| 1 | Supply, installation, testing & commissioning of factory assembled silent Diesel Engine driven generating set 1500 RPM of capacity 40 KVA, 3 phase, 4 wire, 415 volt, 0.8 PF (MSL complete with control panel including integrated powder coated accoustic enclosure as per CPCB regulations and duly certified by agencies / labs designated by CPCB for noise and sound pollution level, etc floor mounted including PCC foundation as per manufacturer\"s instructions complete all as specified and directed and comprising of the following :- (Note: main power house) DIESEL ENGINE required capacity for driving 40 KVAin the ambient conditions of Pathankot (Punjab) alternator multi cylinder, vertical type, 4 stroke, water cooled, electric start conforming to IS : 10001/10002/BS-5514 for continuous running capable of taking 10% overload for one hour in 12 hours complete and comprising of the following:- (i) Radiator cooling(ii)Radiator fan with guard (iii)Flywheel with starter ring (iv)Air cleaner oil bath type(v) Vacuum indicator(vi)Electronic governor class 1A(vii) Exhaust silencer(viii) Fuel filters & fuel pipelines including fuel flow meter (ix) Fuel injection pump (FIP)(x)Fan & water pump assembly (xi)Lub oil filter & Pump(xii)Oil filter (xiii)Exhaust gas driven turbo charger(xiv) Lub oil cooler(xv)Engine maintenance manual with spare parts list (xvi) Suitably designed accoustic enclosure as per CPCB regulations.(xvii) Engine safety shut down system against low lub oil pressure and high water pressure. (xviii) Electric starting system with battery charging alternator and axial type starter motor including adequate number of high capacity maintenance free lead acid battery 12 volts 140 AH including interconnecting cables/ leads with terminals complete with starting/ stopping switch, volt meter etc - 01 Set.(B) ENGINE INSTRUMENT PANEL digital type indicating the following :(i) Starting switch on/off (ii) Water temp guage(iii)Hour meter cum RPM indicator(iv) Lub oil pressure (v) Lub oil temperature(vi) Battery charging meter(vii) Safety alarm against high water temp and lub oil pressure (C)ALTERNATORShall be self excited, self regulated, brushless for 40 KVA continuous operation at the speed of 1500 RPM at 415 volts, 50Hz , three phase four wire system with advance electric voltage regulator to ensure high voltage accuracy with ± 1% with class \"H\" insulation and SPDP enclosure directly coupled with engine through flexible coupling and confirming IS- 13364 complete - 1 No.(D) Common fabricated base frame for engine & alternator made from structural channel, jerk proof PCC 1:2:4 type B1 foundation including adequate number of suitable anti-vibration pads all as per the recommendation of the manufacture- 01 No (NOTE:- Cost of suitable size of PCC foundation is deemed to be included in the unit rate quoted by the contractor. (E) Fuel tank fabricated out of 14 SWG MS sheet of capacity not less than 8 hrs continuous operation, inside canopy, with fuel level guage, drain plug, locking arrengements, etc with & including GI pipe connections duly laid as per engineering practice complete.(F) AMF CONTROL PANEL Supply, fabrication, fixing commissioning and testing, factory made, floor mounted, cubical automatic mains failure panel suitable for 40 KVA DG set, fabricated using 14 guage thick CRCA sheet, powder coated painting, suitable rated bus bar, internal wiring with control fuse, provn of connecting incoming & outgoing leads/bus bas as approved with and including the following accessories as under:-(i) Master switch for auto/ manual/ reset/ off - 01 No(ii) Ammeter digital type 96x96 mm to read 0 - 100 amps with CTs 1 set of 3, aux supply 230 volts, AC, accuracy class 1.0(iii) Voltmeter digital type, 96 x 96 mm to read 0 - 500 volts aux supply 230 volts, AC, accuracy class 1.0 (iv) Digital frequency meter -01 No. aux supply 230 volts, AC (v) Push button start, stop/ reset - 01 No(vi) Set of lamp for indicating load on , low pressure, high cylinder temperature, load on mains, set fails to start, low oil pressure . |
