| 1 | Excavation in trenches in soft/loose soil not exceeding 1.50 metre wide and not exceeding 1.50 metre in depth; for foundation, etc. and getting out complete, all as specified. |
| 2 | Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick each, complete, all as specified. |
| 3 | Removing excavated spoil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete, all as specified. |
| 4 | Sandcushioningwith clean dry sandto cables with layer of sand 8cm before laying of cable and 15cm thick after laying of cablecomplete all as specified. Note : For payment purpose punned thickness of 18cm shall be measured against spread thickness of 23cm as mentioned in para 19.75 of SSR part-I |
| 5 | Supply and laying of classB bricks for under ground cable protection as directed by Engineer- in - charge |
| 6 | Taking out existing damage/unservisable PVC\ XLPE insulated, armoured, aluminium conductor 1100V grade cable of any size and core from trenches, pipes, walls and/or poles, complete all as specified . Note: Excavation and earthwork shall be measured and paid for separaetly |
| 7 | Supply & Laying ofXLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric cables (heavy duty) cross sectional area 50 sq. mm, 3.5 core,stranded aluminium conductor including cable glands, cable lugs etc , to suit the cable size, 1100 volt grade, ISI marked,laid in trenches or fixing along the poles or passing through the pipes or laid under floors or through walls/ducts etc. complete all as specified. |
| 8 | All as per item No 07 above but cable of size 35 Sqmm, 3.5 core |
| 9 | All as per item No 07 above but cable of size 25 Sqmm, 3.5 core |
| 10 | All as per item No 07 above but cable of size 25 Sqmm, 2 core |
| 11 | All as per item No 07 above but cable of size16 Sqmm, 4 core |
| 12 | All as per item No 07 above but cable of size 16 Sqmm, 2 core |
| 13 | All as per item No 07 above but cable of size 10 Sqmm, 4 core |
| 14 | All as per item No 07 above but cable of size 10 Sqmm, 2 core |
| 15 | S&Fin repair heat shrinkable end joint (indoor/outdoor) for 1100 volt grade XLPE cable of size 25 Sqmm to 50 Sqmm, 3.5/4 core complete all as specified |
| 16 | All as per item No 15 above but of size 4 Sqmm to 16 Sqmm, 3.5/4 core complete all as specified |
| 17 | S&Fin repair 100 mm bore Tubes‘light grade’, galvanized with all fittings, laid in trenches or fixed along poles with mild steel clamps, as protection to cable, complete all as specified . |
| 18 | S&Fin repair 80 mm bore Tubes‘light grade’, galvanized with all fittings, laid in trenches or fixed along poles with mild steel clamps, as protection to cable, complete all as specified . |
| 19 | S&Fin repair 50 mm bore Tubes‘light grade’, galvanized with all fittings, laid in trenches or fixed along poles with mild steel clamps, as protection to cable, complete all as specified . |
| 20 | S&Fin repair 40 mm bore Tubes‘light grade’, galvanized with all fittings, laid in trenches or fixed along poles with mild steel clamps, as protection to cable, complete all as specified . |
| 21 | Repair toLT panel board/Feeder pillar box indoor/outdoortype by means of cuttingofdamaged portion of top/ bottom sheet, front /back door sheet .Welding new peace of CRCA sheet 2 mm thickas requiredat site . Replacement ofunsv door hinges and door lockes withkeys.Scrubing /scratching of old rusted paint by burning through blow lamps and applying metalic filler .Painting of LT Panel board/Feeder pillar box any size any description , externally and internallywith 02 coats of approved colour of paint with two coats of superior quality synthetic enamel paint over a coat of red oxide as primercomplete all as specifired and as directed by Engr-in-Charge. |
| 22 | Supply and fix Moulded case circuitbreaker4 Pole, 415 V, adjustable thermal type (40% to 100%) and adjustale magenetic release TPN 415 volt volt 600 Amps with breaking capacity 35 KA,, ICS =100 ICU, Adjustable type, 630 Amps complete all as specifired and as by Engr-in-Charge. |
