| 1 | M & L for dismantling Centrifugal pump motor of size 50 HP from its position alongwith base frame,tyre coupling by disconnecting electric connections and by unscewing nut bolt and rubber sheet from suction and delivery MS Pipe of size 125 mm dia and 100 mm dia without any damage to the pipe all as directed and specified. Note :- (i) T&P required for dismantling will be arranged by the contractor. |
| 2 | M & L for refixing Centrifugal pump motor of size 50 HP in its original position after making good existing pcc foundation replacing damaged and rusted base frame structure, anti vibration pad and making electric connection, Tightening/replacing damaged nut bolt and damaged rubber sheet and refixing the pump motor with suction and delivery pipe and checking for alignment after Painting the pump motor by the enamel paint of same colour as original after removal of old paint, writing the SM/MHS number provided by the department and checking for any leakage in the pump and motor assembely. Note :- (i) Cost of replacing Nut, bolt ,rubber sheet, painting, writing may please be included in the quoted rate no extra payment/claim will be accepted. (ii) Cost of replacing base frame foundation of same size and shape will be measured and paid under respective item of BOQ. |
| 3 | M & L for in replacement heavy duty tyre coupling (TC-15) of centrifugal pump motor of size 50 HP all as directed and specified. |
| 4 | M&Lfor framed work such as grills, gratings, etc. with ends of bars shouldered and/or riveted, or forged into spikes, framed guard bars, barred iron doors, ladders, framed balusters, walk ways, railings, framework of water tanks and similar work con- forming to Fe.29 .Gde-E-165 including portions framed and hung as gates, including pintle hinges, stops, hand-made sliding bolts including dismantling old steel work etc complete all as specified and directed. |
| 5 | M&L for Earthing complete with galvanized steel earth plate electrodes 600 mmx600 mm x6 mm thick buried directly in ground earth plate not less than 2.25 m deep below normal ground level with top edge of the plate not less than 1.5 m below normal ground level connected to and including galvanized GI strip 32x6mm as earth lead up to 7.5 mtr long by means of bolts, nuts, check nuts and washers of galvanized iron and steel including PCC pit in PCC 1:2:4 type B-1using 20 mm graded crushed stone aggregate, RCC framewith 40mm thick RCC cover reinforced with 8mm dia deformed barshandle. including excavation and earth work in any type of soil medium grade GI watering pipe 20mm bore with funnel and wire mesh and light grade GI protection pipe 40mm bore main board complete all as shown in electrical plate No 3connected to main control board all as specified and testingon completion. Note: (i) Excavation earthwork charcoal PCC pit is covered under this item including taking out existing earthing complete all as specified and directed.(ii) GI strip exceeding 7.5mtr lnong shall be measured and paid seperately. |
| 6 | M&L for dewatering of existing underground reservoirs Central pump house Sump well of any description clean inside surfaces of water under ground sump by scraping down walls & bottom surfaces of the sump with using steel wire brushes and light hammer to remove all deposition/fungus other micro organism sediment loose dis/mud sluge, vegetation other micro foreign materials etc and also removing loose/onground concrete/plaster including taking out and removing all disposal waste/spoil to a distance not exceeding 50mtr and washing the cleaned surfaces with water and washing repeatedly with rebekience solution floor/bottom of OH tanks/underground reservoirs complete all as specified and directed.Note:- (i) Area of each sump well of 5 lakh gln capacity is 1511 Sqm.(ii) All T&P used in draining out and completing the job will be provided by the contractor without any extra cost to the department. |
| 7 | M&L for dewatering of existing underground reservoirs Central pump house Sump well of any description clean inside surfaces of water under ground sump by scraping down walls & bottom surfaces of the sump with using steel wire brushes and light hammer to remove all deposition/fungus other micro organism sediment loose dis/mud sluge, vegetation other micro foreign materials etc and also removing loose/onground concrete/plaster including taking out and removing all disposal waste/spoil to a distance not exceeding 50mtr and washing the cleaned surfaces with water and washing repeatedly with rebekience solution floor/bottom of OH tanks/underground reservoirs complete all as specified and directed.Note:- (i) Area of each sump well of 8 lakh gln capacity is 2450 Sqm. (i) All T&P used in draining out and completing the job will be provided by the contractor without any extra cost to the department. |
