| 1 | Fabricate, supply ,install testing and commissioning of LT panel indoor type 415 Volts, 50 Hz, 3 phase, 4 wire suitable for accommodating the following accessories totally enclosed self supporting structure fully compartmentalized suitable for indoor use with bottom cable entry with suitable cable glands made out of CRCA sheet 2mm thick with angle iron frame works with suitable legs of ISA 50x50x5mm with four legs grouted PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for aluminium bus bars 1200 Amps capacity, hinged door at front with suitable locking arrangement, provision of louvers at sides, CPRI approved, dust and vermin proof, powder coated with following accessories suitable for incoming/outgoing arrangements complete all as specified and directed:- (a) 4 Pole ACB 800 Amp, 50 Hz, 415 V with rupturing capacity 50 KA, Incomer -1 No(b) 4 Pole MCCB 400 Amp, 50 Hz, 415 V with rupturing capacity 36 KA,-04 Nos(c) ON Load changeover switch 4 pole 320 Amps - 1 No(d)Digital VAF Meter-01 Nos(f) CT\"s 800/5- set of 3 No(g) LED type Indication lamps (RYB)-one set(for each incoming and outgoing) Note : (i) Contractor has to get the approval of drawings of LT panel from the Engr In Charge /GE before commencement of work. (ii) Switch gear and connected items should be of approved make. (iii) Bottom portion of panel should be 30 CM above from the ground level. |
| 2 | Fabricate, supply, install, testing and commissioning of LT panel outdoor type 415 Volts, 50 Hz, 3 phase, 4 wire Suitable for accommodating the following accessories totally enclosed self supporting structure fully compartmentalized suitable for outdoor use with bottom cable entry with suitable cable glands made out of CRCA sheet 3.15mm thick with angle iron frame works with suitable legs of ISA 50x50x5mm with four legs grouted PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for aluminium bus bars 500 Amps capacity, hinged door at front with suitable locking arrangement, provision of louvers at sides, CPRI approved, dust and vermin proof, powder coated and with following accessories suitable for incoming/outgoing arrangements complete all as specified and directed:-(a) On load changeover switch 315 Amps, Incomer -1 No(b) 4 Pole MCCB 320 Amp, 50 Hz, 415 V with rupturing capacity 36 KA,-01 No(c) 4 Pole MCCB 100 Amp,50 Hz, 415V with rupturing capacity 25 KA- 01 No(d) 4 Pole MCCB 63 Amp,50 Hz, 415V with rupturing capacity 16 KA- 01 No(d) Multifunctional VAF meter -01 Nos (f) CT\"s 320/5- set of 3 No(g) LED type Indication lamps (RYB)-one set(for each incoming and outgoing) Note : (i) Contractor has to get the approval of drawings of LT panel from the Engr In Charge /GE before commencement of work. (ii) Switch gear and connected items should be of approved make. (iii) Bottom portion of panel should be 30 CM above from the ground level. |
| 3 | Fabricate, supply, install, testing and commissioning ofLT panel Outdoor type 415 Volts, 50 Hz, 3 phase, 4 wire for accommodating the following accessories totally enclosed self supporting structure fully compartmentalized suitable for outdoor use with bottom cable entry with suitable cable glands made out of CRCA sheet 3.15mm thick with angle iron frame works with suitable legs of ISA 50x50x5mm with four legs grouted PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for aluminium bus bars 600 Amps capacity, hinged door at front with suitable locking arrangement, provision of louvers at sides, CPRI approved, dust and vermin proof, powder coated and with following accessories suitable for incoming/outgoing arrangements complete all as specified and directed:- (a) On load changeover switch 4 Pole 315 Amps, Incomer -1 No(b) 4 Pole MCCB 320 Amp, 50 Hz, 415 V with rupturing capacity 36 KA, -1 No(c) 4 Pole MCCB 125 Amp, 50 Hz, 415 V with rupturing capacity 25 KA, -01 No(d) 4 Pole MCCB 100 Amp, 50 Hz, 415 V with rupturing capacity 16 KA, -01 No(e) 4 Pole MCCB 40 Amp 50 Hz , 415V with rupturing capacity 16 KA -01 Nos (e) Multifunctional VAF Meter -01 No(f) Digital Ammeter-01 No(g) CT\"s 315/5- set of 3 No(h) LED type Indication lamps (RYB)-one set (For each incoming and outgoing ) Note : (i) Contractor has to get the approval of drawings of LT panel from the Engr In Charge /GE before commencement of work. (ii) Switch gear and connected items should be of approved make. (iii) Bottom portion of panel should be 45 CM above from the ground level. |