| 2 | Supply, install, test and commissioning in replacement of outdoor factory made powder coated cubical type double door, compartmentalised LT feeder pillar box of size 0.90x0.45x1.2m complete weather proof and verminproof conforming to IP-54 made out of 3.15mm thick CRCA sheet including provisions for ventilation and cable termination alley all as per IS.It should be mounted on 40 x40 x 6mm angle frame with a clearance of at least 0.45mtrs above GL and 0.30mtrs below ground including required PCC for foundation and coping.Markings should be made with vinyl sheet indicator to identify incoming and outgoing circuits. Feeder pillar box shall be comprising of following :- a) MCCB, 4 pole, 125 Amps, 25KA with thermal magnetic relaese - 1 No. ( incoming) b) MCCB 3 Pole 63Amps, 25 KAwith thermal magnetic release - 04No. ( out going) c)change over switch 40 Amps automatic-01d) MCB SPN 16 Amps, 16 KA- 01 Nos.(out going) (f )LED phase indicating lamp - 01 Set. g) copper Bus bar 3 phase 4 wire of capacity 100Amps - 01 Set Note :- Rates for necessary for finding out the loops of connecting cables to old panel and for new panel foundation are deemed to be included in the quoted rates. |
| 3 | Supply, laying, jointing and testing, fixing to wall using clamps/pole/floor or in air or passing through pipes /ducts / road/path/drain, laid in trenches, 1100 volts grade heavy duty electric cableXLPE insulated,screened ,PVC bedded, galvanised steel wire or wire armoured with electric power cable 1100 volts grade with stranded aluminium conductor of size 2 core 10 sqmm ISImarked( IS - 7098 Part-1) and its latest amendments complete all as specified and directed by Engr-in-Charge. |
| 4 | Supply,laying, jointing and testing, fixing to wall using clamps/pole/floor or in air or passing through pipes /ducts / road/path/drain, laid in trenches, 1100 volts grade heavy duty electric cableXLPE insulated,screened ,PVC bedded, galvanised steel wire or wire armoured with electric power cable 1100 volts grade with stranded aluminium conductor of size 3.5 core 70 sqmmISI marked (IS - 7098 Part-1) and its latest amendments complete all as specified and directed by Engr-in-Charge. |
| 5 | Supply, laying, jointing and testing, fixing to wall using clamps/pole/floor or in air or passing through pipes /ducts / road/path/drain, laid in trenches, 1100 volts grade heavy duty electric cableXLPE insulated,screened ,PVC bedded, galvanised steel wire or wire armoured with electric power cable 1100 volts grade with stranded aluminium conductor of size 3.5 core 50 sqmmISI marked ( IS - 7098 Part-1) and its latest amendments complete all as specified and directed by Engr-in-Charge. |
| 6 | Supply, laying, jointing and testing, fixing to wall using clamps/pole/floor or in air or passing through pipes /ducts / road/path/drain, laid in trenches, 1100 volts grade heavy duty electric cableXLPE insulated,screened ,PVC bedded, galvanised steel wire or wire armoured with electric power cable 1100 volts grade with stranded aluminium conductor of size 4 core 25 sqmmISI marked ( IS - 7098 Part-1) and its latest amendments complete all as specified and directed by Engr-in-Charge. |
| 7 | Supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade, of size 95 sq mm, 3.5 coreincluding cable lugs, jointing materials,GI pipe etc, laid in trenches fixed on poles or laid through GI pipes complete all as specified and directed by Engr-in-Charge. |
| 8 | M&L for earthingcompletewith galvanisedsteelearthplateelectrode 600x600x6mm burrieddirectlyin groundnotless than2.25mtr deepbelow normal ground level with top edgeof earth plate not less than 1.5mtrbelow normal ground level connected to the Galvanised iron strip 32x6mm sizeby meansof bolts, nuts, check nutsandwashersof galvanisediron and 32x6mm GI strip procted by provision of GI light grade pipe 40 mm boreincl provision of concrete pit in PCC1:2:4 typeB-1, using 20 mm graded crushed stone aggregates with 40 mm thick cover of RCC (1:2:4) reinforced with XPMweight not less than 4 Kg /Sqm and 6mm diabar handle ,excavationand earthworkin any type of soil, charcoaldustand saltlightgrade GI watering pipe 20 mm bore with funnel and wire mashand medium grade GIprotectionpipe 15mm bore 5 Mtr long and GI strip upto main earthingof polecomplete all as shown in electrical plateNo 5 of MES Sch 191 Part-I all as specifiedand directed . On testing after completion if the desired resistenance is not obtained the contrator shall redo the earthing without any extra cost to the departmentcomplete all as specified and directed by Engr-in-Charge. |