| 8 | M&L for dewatering of existing underground reservoirs Central pump house Sump well of any description clean inside surfaces of water under ground sump by scraping down walls & bottom surfaces of the sump with using steel wire brushes and light hammer to remove all deposition/fungus other micro organism sediment loose dis/mud sluge, vegetation other micro foreign materials etc and also removing loose/onground concrete/plaster including taking out and removing all disposal waste/spoil to a distance not exceeding 50mtr and washing the cleaned surfaces with water and washing repeatedly with rebekience solution floor/bottom of OH tanks/underground reservoirs complete all as specified and directed.Note:- (i) Area of each sump well of 1 lakh gln capacity is 300 Sqm. (i) All T&P used in draining out and completing the job will be provided by the contractor without any extra cost to the department. |
| 9 | M&L for repairing of sluice valve with opening and taking out old unservercible defective spindle and refix the same after taking out the spindle transporting to workshop for machine work in only old gun metal/stainless steel spindle by making new threads on lathe machine with check nut, rubber gasket, gland packing, nuts & bolts all as required at site and directed by Engineer-in-charge for the following sizes:- |
| 10 | 100mm dia bore |
| 11 | 150mm dia bore |
| 12 | 200mm dia bore |
| 13 | 250mm dia bore |
| 14 | 125mm dia bore |
| 15 | Supply & fixing single phase motor 2780 RPM of capacity 0.75 KW / 1HP, pressure booster pump rated discharge approx 1500 LPH at rated head 40 m suction discharge of pump 25x25 mm alongwith pressure tank of capacity 10 litre including taking down old unserviceable pressure pump motorcomplete all as specified and directed.Note : Old unserviceable motor deposited to E/M (West) store yard. |
| 16 | Supply, install and testing of submersible pump motor copper winding 11 KW/15 HP @1500 LPM at 32 mtr head including taking down old unserviceable submersible pump motorcomplete all as specified and directed.Make : Crompton Cat part No J3B15/J3B15-WX or equivalent in make as specified in list of make.Note : Old unserviceable motor deposited to E/M (West) store yard. |
| 17 | M&L for in replacement contactor MNX 110 Amp, 3 pole, 415 volts including fixing of all necessary connections complete all as specified and directed. |
| 18 | M&L for dewatering of existing over head tanks of staging up to 21 meter of any descriptionof capacity 0.25 Lakh GallonsLoc PH NO 20 at OD complex, clean inside surfaces of OHT of all chambers i.e inner and outer by scraping down walls & bottom surfaceswith using steel wire brushes and light hammer to remove all deposition/fungus other organism sediment loose dis/mud sluge, vegetation other micro foreign materials etc andalso removing loose/unsound concrete/plaster including taking out and removing all disposal waste/spoil to a distance not exceeding 50 mtr and make good plastering surface wall of OHT with cement mortar (1:3) and finish surface even and smooth with using extra cement including washing the cleaned surfaces with water and washing repeatedly with rebekience solution floor/bottom of OH tanks to acheive disinfected surface inside OHT complete all as specified and directed by Engineer-in- Charge.Note (i) Contractor will start the work after the prior permisson of department for the concern site .(ii) Contractor will do once a job in one time so that the crises of water can not be happened.(iii) Contractor will apply hislabour ,reinforcement ,T&P all material and related items near the site before starting the work. |
| 19 | (iv) Contractor will reasponsible for water supply if not finish in stipulated time he will supply to the concern area through water bouser or penality ofRs 2500/- will be charged for the compensation of no water supply. (v) OHT Cleaning done and due will be written on a block marked with outline with colour on black/blue/white back groundon the OHT at visible place in bold and clear writting with proper painting alphabtes Writing letters or figures (Block. Roman, Italic or Indian) n exc. 30 cm high Letters etc., shall be painted with thick paint, so that they stand out boldly and solidly without showing signs of brush marks, if necessary, they shall be repainted until the desired result is obtained.(vi) Video recording of each and every OHT work before and after the work will be done by the contractor and kept in record.(vii) Cost of disinfection rebekience solution is deemed to included in the quoted rate. |
| 20 | All as per Item No 13.00 & 13.01 (here-in-before) but 0.5 Lakh gallonLocation - PH No. 10 (RATC) - 02 Nos , PH No. 11-02 Nos , PH No 20 (MAP & KLP)-02 Nos, PH No. 14 (NHL)-01,PH No-15 (RATC)-01,PH No-17(NHL)-01, 3 RPD-01 No ,1 CSR KLP -01 No ,LOHARA MARG -01 No,EME KLP-01, CGSR KLP-01. |
| 21 | All as per Item No 13.00 & 13.01 (here-in-before) but1 Lakh gallon Loc PH No 19 (RATC Line JCO Accn),PH No 12,(MES Line), PH No 09 (OHL), PH No 24 (Near Single Offr Mess)-01 No, Core HQ-01 No, PH No 20 OD-01 No. |
| 22 | All as per Item No 13.00 & 13.01 (here-in-before) but1.1 Lakh gallon Loc PH NO 20 at OD complex, |
| 23 | All as per Item No 13.00 & 13.01 (here-in-before) but1.40 Lakh gallon Loc RATC -II |
