| 1 | Excavation in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth; taking out/laying LT cables, foundation of pole etc. not exceeding 10sq.m on plan and getting out including forming bottom surface in soft/loosesoil complete all as specified and as directed. |
| 2 | Excavating in trenches. n exc 1.5 m wide anddepth exc 1.5m and not exc 3m, for foundation, etcn exc 10 sq m on plan and n exc 1.5 m in depth and getting out soft/loose soil complete all as specified and as directed. |
| 3 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cmcomplete all as specified and as directed. |
| 4 | Removing excavated materials to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point, complete all as specified. |
| 5 | Supply and layingdry river sand cushioning UG cable protection under floor in foundation including watering and consolidation and for cable protection with a layer of 8cm deep before laying and 15cm after layinggently punned down to 10 cm on top of the cable as per SSR Part-I complete all as specified and as directed. (Note : Punned thickness shall be measured). |
| 6 | M&L for bricks protection cover to under ground cable with sub class \"B\" old size over burnt bricks laid dry and flat across the axis of cable, abutting each other with gaps between adjacent bricks not exceeding 10mm complete all as specified and as directed. |
| 7 | Supply and fixing / Laying, connecting, testing and commissioning of LT under ground cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric cable (heavy duty) with multistranded aluminium conductor, 1100 volt garde, cross sectional area 50 Sqmm x 3.5core, laid in trenches/on wall/poles laid in ducts/inside protection pipe including cable glands,lugs and suitable size of MS saddle clips (where ever cable laid in ceilings / walls without cable duct) complete all as specified and as directed. |
| 8 | Supply and fixing / Laying, connecting, testing and commissioning of LT under ground cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric cable (heavy duty) with multistranded aluminium conductor, 1100 volt garde, cross sectional area 70 Sqmm x 3.5core, laid in trenches/on wall/poles laid in ducts/inside protection pipe including cable glands,lugs and suitable size of MS saddle clips (where ever cable laid in ceilings / walls without cable duct) complete all as specified and as directed. |
| 9 | Supply and fixing / Laying, connecting, testing and commissioning of LT under ground cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric cable (heavy duty) with multistranded aluminium conductor, 1100 volt garde, cross sectional area 120 Sqmm x 3.5core, laid in trenches/on wall/poles laid in ducts/inside protection pipe including cable glands,lugs and suitable size of MS saddle clips (where ever cable laid in ceilings / walls without cable duct) complete all as specified and as directed. |
| 10 | Supply and fixing / Laying, connecting, testing and commissioning of LT under ground cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric cable (heavy duty) with multistranded aluminium conductor, 1100 volt garde, cross sectional area 185 Sqmm x 3.5core, laid in trenches/on wall/poles laid in ducts/inside protection pipe including cable glands,lugs and suitable size of MS saddle clips (where ever cable laid in ceilings / walls without cable duct) complete all as specified and as directed. |
| 11 | Supply and fixing / Laying, connecting, testing and commissioning of LT under ground cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric cable (heavy duty) with multistranded aluminium conductor, 1100 volt garde, cross sectional area 240 Sqmm x 3.5core, laid in trenches/on wall/poles laid in ducts/inside protection pipe including cable glands,lugs and suitable size of MS saddle clips (where ever cable laid in ceilings / walls without cable duct) complete all as specified and as directed. |
| 12 | Supply and fixing / Laying, connecting, testing and commissioning of LT under ground cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric cable (heavy duty) with multistranded aluminium conductor, 1100 volt garde, cross sectional area 300 Sqmm x 3.5core, laid in trenches/on wall/poles laid in ducts/inside protection pipe including cable glands,lugs and suitable size of MS saddle clips (where ever cable laid in ceilings / walls without cable duct) complete all as specified and as directed. |