| 9 | M&L for earthing complete with copper earth plate elect rode 600x600x3mm thick buried directly in ground to a depth not less than 3mtr deep below normal ground level with top edge of the earth plate not less than 2.25mtr deep below normal ground level connected to copper strip 20x3mm size as earthing lead by means of soldering/brazing and bolts, nuts, check nuts and washers of brass, GI protection pipe light grade 40mm bore up to test point 20mm dia GI watering pipe with funnel and wire mesh, PCC pit 1:2:4 type BI, RCC cover with suitable handle, earth pit filled with ground enhancing material i.e. mixture of copper sulphate, magnesia sulphate, graphite power etc mixed in equal quantity all around earth plate up to 150 cm and filledwith vegetable soil above GEM up to ground level earth work in any type of soil all as required including testing on completion complete all as specified and directed by Engr-in-Charge. |
| 10 | Supply, installation, connecting electrically & commissioning LT feeder box , outdoor type of size 0.90x0.60x0.40 Mtr size factory fabricated made out of MS sheet of thickness 3.15mm front and backdoor openable with locking arrangement mounted on angle iron legs made out of angle iron of size 40x40x6mm, 1.0 mtr long , 0.7 mtr above ground level and 0.30 mtr embedded in PCC blocks of size 0.30x0.30x0.30 mtr -04 Nos duly painted with two coats of synthetic enamel paint over a coat of red oxide complete with 400 Amps rated aluminium bus bar suitable for 3 phase 4 wire supply dully drilled holes for cable connection mounted on epoxy based post insulators and MCCB 200 AMP,35 KA, 4 Pole 415 V complete all as specified and directed by Engr-in-Charge. |
| 11 | Supplying, installing and commissioning ofLT feeder box, outdoor type of size 0.90m x 0.60m x 0.50m, made out of MS sheet 3.15mm thick,legs made out of angle iron 40mmX40mmX6mm, 1.50m long (1.00m above ground level and 0.50m embedded in PCC (1:2:4), with openable shutter on both side (front and rear) having locking arrangement with 300 Amp rated aluminium bus bar suitable for 3 phase, 4 wire supply, drilled holes for cable connection, mounted on epoxy based post insulators and MCCB 4 pole, 160 Amp, 415 volt, microprocessor release with rupturing capacity 36 KA, complete all as specified and directed by Engr-in-Charge. Note :- rates for necessary for finding out the loops of connecting cables to old panel and for new panel foundation are deemed to be included in the quoted rates. |
| 12 | Supply, install, connect & testing cubical outdoor type factory made double door , powder coated LT bus bar feeder pillar box for 150 amps 3ph and neutral arrangement of size 500mmx500mmx200mm complete weather proof and verminproof conforming to IP-54 made out of 2mm thick CRCA sheet including provisions for ventilation and cable termination alley all as per IS.It should be mounted on 40 x40 x 6mm angle frame with a clearance of at least 0.45mtrs above GL and 0.30mtrs below ground including required PCC for foundation and coping complete all as specified and directed by Engr-in-Charge. (Note:-LT Panel/ LT feeder box must be approved by CPRI.) |
| 13 | M&L for cutting of bituminous road / floor for laying of pipe / cables not exc 1.5 meter wide and not exc 1.5 meter deep including refilling / with material and , watering well ramming / compacting and making good with PCC 1;2;4,type B-1, 100 mm thick complete all as specified and directed by Engr-in-Charge. |
| 14 | Excavation in trenches not exc 1.5m wide and not exc 1.5m deep and getting out in any type of soil for laying of cable complete all as specified and directed by Engr-in-Charge. |
| 15 | Returning filling in (soil) including spreading levelling, watering and well ramming in layers not exc 25cm thick complete all as specified and directed by Engr-in-Charge. |
| 16 | Removal of excavated soil to a distance not exc 50 m and depositing where directed at a level not exc 1.5 mtr above the ground level/starting point complete all as specified and directed by Engr-in-Charge. |
| 17 | M&L for dry river bed sand filling in trenches for cable cushioning below and above the cable complete all as specified and directed by Engr-in-Charge. |
| 18 | M&L for sub class\"B\"brickcovering protectionto the eletric cablelaiddry flat transversallyalongthe lengthof cableon sandcushioningwith widthequal to lengthof brick complete all as specified and directed by Engr-in-Charge. |
| 19 | M&Lfor 50mm dia GI pipe medium grade, for road crossing /on wall/on pole for cableprotection complete all as specified and directed by Engr-in-Charge. |
| 20 | M&Lfor 80mm dia GI pipe medium grade, for road crossing/on wall/on pole for cable protection complete all as specified and directed by Engr-in-Charge. |
| 21 | M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or chases or buried in ground or drawn in conduit /pipe fixed to pole or any other indicated situation for loop earthing etc as required 20x3 mm copper strip complete all as specified and directed by Engr-in-Charge. |