| 24 | M & L for replacement of pressure gauge of size 200 mm dial 0-21 Kgs rating by with allfitting and testing and arresting any leakage after removing existing unserviceable pressure gauge from its original position without damaging existing structure all as specified and directed. |
| 25 | M & L for opening the door by dismantling all nut bolts and packing material without damaging any part of pressure filter of capacity 27500 Gln/hour and removing complete filter media from pressure filter and stacking it in a clean and safe place all as specified and directed. |
| 26 | M & L for refilling the serviceable media of existing quality, size and shape in engineered manner layer wise after properly cleaning,removing unserviceable media, topping up serviceable media of same size, shape, closing of door by serviceable nut bolts and packing sheet and testing it completely all as specified and directed.Note :- Media require for topping up will be measured and paid seperatelyunder respective item of BOQ. |
| 27 | M & L for cleaning of inner shell of pressure filter of size 27500 Gln/Hr by removing dirt,mud,rusted particles, removing any blockage in the air vents and painting the inner shell and pipes completely by one coat of primer and one coat of enamel paint all as specified and directed |
| 28 | Supply and mixing pressure filter media (sand and gravel) of washed,best quality, different size and shape as required suitable for pressure sand filter all as specified as per IS-8419 all as specified and directed |
| 29 | S&F in replacement Security Light LED 70W of new generation energy saving and environmental friendly longlife LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens empedded PC cover having TOP openining seperate driver compartment with IP-66 protection and impact resistance of IK07 with 10 KV Built surge Protection Devices and electronic driver including suitable pipe for light fiftings, bolts, brackets and necessrary paintingof connected accessories complete all as specified and as directed. |
| 30 | S&F in replacement of Post Top Lantern 40 Watts the system shall include FRP housing Hi-brightness W-LED (120-140 lumens per watt) operating voltage 11.1/12.8V, IP-65 complaint driver efficieny 85% to 90% CRI > 70 CCT 5000 to 6500 kelvin toughen glass/acrylic cover complete with GI iron pipe 65 mm dia, medium grade, 5 mtr high excluding 1 mtr planting depth with aluminium painted foundation of pole with PCC (1:3:6) using 20 mm graded stone aggregate of size 450 x 450 x 1000 mm deep including earthwork complete all as specified and directed. |
| 31 | Supply & laying in trenches or passing through pipe, 1100 volts grade heavy duty cable with \"\"XLPE\"\" insulated aluminium conductor standard served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed of 70 Sqmm x 3.5 core size including taking down old unserviceable cable complete all as specified and directed.Note: Earth work and other connected work shall be measured & paid sperately. |
| 32 | M&L and T&P for scraping/removing of complete old paint from pump motor of capacity 50 HP and painting the same with two coat of synthetic supper enamelled paint over one coat of primer as existing color including writing SM/MES No complete all as directed by Engineer in charge. |
| 33 | Supply, installation and testing in replacement MS Galvanised Pipe heavy class of size 80mm dia with all fittings/flanged all as specified and as directed |
| 34 | Supply, installation and testing in replacement MS Galvanised Pipe heavy class of size 100mm dia with all fittings/flanged all as specified and as directed |
| 35 | Supply, installation and testing in replacement MS Galvanised Pipe heavy class of size 125mm dia with all fittings/flanged all as specified and as directed |
| 36 | M&L for installation, commissiong and testing fully automatic star delta starters rating 50 HP, with ammeter, voltmeter, automatic phase sequence corrector, overload relay 37.6-60.0 range, 95 amps of E type contactor in steel sheet encloser with IP-54 protection, including all required electrical connection and thimbles complete all as specified and directed. |
| 37 | S&F in replacement PVC cables copper conductor insulated and unsheathed multistrandedsingle core of size 70 sqmm 1100 V including copper lugs complete all as specified and directed. |
| 38 | Supply, installation and testing in replacement of Sluice valve PN 1.6 200 mm dia ISI Markedall as specified and directed |
| 39 | Supply, installation and testing in replacement of Sluice valve PN 1.6 100 mm dia ISI Markedall as specified and directed |
| 40 | Supply, installation and testing in replacement of Sluice valve PN 1.6 150 mm dia ISI Markedall as specified and directed |