| 13 | Supply fixing as in repair steel tubular swaged pole 9.00m long Type -410 SP-31 conforming to IS-2713 part I to III 1980 with and including cast iron base plate, finial taper plug,nuts, bolts and washers etc. and fixed into plain cement concrete foundation duely painted with two coats of aluminium paint over one coat of red oxide primer including preparetion of surfaces and making strip 150mm wide upto 1.50m (above PCC coping) by black, yellow paint in alternate layers and pole nos.including dismantling of old poles of any descriptionincluding demolition of concrete foundation complete all as specified and directed. NOTE: Earth work, cement concrete will be measured and paid seperately. |
| 14 | M&L for plain cement concrete (1:3:6) type C2 (40mm graded aggregate) as in foundation for filling in mass concrete for pole and stay complete all as specified and directed. |
| 15 | M&L for plain cement concrete (1:2:4) type B-1(using 20 mm graded crushed stone aggregate)as in coping of pole etc including form work complete all as specified and directed. |
| 16 | M&L formaking hole 150mm bore by suitable means for insertion of GI pipe 80mm bore for passing cable across the road withoutcutting the road complete all as specified and as directed. |
| 17 | S&F in repair, MCCB 630 Amps, 415 Volt, 50 KA, 4 pole with adjustable thermal &magnetic trip setting unit complete all as specified and directed. |
| 18 | S&F in repair, MCCB 400 Amps, 415 Volt, 36 KA, 4 pole with adjustable thermal & magnetic trip setting unit complete all as specified and directed. |
| 19 | S&F in repair, MCCB 250 Amps, 415 Volt, 36 KA, 4 pole with adjustable thermal &magnetic trip setting unit complete all as specified and directed. |
| 20 | S&F in repair, MCCB 200 Amps, 415 Volt, 36 KA, 4 pole with adjustable thermaltrip setting unit complete all as specified and directed. |
| 21 | M&L for replacement of galvanised tubing light grade of 80 mm dia laid in trenches or fixed to pole and / or laid under road in any position with necessary clamp nut and bolt etc complete all as specified and directed. |
| 22 | M&Lfor replacement of Cross arms bracing supports clamps and back plate fabricated from structural steel section including nuts bolts washers welding bending cold or hot drilling holes for bolts in any shape & size as indicated or directed and including of one primer coat one under coat one finishing coat with saluminium paint includin taking down old unserviceable cross arms complete all as per specified and directed. |
| 23 | M&Lfor replacement of pin type porcelain vitreous white brown or green insulator including one galvanised mild steel spindle two galvanised iron washer and one galvanised iron nut 100 mm height , 65 mm dia for 1100 volts grade complete all as per specified and directed. |
| 24 | M&L for aluminium conductor, steel reinforced (ACSR) of any size as approved on LT Poles including straining, binding to insulators with aluminium binding wire with connectors, etc, providing PVC sleeves for jumpers as in OH conductors including dismantling of old ACSR conductors of any size and description from pole complete all as specified and as directed. |
| 25 | Supply, install, test and commission LT Panel board, TPN 415 Volts, 50 Hz,out door cubical type floor mounted CPRI approved factory made,double doordust and vermin proofIP-54, fabricatedout of CRCA sheet not less than 3.15 mm thickwith 2mm thick for internal compartment duly powder coated fixed on angle iron pedestalmade out of 50x50x6 mm with cable chamberfor individual feeders for incommingand outgoing connections,one set of LED indicator lampRYB with switch and fuse and the panel board shall be provided with proper ventillation including suitable size of cable alley aluminium bus bar suitable for carrying of current 400 Amps with suitable connections from MCCB out going to main bus bar shall be carried out with TPN aluminium bus bars of suitable rating and connections from main bus bar to out going MCCB\"s (intake point) will be carried out with TPN aluminium bus bar as per MCCB rating duly insulated and colour coded heat shrinkable sleeve and shall be rigidly mounted on suitable size of bridge insulator including necessary PCC foundation of minimum 0.50 m height positioned and fixed with suitable nut, bolts, washers etc to the MC pedestal all as specified and directed comprising of the following :-Item continued to Srl item No.25.10 |