| 4 | Fabricate, supply, install, testing and commissioning of LT panel outdoor type 415 Volts, 50 Hz, 3 phase, 4 wire for accommodating the following accessories totally enclosed self supporting structure fully compartmentalized suitable for indoor use with bottom cable entry with suitable cable glands made out of CRCA sheet 3.15mm thick with angle iron frame works with suitable legs of ISA 50x50x5mm with four legs grouted PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for aluminium bus bars 600 Amps capacity, hinged door at front with suitable locking arrangement, provision of louvers at sides, CPRI approved, dust and vermin proof, powder coated and with following accessories suitable for incoming/outgoing arrangements complete all as specified and directed:- (a) 4 Pole MCCB 400 Amp, 50 Hz, 415 V with rupturing capacity 50 KA, Incomer -1 No(b) 4 Pole MCCB 200 Amp, 50 Hz, 415 V with rupturing capacity 36 KA,-01 No(c) 4 Pole MCCB 100 Amp, 50 Hz, 415 V with rupturing capacity 25 KA, -03 No(d) Digital Multifunctional VAF Meter -01Nos (e) CT\"s 400/5- set of 3 (g) LED type Indication lamps (RYB)-one set of 03 (for each incoming and outgoing)Note : (i) Contractor has to get the approval of drawings of LT panel from the Engr In Charge /GE before commencement of work. (ii) Switch gear and connected items should be of approved make. (iii) Bottom portion of panel should be 30 CM above from the ground level. |
| 5 | Fabricate, supply, install, testing and commissioning of LT panel outdoor type 415 Volts, 50 Hz, 3 phase, 4 wire for accommodating the following accessories totally enclosed self supporting structure fully compartmentalized suitable for outdoor use with bottom cable entry with suitable cable glands made out of CRCA sheet 3.15mm thick with angle iron frame works with suitable legs of ISA 50x50x5mm with four legs grouted PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for aluminium bus bars 600 Amps capacity, hinged door at front with suitable locking arrangement, provision of louvers at sides, CPRI approved, dust and vermin proof, powder coated and with following accessories suitable for incoming/outgoing arrangements complete all as specified and directed:- (a) 4 Pole MCCB 320 Amp, 50 Hz, 415 V with rupturing capacity 36 KA, Incomer -1 No(b) 4 Pole MCCB 125 Amp, 50 Hz, 415 V with rupturing capacity 25 KA-03 Nos(c) 4 Pole MCCB 200 Amps , 50 Hz , 415V with rupturing capacity 36 KA-01 Nos (d)Digital Multifunctional VAF Meter -01 nos(e) CT\"s 400/5- set of 3 No(e) LED type Indication lamps (RYB)-one set (for each incoming and outgoing)Note : (i) Contractor has to get the approval of drawings of LT panel from the Engr In Charge /GE before commencement of work. (ii) Switch gear and connected items should be of approved make. (iii) Bottom portion of panel should be 30 CM above from the ground level. |
| 6 | Fabricate, supply, install, testing and commissioning of LT panel Outdoor type 415 Volts, 50 Hz, 3 phase, 4 wire suitable for accommodating the following accessories totally enclosed self supporting structure fully compartmentalized suitable for outdoor door use with bottom cable entry with suitable cable glands made out of CRCA sheet 3.15mm thick with angle iron frame works with suitable legs of ISA 50x50x5mm with four legs grouted PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for aluminium bus bars 400 Amps capacity, hinged door at front with suitable locking arrangement, provision of louvers at sides, CPRI approved, dust and vermin proof, powder coated and with following accessories suitable for incoming/outgoing arrangements complete all as specified and directed:- (a) 4 Pole MCCB 320 Amp, 50 Hz, 415 V with rupturing capacity 36 KA, Incomer -1 No(b) 4 Pole MCCB 125 Amp, 50 Hz, 415 V with rupturing capacity 25 KA-01Nos (c) 4 Pole MCCB 100 Amp, 50 Hz, 415 V with rupturing capacity 25 KA-03 Nos (d) Digital Ammeter-01 No(e) Digital voltmeter (0-500V)-01 Nos (f) CT\"s 400/5- set of 3 No(e) LED type Indication lamps (RYB)-one setNote : (i) Contractor has to get the approval of drawings of LT panel from the Engr In Charge /GE before commencement of work. (ii) Switch gear and connected items should be of approved make. (iii) Bottom portion of panel should be 30 CM above from the ground level. |
