|
| 1 | MV CablesLaying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/DWC/HUME/Metal pipe |
| 2 | Upto 35 sq. mm |
| 3 | Above 35 sq. mm and upto 95 sq. mm |
| 4 | Above 185 sq. mm and upto 400 sq. mm |
| 5 | Supply of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 6 | 3.5C x 300 Sq.mm. Aluminum XLPE armored cable |
| 7 | 3.5C x 95 Sq.mm. Aluminum XLPE armored cable |
| 8 | 3.5C x 70 Sq.mm. Aluminum XLPE armored cable |
| 9 | 3.5C x 50 Sq.mm. Aluminum XLPE armored cable |
| 10 | 4C x 6 Sq.mm. CU XLPE armored cable |
| 11 | CABLE TERMINATIONSupply and Providing heavy duty double compression brass gland and lugs end terminations,IP 66 complete,SIBG type, for the cable specified under above item with Bi-metallic lugs using crimping tool, Insulation tape, Identification tags etc., including end termination and Earthing of Gland. |
| 12 | 3.5C x 300 Sq.mm. Aluminum XLPE armored cable |
| 13 | 3.5C x 95 Sq.mm. Aluminum XLPE armored cable |
| 14 | 3.5C x 70 Sq.mm. Aluminum XLPE armored cable |
| 15 | 3.5C x 50 Sq.mm. Aluminum XLPE armored cable |
| 16 | 4C x 6 Sq.mm. CU XLPE armored cable |
| 17 | EARTHING |
| 18 | S/L SWG GI wire in ground:Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including soldering etc. as required |
| 19 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I.pipe from earth electrode including connection with G.I. nut,bolt, spring, washer excavation and re-filling etc. as required. |
| 20 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface forconnections etc. as required.Details of cost for 10 Metres |
| 21 | Supply, Installation, Testing and Commissioning of UL Listed maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 25.0 mm with copper coating thickness of 250micron tested as per IEC 62561-2 + Universal clamp (SS), 25mm + Earth conductivity enhancing mineral compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested OEC 2 25 + The above arrangements shall be provided with Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system Under floor earth inspection pit. Cost include to have earth pit cover, testing of all things, etc. in all complete manner. |
| 22 | DWC PIPESSupplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required. |
| 23 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 24 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 25 | 200 mm dia (OD-200 mm & ID-175 mm nominal) |
| 26 | DG SET FOR STPSupplying and erecting, commissioning and testing diesel generating set having continuous rating, 3 phase, 415 volts, 50 cycles A.C. supply comprising of a totally enclosed air/water cooled diesel engine with multi-cylinders developing suitable BHP not less than following capacity at 1500 RPM with 10% overload for one hour in 24 hours with standard accessories like fly wheel, lubricating oil cooler, \"A\" class governor, heavy duty fuel wheel and lubricating oil filter, oil bath air filler, lubricating oil pressure gauge, end exhaust manifold, standard set of tools with adjustable spanners, screw drivers, feeder gauge, cylinder head to cover, joint cylinder head to exhaust, element lube oil filter, 12/24 volts electric starting equipment complete with standard battery, dynamo, cut-outs, ammeter, necessary wiring, pressure gauge, starter etc and heavy duty Residential type exhaust silencer and vertical hot air duct both acoustic enclosure.logged with asbestos rope, save oil trays, exhaust piping of required length, standard wall/floor mounted fuel with level indicator and piping and drip proof alternator, self excited, self regulated, screen protected, with excitation system, capable of delivering the rated system output at 415 volts, 3 phase, 0.8 PF, 50 Hz, 4 wire, running at 1500 RPM, conforming to IS-4722- 1968 with voltage regulation +/- 5% of rated voltage from no load to full load. Both the engine and alternator fitted on a common fabricated steel base plate with antivibration mounting engine and alternator both connected to each other by flexible flange coupling and with floor/wall mounted control panel box comprising of voltmeter ammeter, selector switches, ACB / MCCB / MCB of adequate capacity, |
| 27 | indicator lamps duly wired with HRC fuses. The alternator & control panel shall be connected with provided suitable capacity armoured cable and complete with Acoustic enclosure (canopy) made out of 18 SWG CRCA Sheet, sound absorbing material Rockwool of 64 density & 100 mm thick conforming to IS:8183 The resin bonded rockwool covered from inside the canopy by perforated sheet with 3/4 mm holes, sound level not more than 75 dB at a distance of 1 mtr, as per PVCT norms. Erection, commissioning and satisfactory testing as per requirement with first filling of fuel, oil, etc. with guarantee of complete system for One year. & with obtaining all necessary certificate from Electrical Inspector. The Capacity and Ratings of DG sets are as below. Scope also includes as per below:To submitt drawing showing , overall lay out with dimensions, plan, elevations an sections and got approved prior to commencing of manufacturing.To submit drawing showing, SLD with rating of equipemnts / make etc., and got approved prior to commencing of manufacturing. DG SET should be complied as per latest CPCB Norms. |