| 26 | Item continued from Srl item No.25.00(a) MCCB 400 Amps 4 Pole 50 Hz 415 V with thermal magnectic& adjustable Magnetic type capacity 36 KA - 1Nos (Incoming).(b) MCB 250 Amps 4 pole, 50 Hz, 415 Volt ith adjustable thermal & Fixed magnetic type, 36 KA - 01 Nos (Outgoing).(c)MCB 160 Amps 4 pole, 50 Hz, 415 Volt ith adjustable thermal & Fixed magnetic type, 36 KA - 02 Nos (Outgoing).(d) 3Ph digital multi function meter modelA, class 1, 5A with relay Vega Series - 1Nos(e) Indicating lamp 240 volts LED type - set of three. |
| 27 | Supply, install, test and commission LT Panel board, TPN 415 Volts, 50 Hz,out door cubical type floor mounted CPRI approved factory made,double doordust and vermin proofIP-54, fabricatedout of CRCA sheet not less than 3.15 mm thickwith 2mm thick for internal compartment duly powder coated fixed on angle iron pedestalmade out of 50x50x6 mm with cable chamberfor individual feeders for incommingand outgoing connections,one set of LED indicator lampRYB with switch and fuse and the panel board shall be provided with proper ventillation including suitable size of cable alley aluminium bus bar suitable for carrying of current 400 Amps with suitable connections from MCCB out going to main bus bar shall be carried out with TPN aluminium bus bars of suitable rating and connections from main bus bar to out going MCCB\"s (intake point) will be carried out with TPN aluminium bus bar as per MCCB rating duly insulated and colour coded heat shrinkable sleeve and shall be rigidly mounted on suitable size of bridge insulator including necessary PCC foundation of minimum 0.50 m height positioned and fixed with suitable nut, bolts, washers etc to the MC pedestal all as specified and directed comprising of the following :-Item continued to Srl item No.26.10 |
| 28 | Item continued from Srl item No.26.00(a) MCCB 315 Amps 4 Pole 50 Hz 415 V with thermal magnectic& adjustable Magnetic type capacity 36 KA - 1Nos (Incoming).(b) MCB 200 Amps 4 pole, 50 Hz, 415 Volt ith adjustable thermal & Fixed magnetic type, 36 KA - 01 Nos (Outgoing).(c)MCB 160 Amps 4 pole, 50 Hz, 415 Volt ith adjustable thermal & Fixed magnetic type, 36 KA - 01 Nos (Outgoing).(d) 3Ph digital multi function meter modelA, class 1, 5A with relay Vega Series - 1Nos(e) Indicating lamp 240 volts LED type - set of three. |
| 29 | M&L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6mm thick buried directly in ground vertically [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized earth strip 25mm x 4mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 3 of MES SI Part I all as specified and testing on completion earth plate sourrounded by adequate quantity of charcoal dust and comman salt to a packed thickness of 15cm on all sides connected to GI strip/ copper strip includingprovisionof earth lead protected by 40 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work, PCC pit with RCC cover, char coal, salt, funnel etc including taking down old earthing complete all as specified and as directed.Note:- Rate quoted by tenderers shall be deemed to include for following provisions- [i]. Excavation & earth work in any type of soil including removing of surplus material upto 50 m. [ii].PCC 1:3:6 type C1 using 20mm graded stone aggregate in pit & 40mm thick precast RCC 1:2:4 type B1 cover 54x54x5 cm with 8mm TMT bars @ 15 cm C/C both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel. [iii]. Main earthing lead from earth electrode to test point upto 7.5 mtr.[iv]. Funnel with watering pipe [GI pipe] 20mm bore medium grade & copper lugs, charcoal & salt as reqd[v]. GI protection pipe of size 40 mm bore light grade. |
| 30 | Supplying, installing, commissioning and tastingin repair factory made outdoor type LT Kiosk box with canopyof size 1000mmx600mmx450mm made out of 3.15mm thick CRCA sheet duely powder coatedwith 4 nos 300 Amps copper busbarand 4 nos Mild steel legs of size 40mmx40mmx5mm of length 1000 mmand locking arrangement with one Nos of MCCB of 250 Amp 4 pole 36 KAas incomming includinggroutingin PCC 1:3:6 type C-1complete all as specified and directed. |
| 31 | M&L for scrapping, cleaning, including necessary preparation of old steel surfaces of LT pole of full length including cross arms (outer/inner surface and applying two coats of synthetic enamel paint of provide shade over one coat of red oxide/zinc chrome primer through spare/machine including wiring of pole no and symbols of HT/LT complete all as specified and a directed. |