| 7 | M&L for Earthing complete with galvanised earth plate electrode of size 600x600x6 mm thick burried directly in ground earth pit not less than 2.25 m below ground level with top edge of earth plate not less than 1.5 mtrs below ground level connected to 25X4 mm galvanised iron strip as earth lead upto a length of 7.5 metre long by means of bolts,nuts, washers etc and protected by GI pipe light grade 15mm dia and 20mm dia GI tubing light grade with funnel for watering, all as shown in electrical plate No 3 of SSR Part-I, back-fill with salt and charcoal, provision of test point including connected to earth test point and necessary earth work excavation in any type of soil PCC (1:3:6) type C1 bed and chamber RCC (1:2:4) type B1, iron grill including GI cover with hinge and funnel watering pipe etc all as specified and directed.Note:-(a)Earthing value should be less than 5 ohms.(b)If desired value of earth resistance not achieved during testing, the earthing work shall be redone by the contractor at free of cost to achieve the desire value of earthing resistance. The rate quoted by the contractor deemed to be inclusive of the provision. |
| 8 | Supply and laying in trenches, LT underground cable of size 10 Sqmm4 core XLPE insulated armoured and PVC sheathed 1100 Volts grade with aluminium conductor multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, roof, ducts and fixing using clamps, saddle for pole, wall including taking down complete all as directed. |
| 9 | All as per item No 8 here-in-before but 16 Sqmm 4 core |
| 10 | All as per item No 8 here-in-before but 25 Sqmm 3.5 core |
| 11 | All as per item No 8 here-in-before but 35 Sqmm 3.5 core |
| 12 | All as per item No 8 here-in-before but 70 Sqmm 3.5 core |
| 13 | All as per item No 8 here-in-before but 95 Sqmm 3.5 core |
| 14 | All as per item No 8 here-in-before but 120 Sqmm 3.5 core |
| 15 | All as per item No 8 here-in-before but 240 Sqmm 3.5 core |
| 16 | All as per item No 8 here-in-before but 300 Sqmm 3.5 core |
| 17 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes, foundation for poles etc., and getting out in hard/dense soil complete all as specified and as directed. |
| 18 | Returning, filling in excavated soil upto a depth of 30cm after riddling of excavated soil (in lieu of sand) for cushioning of cable and refilling of trenches with left over normal excavated soil including spreading, levelling, watering and well ramming in layers complete all as specified and as directed. |
| 19 | Removing surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed. |
| 20 | Supplying and laying un-reinforced precast concrete cable cover, class LV, Type 1 with peak, size 250 mm x 150mm x 40mm complete all as specified and as directed. |
| 21 | M&L for Plain Cement Concrete 1:4:8 type D2 (using 40mm graded stone aggregate) in foundation complete all as specified and as directed. |
| 22 | M&L for Plain Cement Concrete 1:3:6 type C1 (using 20mm graded stone aggregate) for stay and coping for poles including necessary form work to exposed surface finished smooth and even complete all as specified and as directed. |
| 23 | Supply and laying GI tubing light grade 50mm dia in trenches/fixing on pole /wall/crossing in drain etc. for protection of UG cable complete all as specified and as directed. |
| 24 | Supply and laying GI tubing light grade 80mm dia in trenches/fixing on pole /wall/crossing in drain etc. for protection of UG cable complete all as specified and as directed. |
| 25 | M&L for boring of holes under roof, pavement, hardstanding by trenchless technology and necessary machine including GI pipe of 50/80/100mm dia suitable for 0.4mpa working pressure complete all as specified and as directed. |
| 26 | Supply and fixing in repair of 9 metre high hot dipped octagonal poles with 130mm bottom dia & 70mm top dia made up of 3mm thick HT Sheet alongwith base plate of size 200x200x12mm including foundation bolts & bracket of size M20x600mm EN 8 grade \"J\" type foundation bolts and numbering of poles, in white paint over black painted back ground at a height of 1.5m from bottom of pole with 5 cm large bold letters 2\" (inch) wide etc including accessories as required including dismantling existing pole complete all as specified and directed. |