| 28 | The scope includes to test the DG set for factory test witnessed by Owner represantative prior to dispatch of following:-1. Load trial test for equal ratings of load for continous 4 Hrs.2. Sudden shock load at every One hour during above test.3. Vibration Test4. Noise level test.5. Fuel gas analysis.6. Delta ` t \" inside acoustic enclosure.(2) Delivery of the DG set at site.(3)Specific Fuel Consumption Test(4) Unloading of the DG set at Required Location of Installation & test at manufacture\"s place.(5) Technical support & supervision during commissioning of DG Set & Synchronizing Panel.(6) To get Battery charged and to test Battery charger.(7) Testing of the DG Set with Supply of Consumable.(8) Painting of the parts damaged during Transportation or Installation(9) Power & Control cabling between D.G. Panel & D. G. Set, syncronising Panel & alternator to ACB/MCCB inside the enclosure.(10) D.G. set should have exhaust chimney of Suitable Length (AS PER LATEST CPCB NORMS/LOCAL NORMS) as per statutory requirement with suitable M.S. structure complete between exhaust of engine till out let point for discharging fuel gas. Drawing of which should be submitted for approval.(Necessary cost to shall be included.) If required Contractor has to visit site and accordingly rate shall be included.(11) The rate quoted shall be for the entire job including exhaust piping complete up to trial test. No extra rates to be quoted for any items for the DG set.(12) The day tank must be part of acoustic enclosure. No external fuel tank required. |
| 29 | 13) All Necessary control cables of between DG set, AMF panel/Sync Panel, MLTP and Battery charger shall be part of supply. Necessary BOM shall be submitted during approval process.14)To prepare & submit as-built drawing and handing over document to end user.15) Scope also includes preparing necessary drawing submitting to authorities, getting their approval / sanction and final certificate including NOC from pollution board(if required) to energize the D G Set.16)DG vendor has to arrange for inspection and factory acceptance test as detailed in specification. The Item shall include TO and FRO travelling economy class Air ticket/second class AC/Air-conditioned car, whichever feasible from the port of boarding of client/consultant lodging/boarding as necessary for at least three representatives of client/consultant.(Suitable up to 3583m Altitude) |
| 30 | Supply of Prime duty 160 KVA DG set, acoustic enclosure suitable for 75 db(A) sound level reduction to be measured at 1 mtr. from the enclosure. Cost should cover D.G. set control panel, necessary control and metering, control & power wiring, indication /annunciation & other accessories. (DG SET Shall be worked Satisfactory at 3583m Altitude) |
| 31 | Providing & erecting approved make AMF control panel suitable for following size of 3 phase, 415 V, 50 cycles, A.C. diesel generating set along with required MCCB protection complete of scope as detailed below: 1) Power module: A pair of electromechanically interlocked contactors (for mains & generator) Overload relay for generator contactor Neutral contactor for mains and generator Power socket for connections.2) Control and metering module: Line voltage monitor. Generator voltage monitor Ammeter 3 items attempt start facility. Air circuit breakers/MCB/MCCB of suitable rating for auto/manual operation. Auto/manual switch. Emergency stops push buttons. Manual start push button. frequency meter. Engine hour meter. Two earthing studs.3) Protection module: The engine shutdown in the unlikely event of Low lube oil pressure High cylinder head temperature. V belt failure.4) Indicators with alarm Load on generator.5) Indicators Load on mains Engine fails to start . Emergency stop battery charger.The AMF Panel of following capacity(Suitable up to 3583m Altitude)AMF Control Panel for 160 KVA, 3 phase DG Set |
| 32 | Earthing for DG Set |
| 33 | Supply, Installation, Testing and Commissioning of UL Listed maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 25.0 mm with copper coating thickness of 250micron tested as per IEC 62561-2 + Universal clamp (SS), 25mm + Earth conductivity enhancing mineral compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested OEC 2 25 + The above arrangements shall be provided with Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system Under floor earth inspection pit. Cost include to have earth pit cover, testing of all things, etc. in all complete manner. |