| 22 | S&Fin repair pressure die-cast aluminium IP 65 cool white flood Light luminaire with 80 Watt high power LED as light sourcewith inbuilt surge protection upto 5 KVincluding with Bracket , double clamps complete with nut boltswith pole and connection wire complete all as specified and directed by Engr-in-Charge. |
| 23 | M&Lfor PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) for foundation of poles/stays etc complete all as specified and directed by Engr-in-Charge. |
| 24 | M&L for PCC 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) as in coping including necessary form work finishing the cement concrete surfaces even & smooth using extra cement complete all as specified and directed by Engr-in-Charge. |
| 25 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc.removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc. complete all as specified and directed by Engr-in-Charge. |
| 26 | M&Lfor point wiring with two single core 1.5 sqmm cable (nominal area) stranded copper conductor, PVC insulated unsheathed cable, 1100 V grade in and including concealed PVC conduit of size not less than 20mm dia with sunken type pressed steel terninal box 1.6 mm thick of suitable size, duly painted with one coat of red oxide primer andtwo coats of black bituminous paint for mounting fittings/ junction boxes and wiring to be terminated in pressed steel sunken boxes including all accessories and using single core 1.5 Sqmm (nominal area) stranded copper conductor, PVC insulated unsheathed cable as in earth wire (green colour) connected to common earth dolly complete all as specified and directed by Engr-in-Charge for following :-(a) One light point controlled by one switch. |
| 27 | All as per item No 26 above but One fan/Exhaust fanpoint controlled by one switch and one regulator complete all as specified and directed by Engr-in-Charge. |
| 28 | All as per item No 26 above but One 3 pin switch socket outlet point 5 Amps on independent board complete all as specified and directed by Engr-in-Charge. |
| 29 | All as per item No 26 One 3 pin switch socket outlet point 5 Amps on same board with other switch complete all as specified and directed by Engr-in-Charge. |
| 30 | All as per item No 26 above but One bell point controlled by one 5 Amps bell push complete all as specified and directed by Engr-in-Charge. |
| 31 | All as per item 26 above but with copper conductor cable for one 3 pin socket outlet, 15 amp independent, with cable 2.5 sqmm size complete all as specified and directed by Engr-in-Charge. |
| 32 | M&L for switch piano flushtype single pole, one way 5 Amps 230 Volts AC circuit complete all as specified and directed by Engr-in-Charge. |
| 33 | M&L for switch piano flush type single pole, one way 15 Amps 230 Volts AC circuit complete all as specified and directed by Engr-in-Charge. |
| 34 | M&L for bell push 5 Amps 230 V, AC circuit complete all as specified and directed by Engr-in-Charge. |
| 35 | M&L for socket outlet 5 Amps, 5 Pin flush type multipurpose, 230 Volts AC circuit complete all as specified and directed by Engr-in-Charge. |
| 36 | M&L for socket outlet 2 in 1, 3 Pin 5 & 15 Amps, 230 Volts AC circuit complete all as specified and directed by Engr-in-Charge. |
| 37 | S&F stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. complete all as specified and directed by Engr-in-Charge. |
| 38 | M&L for call bell ding dong 230 V AC circuit complete all as specified and directed by Engr-in-Charge. |
| 39 | S&Fceiling rose surface backlite 65x50mm 3 terminals complete all as specified and directed by Engr-in-Charge. |
| 40 | Taking down old and unserviceable light fittings conventional type from wall surface/ceilling or any position and making good the disturbed surfaces complete all as specified and directed by Engr-in-Charge. |
| 41 | S&F LED lights fitting 1x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed by Engr-in-Charge. |
| 42 | S&F LED light fittingwith high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed by Engr-in-Charge. |
| 43 | S&F LED luminaire 600 mm x 600 mm, 40 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed by Engr-in-Charge. |
| 44 | S&F round shape 12 watt 220 volts AC recessed/surface type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed by Engr-in-Charge. |
| 45 | Taking down carefully unserviceable DB any type/size disconnecting and making good disturbed surfaces complete all as specified and directed by Engr-in-Charge. |