| 27 | Supply and fix in repair energy saving rectangular LED flood light fitting 150 Watts, 240 volts AC, cool white colour, CCT5700°K, CRI>70, THD<10%, system lumens not less than 100lumens/watt with innovative thermal management, available with multiple optics, equipped with IP-66 protection, 5 KV surge protection, aluminium die cast housing, life of luminaires should not be less than 50000 burning hours and suitable for large area lighting including fixing on High mast pole/Buildings/TARMAC poles etc. by means of clamps, nuts, bolts and any other accessories complete all as specified and as directed. |
| 28 | S&F in repair of 7 metre high hot dipped octagonal poles with 130mm bottom dia & 70mm top dia made up of 3mm thick HT Sheet alongwith base plate of size 200x200x12mm including foundation bolts & bracket of size M20x600mm EN 8 grade \"J\" type foundation bolts and numbering of poles, in white paint over black painted back ground at a height of 1.5m from bottom of pole with 5 cm large bold letters 2\" (inch) wide etc with accessories as required including dismantling existing pole complete all as specified and directed. |
| 29 | S&F in repair LED street light fitting 70/72 Watt 230 V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP-66 protection, CCT 5700K, lumen efficacy not less than 110 lumen/watts complete all as specified and directed. |
| 30 | S&F in repair aesthetically designed decorative hot dipped galvanised mild steel step pole of 3 mtrs with grey powder finish window - Plasma cut & Duly chamfered opening window of 300x10mm including taking down existing unserviceable pole and light fitting complete all as specified and directed. |
| 31 | S&F decorative arms in different designs, shaped and length to compliments in EROS LED Post tops and Poles family suitable for Orbit plus S round arm for pole complete all as specified and directed. Make : Havells / Polycab / Crompton/ Hallonix |
| 32 | S&F new generation IP 65 Post top energy saving environmental friendly long life aesthetically designed with good indirect symmetrical light distribution, die cast aluminium landscape luminaire with high power Victoria LED Posttop light as light source for LED Light of capacity 20 Watt suitable for pole of dia 76mm complete all as specified and directed. |
| 33 | S&F in repair, “Lithium based Energy Efficient Integrated Solar Street Light of 40Watt”in rust proof Aluminium housing with Monocrystalline Solar PV Panel of 75W(-0/+4W)Mono, Lithium Battery 12.8V, 42AH(BIS Certified), IP 65, High brightness W-LED(150 Lm/watt) lamp with Aluminium reflector for better light distribution,Color Temperature 6500K +500K, Microcontroller based charge controller cum driver, automatic dimming function( with PIR Motion Sensor), Dusk to Dawn Operation, suitable to working temperature: (-) 5 degree C to (+) 45degree C, Charging time 1 day and Autonomy 2 days with dimming Protections: Short Circuit, overload, Reverse polarity and battery protections. |
| 34 | S&F in repair of 6 metre high hot dipped octagonal poles with 130mm bottom dia & 70mm top dia made up of 3mm thick HT Sheet alongwith base plate of size 200x200x12mm including foundation bolts of size M20x300mm EN 8 grade \"J\" type foundation bolts and numbering of poles, in white paint over black painted back ground at a height of 1.5m from bottom of pole with 5 cm large bold letters 2\" (inch) wide etc with accessories as required including dismantling existing pole complete all as specified and directed. |
| 35 | S&F in repair glow signage boardswithbase frame made from angle iron and backside form ACP sheet 3mm thick with IP 68 Protection LED module, good quality virgin monomer Acrylic sheet, MES Logo & Southern Command logo in letters with 5 mm sun board channel, including complete wiring and power supply with IP 68 protection, each letter will be made with computer offset for having same letter style and type as approved by Engineer-in-charge, complete all as specified and directed for following boards :- (a) SUB STATION A (11/.440 KV) MILITARY ENGINEER SERVICES GARRISON ENGINEER (AF) YELAHANKA (b) SUB STATION B (11.440 KV) MILITARY ENGINEER SERVICES GARRISON ENGINEER (AF) YELAHANKA |
| 36 | M&L for hardcore of gauge not exceeding 63 mm of broken stone, deposited, spread and levelled in layers not exceeding 15 cm thick, watered and rammed to a true surface complete all as specified and directed. |
| 37 | M&L local sand dry, filling in trenches around, under ground cable complete all as specified and directed.NOTE: Consolidated thickness will be considered for the payment. |
| 38 | M&L for spreading/filling loose stone aggregate of 40mm graded broken stone or boulders complete all as specified and directed. |