-stranded, FRLS, ISI marked, 1100 Volts grade and one run of 6.0 Sqmm, FRLS, PVC insulated copper conductor, single core cable, multi stranded, ISI marked, 1100 Volts grade as earth wire connected to earth terminal, using colour coding, drawn in and including any type of conduit/ new casing and caping, any size/ dia including all accessories concealed by chasing/ cutting or fixed with PVC plug and mild steel screws on the surface of walls/ floors/ ceilings and making good the disturbed surface matching to existing descriptions/ specifications, complete all as specified and as directed.Note: Cost of all three run of wire and one run of conduit of 25mm dia will be included in quoted rate. |
| 11 | MCB, single pole, 6 to 32 Amps, 240 Volts, 50 Hz, \"C\" curve including necessary incoming and out going electric connection with suitable size of copper lugs, fixing in repairs, complete all as specified and as directed. |
| 12 | MCB, single pole and neutral, 40 Amps, 240 volts, 50 Hz, \"C\" curve including necessary incoming and out going electric connection with suitable size of copper lugs, fixing in repairs, complete all as specified and as directed. |
| 13 | MCB, single pole and neutral, 63 Amps, 240 volts, 50 Hz, \"C\" curve including necessary incoming and out going electric connection with suitable size of copper lugs, fixing in repairs, complete all as specified and as directed. |
| 14 | Excavation in trenches, not exceeding 1.50mtr wide and not exceeding 1.50mtr in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 Sqm on plan and not exceeding 1.50 mtr in depth and getting out, in any type of soil, complete all as specified and as directed. |
| 15 | Excavation in trenches, not exceeding 1.50mtr wide and not exceeding 1.50mtr in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 Sqm on plan and not exceeding 1.50 mtr in depth and getting out, in hard rocks, complete all as specified and as directed. |
| 16 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm, any type of soil, complete all as specified and as directed. |
| 17 | Removing excavated soil not exceeding 50mtr and depositing where directed at a level not exceeding 1.50 mtr above the starting point, complete all as specified and as directed. |
| 18 | Sand cushioning to protection of underground cables, laid 8 Cm before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cm thick, complete all as specified and directed.Note: Punned thickness shall be measured. |
| 19 | Sub class ‘B’ bricks, modular size, brick covering laid dry, flat, transversally along the length of cable on sand cushioning for mechanical protection of cable, with width equal to the length of the brick, complete all as specified and directed. |
| 20 | Replacement of old unserviceable/ damaged cable jointing kit with new cable jointing kit for Cable jointing kit for 1.10 KV (Earthed) grade cable for straight through/ termination, heat shrink type joint, complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 10 sqmm to 16 sqmm, 3.5-core/4.0-core, complete all as specified and as directed. |
| 21 | Descriptionall as per serial item No- 1.19 here-in-before but for cable ofsize 25 Sqmm to 50 sqmm |
| 22 | Descriptionall as per serial item No- 1.19 here-in-before but for cable ofsize 70 Sqmm to 95 sqmm |
| 23 | Cutting the road depth up to 1.50mtrs below the ground the level and making trench of suitable width to laying 80mm bore galvanised pipe across the cross-section of the road I horizontally for passing electric cable including making good to road surface as per existing specifications or with plain cement concrete M-20 (1:1.5:3), type B-1 (using 20mm graded crushed stone aggregates), complete all as specified and as directed.Note: Cost of cutting the road, laying electric cable through galvanised iron pipe and material required for making good to road surfaces, shall be deemed included in the quoted rate. |
| 24 | Tubes, \"light grade\" galvanised, 80mm bore, ISI marked including all fitting such as bends, socket, connectors, back nuts, etc, laid in trenches or under floors, complete all as specified and as directed. |
| 25 | Description all as per serial item No- 1.23 here-in-before but of size 50 mm bore |
| 26 | Description all as serial item No- 1.23 here-in-before but of size 40 mm bore |
| 27 | Earthing complete with galvanised iron earth plate electrode 600x600x6mm buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of earth plate not less than 1.5mtr below normal ground level, connected with galvanised iron wire, size 4.0mm dia as earth lead, by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete with 20mm dia GI light grade protection pipe, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15, type B-1 in pit with precast RCC M-15(1:2:4), type B-1 (using 20mm graded crushed stone aggregates) in cover reinforced with XPM not less than 4.0 Kg per Sqm, test pointetc. all as shown in electric plate No-3 of SSR Part-I (2009), complete with necessary earth work in any type of soil, removal to a distance not exceeding 50mtr, including testing on completion, complete all as specified and as directed by Engineer-In-Charge.Note: Earth pit chamber and RCC pit cover shall be painted with two coats of red synthetic enamel paint over one coat of primer including preparing of surfaces. |
| 28 | Amount of Schedule of credit as mentioned here-in-after shall be deducted from quoted amount. |