| 32 | M&L for scrapping, cleaning, including necessary preparation of old steel surfaces of LT panel of any size (outer surfaces) and applying two coats of synthetic enamel paint of approved shade provide one coat of red oxide/inc chrome primer complete all as specified and as directed. |
| 33 | Taking down carefully copper / Aluminium point wiring including (light, fan, socket or power complete fittings, such as switches, ceiling roses, pendant holders, Batten holders, shades conical fan regulators, light or power sockets etc) removing materials from site and making good disturbed surfaces of walls roofs etc complete all as specified and as directed. |
| 34 | M&L for concealed point wiring complete with 1.5 Sqmm single core multistranded copper conductor PVC insulated and unsheathedFRLSH cable 1100 volts grade drawn through and including non metallic rigid PVC Concealed conduit medium grade minimum 20 mm dia ISI marked and conduit accessories fixed on recesses of wall/ceiling/roof and chisselling on wall complete andmaking good the disturbed surfaces of wall / ceiling by cement mortar 1:4 including painting to existing surfaces etc with sunken type pressed steel/welded MS terminal boxes made out of 1.25 mm MS sheet for mounting of fittings like switch, socket and fan regulator with 3mm thick hylum laminated sheet cover including cutting chases pining in for concealed conduit wiring amd making good of disturbed surface complete for One light/ Fan/bell point controlled by one no one way switch complete all as specified and as directed. |
| 35 | Supply and fixing Modular switch one way 10 Amp, single pole, 240 Voltscomplete all as specified and as directed. |
| 36 | Supply and fixing ceiling rose surface bakelite two to three terminal65 x 50 mm three terminal 250/230 volts ISI markedcomplete all as specified and as directed. |
| 37 | Supply and fixing in repair LED luminaire600 mm x 600 mm, 40 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for false ceiling including connecting up with driver three core flexible copper conductor cases or suitable sizecomplete all as specified and as directed. |
| 38 | Supply and fixing in repair LED invertor lights fitting 1x 208W, 220V, AC, decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed. |
| 39 | M&L for sub main wiring concealed with two run of single core 6 Sqmm (FRLSH) PVC insulated and unsheathed cable with copper conductor (multi stranded) 1100 volts grade, ISI marked drawing in and including PVC rigid non metalic PVC concealed and conduit of adequate size with proper colour coding and making electric connections & accessories like bends, tee, etc fixed on recess of wall and ceiling and connecting to earth dolly and including one run 6 Sqmm earth wire, FR PVC insulated & unsheathed copper conductor including taking down old submain wiring of any type, complete all as specified and as directed. NOTE: (i) Quoted shall deemed to be included for cutting and chasing for conduits and sinking for boxes, making holes in wall/floor for passing through conduit and making good to wall/concrete/floor etc (ii) 2 runs of main wire, 1 run of earth wire, 1 run of PVC Conduit with accessories shall be measured as one length. |
| 40 | M&L for sub main wiring concealed with two run of single core 4 Sqmm (FRLSH) PVC insulated and unsheathed cable with copper conductor (multi stranded) 1100 volts grade, ISI marked drawing in and including PVC rigid non metalic PVC concealed and conduit of adequate size with proper colour coding and making electric connections & accessories like bends, tee, etc fixed on recess of wall and ceiling and connecting to earth dolly and including one run 4 Sqmm earth wire, FR PVC insulated & unsheathed copper conductor including taking down old submain wiring of any type, complete all as specified and as directed. NOTE: (i) Quoted shall deemed to be included for cutting and chasing for conduits and sinking for boxes, making holes in wall/floor for passing through conduit and making good to wall/concrete/floor etc (ii) 2 runs of main wire, 1 run of earth wire, 1 run of PVC Conduit with accessories shall be measured as one length. |
| 41 | Supply and fixing as in repair factory made board distribution in sheet steel enclosure double door glazed with 200 Amps ratedbus bar, SPN, 12 ways, 240 Volts suitable for housing MCBs.complete all as specified and as directed. Note : Quoted rates deemed to be included concealed fittings of DBs and make good the disturbed surface and painting with same colour after fitting DBs. |