| 34 | Providing and fixing earth bus of 25 mm X 5 mm copper strip in 40mm dia G.I pipe from earth electrode including connection with brass nut bolt spring washer excavation and refilling etc. as required |
| 35 | Providing and fixing earth bus of 25 mm X 5 mm G.I strip in 40mm dia G.I pipe from earth electrode including connection with brass nut bolt spring washer excavation and refilling etc. as required |
| 36 | LT PANELSupply, Installation testing & commissioning of medium Voltage sheet steel metal clad, compartmented cubicle Panel board.Shifting of panels from site store to the suitable location.Installation of panel in Electric room or as located in electrical drawings or as per site conditions, including removing packing etc.Earthing all components, frame etc. to a common internal earth bar.Connection, testing & commissioning.Electrical contractor shall carry out the insulation test at site & all the readings shall be submitted in duplicate to the consultant or engineer-in-charge.Supply, installation, testing and commissioning all accessories, supporting structure, hard ware etc to complete the job.Supply, installation, testing and commissioning of necessary tools, hard ware, testing hard ware, testing equipment etc.The rates for the distribution boards apart from the Breakers and instruments shall also include the following :This schedule of Quantities shall be read in conjuction with the technical specification, General & Special conditions as well as all tender drawings.Supporting rigid steel framework.Cubicle type, 14 gauge CRCA sheet steel enclosed.Proper bonding to earth.Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its circuit diagram.Providing cable clamps / supports within distribution boards cable alley.TPN ACB’s / MCCB’s shall mean 3 pole ACB’s / MCCB’s with adequate size of neutral link. |
| 37 | All MCB’s shall be of minimum 10 KA breaking capacity.The breaking capacity of MCCB’s are mentioned panel wise. All MCCB’s shall be with thermal magnetic releases upto 250 amps and miroprocessor based above 250 amps capacity, unless specified otherwise.All motor feeders MCCBs shall be of motor duty.Distribution panels shall be Powder Coated with Siemens gray paint shade no. RAL-7032 of IS-5.Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993.IP 54 for all Indoor panel.IP 65 and double door for all outdoor panel.All MCCB’s shall be provided with operating mechanism for door interlock.All measuring instruments (Meters) shall be of digital electronic with LED of approved make.All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.All panels shall have provision of the following:Pad locking of Switch board doors.Pad locking of MCCB’s handles in “OFF” Position.All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D characteristic. All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier formation.SPD as shown in SL |
| 38 | Supply, Installation, testing and commissioning of 200A FP ATS Box with Weatherproof enclosure for STP |
| 39 | Supply, Installation, testing and commissioning of IP 54 rated APFC PANEL FOR - 65 KVAR for STP Having,Incomer : 125A FP MCCB ADJUST. TM BASED RELEASE (01NOS.)1 NO SPD (01 Nos).1 NO. DIGITAL VOLTMETER WITH VOLTAGE SELECTOR SWITCH1 NO. DIGITAL AMP METER WITH AMETER SELECTOR SWITCHINDICATION LAMP- 6 NOS (R,Y,B,ON,OFF,TRIP)3Nos. CT 125/5A CL-1,15VA Out Going : 63 Amp TP 16KA MCB (01Nos) - 25 KVAR40 Amp TP 16KA MCB (03Nos) - 15 KVAR16 Amp TP 16KA MCB (02Nos) - 5 KVAR Capacitor Bank (APP TYPE) (01Nos. 25KVAR)Capacitor Bank (APP TYPE) (02Nos. 15KVAR) Capacitor Bank (APP TYPE) (02Nos. 5KVAR)CONTRACTOR TO REFER SLD & DETAIL TECHNICAL SPECIFICATION ALONG WITH THIS. ALL SHOULD BE AS PER SLD & REQUIREMENT. |
| 40 | LIGHTNING PROTECTION SYSTEMContractor to design lightening protection system along with SITC work. Contractor also need to submit Risk Analysis report based on site condition and location. Contractor to take soil resistivity report and necessary consideration to be taken along with below items. In general, the complete system design and installations shall confirm to latest IEC/IS Standards and the specifications, drawings submitted here with. Quantity and items mentioned here under is just for reference; Bidder shall be responsible to calculate the exact quantity as per design requirements for each item during bidding. The bidder shall include all necessary accessories to comply the installation and design to IS/IEC 62305 requirements, which broadly includes all system requirement. Termination |
| 41 | AIR TERMINAL :Supply, Installation, Testing and Commissioning of 8 mm Aluminum Round Conductorcomplete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185part 202) & VDE 0185-305 (IS/IEC 62305) . |