| 46 | S&F factory made epoxy powder coated distribution board double door TPN 4 ways vertical type MCB DB, with metal door (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including 200 Amps copper bus bar, neutral bar, strandard DIN rail, earth bar and cable ties for cable management complete all as specified and directed by Engr-in-Charge. |
| 47 | S&F factory made epoxy powder coated distribution board SPN 8 ways double door with acrylic top cover (IP-43 protection) fabricated from minimum 1.6 mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including 200 Amps copper bus bar, neutral bar, strandard DIN rail, earth bar and cable ties for cable management, top and bottom removable gland plates with Knockouts complete all as specified and directed by Engr-in-Charge. |
| 48 | Taking down carefully unserviceable MCB SP/SPN/Isolator of any rating/size complete all as specified and directed by Engr-in-Charge. |
| 49 | S&F MCB TPN415 Volt C curve 10 KA 40 to 100 Amps capacity including taking down complete all as specified and directed by Engr-in-Charge. |
| 50 | S&F MCB single pole & neutral 240 volt \"C\" curve 10 KA 40Amps complete all as specified and directed by Engr-in-Charge. |
| 51 | S&F MCB single pole 240 volt C curve 10 KA 5 to 32 Amps capacity and including taking down complete all as specified and directed by Engr-in-Charge. |
| 52 | Taking down old and unserviceable aluminium conductor sub main wiring of 2/3 runs or main-wiring or twin core flat cable of any sizes from any position including wood batten, PVC conduit, steel conduit, PVC casing caping etc and making good disturbed surface of wall ceiling etc complete all as specified and directed by Engr-in-Charge. |
| 53 | M&L for concealed sub main wiring using two single core PVC insulated, unseathed stranded copper conductor cable of size 6.0 Sqmm of voltage rarting upto and including 1100 volts drawn in and including PVC conduit of dia not less than 25mm with all fittings and accessories, along with one run of PVC (green colour) insulated, unsheathed, stranded copper conductor of size 4.0 Sqmm (green colour) as earth continuity conductor complete all as specified and directed by Engr-in-Charge. (Note : Two runs of single core PVC cable with one run of earth conductor and conduit shall be measured as one unit) |
| 54 | All as per item No 53 above but sub main wiring using two single core PVC insulated, concealedconduit suitable size ,unseathed FRLS multi stranded copper conductor cable of size 4.0 Sqmm with one run of PVC (green colour) insulated, unsheathed, FRLS multi stranded copper conductor of size 4 Sqmm as earth continuity conductor complete all as specified and directed by Engr-in-Charge. (Note : Two runs of single core PVC cable with one run of earth conductor and conduit shall be measured as one unit) |
| 55 | S&F PVC conduit of size 25 mmdia in wall / surface for existing telephone cable / Lan cable complete all as specified and directed by Engr-in-Charge. |
| 56 | S&F Industrial plug 20 Amps, 240 volt, single phase, 3 pin metal enclosure and socket complete all as specified and directed by Engr-in-Charge. |
| 57 | S&F single pole and neutral enclouser with two pin and earthplug and socket complete with one single pole MCB with 240 V 20 AMPs complete all as specified and directed by Engr-in-Charge. |
| 58 | Taking down the defective ceiling fan of any sweep andmake after disconnecting electrically & mechanically and transporting to the work shop dismantling, examine & carry out the repairs as required and brought back to site, re-fixing, testing in all respect for smooth running and comprising of the following:- (a)Servicing/overhauling the ceiling fan by thoroughly cleaning the bearing, shaft, stator, rotor & applying the lubricant / grease to the bearing including applying one coat of super enameled varnish over the winding to improve the insulation value complete all as specified and directed by Engr-in-Charge. |
| 59 | All as per item No 58 above but re-winding the burnt/short circuited winding with same guage supper enameled copper wire to maintain speed at load complete all as specified and directed by Engr-in-Charge. |
| 60 | All as per item 58 above but applying two coats of synthetic enamel paint after preparation of surface complete all as specified and directed by Engr-in-Charge. |