| 41 | M&L construction of brick masonry valve pit / chamber of size 1050mm x 1050mm x 1050mm (internal dimensions of chamber) using 50% new bricks built in one brick thick wall in cement mortar 1:4) including top of MS cover with MS sheet cover 3mm thick including frame of angle iron 40 x 40 x 6mm with locking arrangement, lifting handle and 02 Nos 100mm size MS butt hinges including painting two coats of black synthetic enamel paint over a coat of red oxide primer, 15mm thick plastering in cement mortar (1:4) (internally on all brick wall and external upto 15cm below ground level) and necessary excavation and earth work in any type of soil, returning, filling in, disposal of surplus spoil to a distance not exceeding 50 mtr, 15 cm thick PCC (1:4:8) type D-2 in foundation projected by 15cm all round from the outer face of brick wall, PCC (1:2:4) type B-1 (using 20mm graded stone aggregate) 40mm thick in coping including dismantling of old unserviceable valve pit chambe complete all as specified and directed. |
| 42 | M&L for cleaning the vegitation, grass, bushes etc inside and out side the installation perameterto maintain the installation premises neat and clean at various places as directed by Engr-in-Charge. |
| 43 | Supply, installation, clamping and testing Cast iron pipes in replcement of rusted leaking vertical rising/delivery mains of OHT of size 100 mm dia , with flanged ends and all nut bolts, centrifugally cast, class A, in any length all as specified and directed. |
| 44 | Supply, installation, clamping and testing Cast iron pipes in replcement of rusted leaking vertical rising/delivery mains of OHT of size 150 mm dia , with flanged ends and all nut bolts, centrifugally cast, class A, in any length all as specified and directed. |
| 45 | Supply, installation, clamping and testing Cast iron pipes in replcement of rusted leaking vertical rising/delivery mains of OHT of size 200 mm dia , with flanged ends and all nut bolts, centrifugally cast, class A, in any length all as specified and directed |
| 46 | S&F in replacement of mechnical chlorine dosing planthigh pressure single head adjustable granular chlorine dosing system and chlorination doser pump with mixing tank for calcium hypo chloride 65 to 70% including connecting pipe complete all as specified and directed with following items :(a) Adjustable High pressure 5 Kg/Sqcm power input 230 V 50 Hz, 40 SPM 1/3 frictional HP, max output 10 Ltr/hr.(b) Preparation Tank of net capacity of 100 LtrsFRP.(c) 200 Ltr FRP dosing tank with gauge agitator 120 watt 900 mm SP range mounted with plastic shaft and impeller including Service tank and all assessories. |
| 47 | Taking out the existing aviation lights from its existing position and S&F new LED avaiation lights with light dependent sensor 12 wattt IP65 protection with all fitting and fixing arrangment including all electric connection wiringand control switch complete all as specified and directed. Note:- (i) The light fitting have provision of proper grouting on PCC pedstal and grouted over the PCC platform, light fitting can sustain the wind and storm pressure and stand delibrately on 21 mtr ht position without any deflection.Contractor shallmaintain the fitting and fixtuers up to 01 year of installation of aviation lights.(ii) Required necessary T&P will be arranged by contractor. |
| 48 | Taking down old damaged/ Worn out / rusted sign board from installation and S&F new sign board made out of flex sheet, tin sheet box to base length and to provision of hollow square tube/ pipe, angle of size 45mm x 45mm x 5 mm thick for fixing proper arrangement of sign board as per existing, (approx length of each sign board 7.5 mtr x 0.75 mtr x 0.20 mtr) with MS clamps, bolts, nuts and washers including 04 Nos LED lights of 20 W (4 feet) in each Sign board and including all electrical connection with separateON & OFF switch box & cable of 1.5 sqmm in casing caping required at site complete all as specified and directed. |
| 49 | Supply, install, testing complete in replacement Non return sluice valve of size 100 mm dia PN 1.6 ISI marked all as specified and directed |
| 50 | S&F in replacement PVC cables copper conductor insulated and unsheathed multistrandedsingle core of size 50 sqmm 1100 V including copper lugs complete all as specified and directed. |
| 51 | Supply and fix in replacement soft starter Suitable for three phase motor pump 30 HP, With overload protection, underload protection, Locked load protection, soft start, soft stop, current limit, coated PCBA, Analog output ,built in bypass for energy saving. Operating voltage 208-600 volt AC all as directed by Engineer-in-charge |
| 52 | M&L for rewinding submersible motor 30 HP three Phase, 415 volts, 50 Hz A/C with insulated copper wire of existing gauge including all insulating materials, complete assembling, connecting and testing on full load complete all as specified and directed. |
| 53 | Supply and fixing in replacement CI body butter fly valve of size 150mm dia half round type ISI marked including nuts, bolts, joint, rubber insertion sheet complete all as specified and directed by Engineer in Charge. |
| 54 | Supply and fixing in replacement CI body butter fly valve of size 200mm dia half round type ISI marked including nuts, bolts, joint, rubber insertion sheet complete all as specified and directed by Engineer in Charge. |