| 42 | Supply, Installation, Testing and Commissioning of Roof conductor holder for sheet asspecified indrawing , Bottom section made of stainless steel(V2A) & conductor holder made up of polyamide with Ø 8.5 mm slot at bottom. |
| 43 | Supply, Installation, Testing and Commissioning of cross universalconnector: For T andcrossconnection, to route vertical down conductor /mesh formation made of hot dipped galvanisediron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8hexagonal nuts . |
| 44 | Supply, Installation, Testing and Commissioning of expansion piece with connector: Forequalising temperature related length changes. Necessary on conductors length over 20meters. |
| 45 | Supply, Installation, Testing and Commissioning of Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised. Conforms to the requirements according to DIN VDE 0185-305 (IS-IEC 62305) (2 Nos for expansion Pieces) |
| 46 | Supply, Installation, Testing and Commissioning of 1 mtr vertical air terminal with mountingaccessories on the flat surface to meet the requirements of IS/IEC 62305. Tested forElectrical , mechanical and chemical as per IEC 62561. |
| 47 | DOWN CONDUCTOR |
| 48 | Supply, Installation, Testing and Commissioning of 8 mm Aluminum Round Conductorcomplete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185part 202) & VDE 0185-305 (IS/IEC 62305) . |
| 49 | Supply, Installation, Testing and Commissioning of Roof conductor holder for parapet- Polyamide Conductor holder: With M8 female thread ordiameter7mm, M8Screw to connect the conductor holder.Weather andtemperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance. |
| 50 | Supply, Installation, Testing and Commissioning of Test Joint (Folding Clamp) suitable to connect 8mm round conductor and max by 30x3 mm GI strip as specified in drawing and directed by Engineer OBO Type No. 271 8-10 ( 5317401 ) or equivalent as per make. |
| 51 | Supply, Installation, Testing and Commissioning of Lightnig counter - To count no of lightning strike & it can record the date and time of the lightning incident also tested as per IEC 62561-6. |
| 52 | RING & VERTICAL EARTHING SYSTEM |
| 53 | Supply, Installation, Testing and Commissioning of Galvanised Steel Flat 30X3 mm thicknessfrom earth electrode directly in ground as required. Flat conductor shall be of Hot Dipped &Cross sectional area of 90mm square Accordingto DINEN 50164-2 (VDE 0185 part 202) Meets therequirement of VDE0185/305(IS-IEC 62305) Zinc coating: 500 g/m square (Approx :70 micron coating) Should be tested andused exclusively for lightning protection earthing system and ring equipotential bonding. |
| 54 | Supply, Installation, Testing and Commissioning of cross connector flat/flat without adapter plate FT • Meets the requirements of VDE 0185-305-3 (IEC/ EN 62305-3) • Fit: Max. FL 30 x FL 30 or max. FL 40 x FL 40• Without adapter plate• Mounted with 4 hexagonal bolts M8 x 25 and 4 hexagonal nuts M8 (F) |
| 55 | Supply, Installation, Testing and Commissioning of flat conductor holder suitable for FL 30. Installed with 2 hexagonal bolts. |
| 56 | EARTH KIT. |
| 57 | Supply, Installation, Testing and Commissioning of UL Listed maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 25.0 mm with copper coating thickness of 250micron tested as per IEC 62561-2 + Universal clamp (SS), 25mm + Earth conductivity enhancing mineral compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested OEC 2 25 + The above arrangements shall be provided with Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system Under floor earth inspection pit |
| 58 | SURGE PROTECTION DEVICES |
| 59 | Supply, Installation, Testing and Commissioning of combination surge arresters Class B+Caccording to IEC 61643-1 for the lightning protection zone 0-2 consisting of din mountable -one common base consisting of 1 numbers of modular pluggable units of high energyvaristorbased technology to be connected between line to neutral and 1 number of GDT to beconnectedbetween neutral to earth complying the below technical parameters:a) Nominal voltage between L-N, Un = 230 voltsb) Maximum continuous operating voltage between L-N, Uc = 320 voltsc) Maximum continuous operating voltage between N-PE, Uc = 255 voltsd) Lightning Impulse Current (L-N), Iimp (10/350 micro sec) = 7 KAe) Lightning Impulse Current (N-PE), Iimp (10/350 micro sec) = 25 KAf) Nominal discharge current In (8/20 micro sec), (N-PE) = 30 KAg) Max discharge current Imax (8/20 micro sec), (L-N) = 50 KA&(N-PE) = 50 KAh) Voltage Protection Level, Up = < 1.3 KV (L-N), < 1.2 KV (N-PE)i) Response time, tA = < 25 (L-N) &< 100 (N-PE) nano secondsj) Working condition of the SPD - Visual indication = Green “OK” & Red “Failure”k) Temp Range, -40° C to +80° C l) Degree of Protection IP 20 |
| 60 | O & M FOR 5 YEARS |
| 61 | Operation and maintanance for 5 year for all parts as per above BOQ Please Enable Macros to View BoQ information |