| 42 | Supply and fixing as in repair factory made board distribution in sheet steel enclosure double door glazed with 200 Amps ratedbus bar, SPN, 8 ways, 240 Volts suitable for housing MCBs.complete all as specified and as directed. Note : Quoted rates deemed to be included concealed fittings of DBs and make good the disturbed surface and painting with same colour after fitting DBs. |
| 43 | Supply and fixing as in repair of Vertical TPN 4 Way, 415 volt with provision and including of MCB of 63Amp, 4 pole, C curve and provided with CRCA sheet steel powder coated, double door ready to use DBs provided with insulated vertical phase bus bar, neutral bal,. earth bar, sticking saddle, colour coded interconnecting wire set, cable ties, blanking plates etc complete all as specified & as directed.Note : Quoted rates deemed to be included concealed fittings of VTPN and make good the disturbed surface and painting with same colour after fitting VTPN. |
| 44 | Supply and fixing as in repair of Vertical TPN 4 Way, 415 volt with provision and including of MCCB of 125Amp, 4 pole, C curve and provided with CRCA sheet steel powder coated, double door ready to use DBs provided with insulated vertical phase bus bar, neutral bal,. earth bar, sticking saddle, colour coded interconnecting wire set, cable ties, blanking plates etc complete all as specified & as directed.Note : Quoted rates deemed to be included concealed fittings of VTPN and make good the disturbed surface and painting with same colour after fitting VTPN. |
| 45 | Supply and fixing as in repair MCB, TPN, 415 volts, B Curve, 40 Amps, 10 KA, complete all as specified and as directed. |
| 46 | Supply and fixing as in repair MCB, SP, 240 volts, C Curve, 10-32 Amps, 10 KA, complete all as specified and as directed. |
| 47 | M&L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6mm thick buried directly in ground vertically [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized earth wire of 4mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 3 of MES SI Part I all as specified and testing on completion earth plate sourrounded by adequate quantity of charcoal dust and comman salt to a packed thickness of 15cm on all sides connected to GI wire includingprovisionof earth lead protected by 40 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work, PCC pit with RCC cover, char coal, salt, funnel etc including taking down old earthing complete all as specified and as directed.Note:- Rate quoted by tenderers shall be deemed to include for following provisions-[i]. Excavation & earth work in any type of soil including removing of surplus material upto 50 m. [ii].PCC 1:3:6 type C1 using 20mm graded stone aggregate in pit & 40mm thick precast RCC 1:2:4 type B1 cover 54x54x5 cm with 8mm TMT bars @ 15 cm C/C both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel. [iii]. Main earthing lead from earth electrode to test point upto 7.5 mtr.[iv]. Funnel with watering pipe [GI pipe] 20mm bore medium grade & copper lugs, charcoal & salt as reqd[v]. GI protection pipe of size 40 mm bore light grade. |
| 48 | M&L for earthing complete with copper earth plate of 60 cm x 60 cm x 3mm thick buried directly in ground vertically [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to copper strip of 20x3mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 3 of MES SI Part I all as specified and testing on completion earth plate sourrounded by adequate quantity of charcoal dust and comman salt to a packed thickness of 15cm on all sides connected to copper strip includingprovisionof earth lead protected by 40 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work, PCC pit with RCC cover, char coal, salt, funnel etc including taking down old earthing complete all as specified and as directed.Note:- Rate quoted by tenderers shall be deemed to include for following provisions-[i]. Excavation & earth work in any type of soil including removing of surplus material upto 50 m. [ii].PCC 1:3:6 type C1 using 20mm graded stone aggregate in pit & 40mm thick precast RCC 1:2:4 type B1 cover 54x54x5 cm with 8mm TMT bars @ 15 cm C/C both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel. [iii]. Main earthing lead from earth electrode to test point upto 7.5 mtr.[iv]. Funnel with watering pipe [GI pipe] 20mm bore medium grade & copper lugs, charcoal & salt as reqd[v]. GI protection pipe of size 40 mm bore light grade. |