| 61 | Taking down the repairable exhaust fan of 300 MM / 380 MM sweep, any make, single phase, 230 volts, 50 HZ, AC after disconnecting electrically and mechanically and transporting to the work shop dismantling, examine & carry out the repairs as required and brought back to site, re-fixing, testing in all respect for smooth running and comprising of the following:- (a) Servicing/overhauling the exhuast fan by thoroughly clelaning the bearing, shaft, stator, rotor & applying the lubricant / grease to the bearing including applying one coat of super enameled varnish over the winding to improve the resistance value complete all as specified and directed by Engr-in-Charge. |
| 62 | All as per item No 61 above but re-winding the burnt/shourt circuited winding with same cauge supper enameled copper wire to maintain speed at load complete all as specified and directed by Engr-in-Charge. |
| 63 | All as per item No 61 above but applying two coat of synthetic enamel paint after preparation of surface complete all as specified and directed by Engr-in-Charge. |
| 64 | S&F 63 Amps MCCB bus bar chambers factory febricated suitable for 3 Phase & neutraliron clad with 4 Nos 100 amp rated copper strips including 01 No incomer of MCCB rating 63Amp 4 Pole, with two Nos Earthing connection bolt with locking arrangement front door operated complete fixed flush in wall and making good the disturbed wall surfaces complete all as specified and directed by Engr-in-Charge. |
| 65 | S&F of anti sucide device safe clamp made by MS Sheet 2 mm thick,electro cable device complete accessories such as nut bolt, rubber & nylock nuts and washer, cut of wire switch, spring with extended length of 1524mm cable tie etc, re-usable type device (can be refixed) istalled between the top down rod and the ceiling hook fan clamp. If load of 20/22 kg the fan should come down sepreately from top of the fancomplete, including taking down ceiling fan from its existing position and refix the same in its original position after fixing with the anti sucide device clamp and electric connection with new twin core twisted wire 1.0 sqmm complete all as specified and directed by the Engineer-in-Charge . Note: (i) Test for proper functioning of anti sucide clamp shall be infront of User Rep and Engineer-in-Charge. |
| 66 | S&F install and testing ISI marked Water heater 25 Ltr capacity 4 STAR Rating vertical type , 1500/2000 Watt heatingelement,PVC connection 450 mm (18\") with brass connector of series for both outlet and inlet, rated pressure 6 Kg/Sqcm supplied and installed complete witharrangement of fixing with suitable stud/Anchor fastner including PCC work with drilling holes if studs provided complete all as specified and directed by Engr-in-Charge. |
| 67 | M&L for sub main wiring in PVC casing and caping of reqd size 2 x 2.5 Sqmm PVC insulated multistrand copper conductor with 01x2.5 Sqmm PVC insulated multistrand copper conductor as earth continuity wire complete all as specified and directed by Engr-in-Charge. |
| 68 | Supply and laying of GI water tubing medium grade of size 15mm conforming to IS 1239 ISI marked including all GI fitting screws band tee union, nippple, flange etc laid in fixed on floor or wall and ceilings complete all as specified and directed by Engr-in-Charge. |
| 69 | S&F stop cock brass 15 mm dia with chromium plated for iron pipe ISI marked with screw end and fancy type complete all as specified and directed by Engr-in-Charge. |
| 70 | S&F 15 mm dia cast copper alloyBib tab with crutch or butterfly handle, screwed down , screwedwith chromium plated for iron pipe and fixed fancy type, ISI marked complete all as specified and directed by Engr-in-Charge. |
| 71 | Cutting & screwing extg steel tubing of size 15 mm dia for alterations or additions or lengthening screw on pipe to form connector and done in position without taking down complete all as specified and directed by Engr-in-Charge. |
| 72 | S&F faber hoodkitchen chimney vertical wall mounted hood with auto clean blower, offering a powerful 1200m3 /hr two way suction . Boa a corrision resistant single layer filter, gesture and touch controls and a 1.5 W LElamp 90 cm hood complete all as specified and directed by Engr-in-Charge. |
| 73 | M&L for industrial stainless steel sink with 16 Gauge sheet and 304 Grade SS and including all type of accessories with stand and plate rack complete all as specified and directed by Engr-in-Charge. |
| 74 | M&L for industrial stainless steel sink with 16 Gauge sheet and 304 Grade SS and including all type of accessories with stand and without plate rack complete all as specified and directed by Engr-in-Charge. |