| 23 | Supply and fix Moulded case circuitbreaker 4 Pole, 415 V, adjustable thermal type(40% to 100%) and adjustale magenetic release TPN 415 volt 400 Amps with breaking capacity 35 KA, ICS =100 ICU, complete all as specifired and as directed by Engr-in-Charge. |
| 24 | Supply and fix Moulded case circuitbreaker 4 Pole, 415 V, Adjustable thermal type(40% to 100%) type, adjustale magenetic release TPN 415 volt 250 Amps with breaking capacity 36 KA with ICU=ICS 100% complete all as specifired and as directed by Engr-in-Charge. |
| 25 | Supply and fix Moulded case circuitbreaker 4 Pole, 415 V, adjustable thermal (40% to 100%) and adjustale magenetic release TPN 415 volt volt 200 Amps with breaking capacity 35 KA, ICS =100 ICU,complete all as specifired and as directed by Engr-in-Charge. |
| 26 | Supply and fix Moulded case circuitbreaker 4 Pole, 415 V, fixed type, 160 Amps with breaking capacity 25 KA with ICU=ICS 100% complete all as specifired and as directed by Engr-in-Charge. |
| 27 | Supply and fix Moulded case circuitbreaker 3 Pole, 415 V, adjustable thermal (40% to 100%) and adjustale magenetic release TPN 415 volt 100 Amps, with breaking capacity 25 KA, ICS =100 ICU complete all as specifired and as directed by Engr-in-Charge. |
| 28 | Supply and fix Moulded case circuitbreaker 3 Pole, 415 V, adjustable thermal (40% to 100%) and adjustale magenetic release TPN 415 volt 63 Amps, with breaking capacity 16 KA, ICS =100 ICU complete all as specifired and as directed by Engr-in-Charge. |
| 29 | Taking out old unserviceable bus bar chamber after disconnecting existing cable connection carefully. Supply and fixing new bus bar chamber TPN of size 0.6x0.6x0.4 mtr with front and back openable and lockable made out of 3 mm thick CRC sheet and supported on MS angle legs of size 40x5mm of 0.4 mtr-4 Nos. and grouted in PCC 1:3:6. The bus bar chamber shall have 04 nos aluminium bus bar of current carrying capacity 400 amps insulated by colour coded heat shrink sleeves and supported on epoxy insulators. The bus bar chamber shall have space for provision of one No 4 Pole MCCB 200 amps to 300 amps. The bottom of the bus bar chamber shall have detachable plate and provision of suitable size MS glands complete all as specifired and as directed by Engr-in-Charge. |
| 30 | Supply and fixing LED street light fitting 45 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specifired and as directed by Engr-in-Charge. |
| 31 | All as per item no 30 above but LED street light 60 watt. |
| 32 | All as per item no 30 above but LED street light 90 watt. |
| 33 | S&F street light bracket made out of 32mm dia, 1.50 mtr long GI tubing, \"medium grade\" ISI marked, bent to required shape and angle as per site requirement with and including MS clamps size 30X6mm,with nuts, bolts, washers etc for fixing street light fittings and bracket, duly painted with two coats of aluminium paint over a coat of red oxide primer including taking out existing unserviceable rusted GI bracket complete all as specified and as directed. |
| 34 | S&F street light bracket made out of /32mm dia, 1.50 mtr long GI tubing, \"medium grade\" ISI marked, bent to required shape and angle as per site requirement with and including MS clamps size 30X6mm,with nuts, bolts, washers etc for fixing 4 street light fittings and bracket, duly painted with two coats of aluminium paint over a coat of red oxide primer including taking out existing unserviceable rusted GI bracket complete all as specified and as directed. |
| 35 | S&F street light bracket made out of /32mm dia, 1.50 mtr long GI tubing, \"medium grade\" ISI marked, bent to required shape and angle as per site requirement with and including MS clamps size 30X6mm,with nuts, bolts, washers etc for fixing 2 street light fittings and bracket, duly painted with two coats of aluminium paint over a coat of red oxide primer including taking out existing unserviceable rusted GI bracket complete all as specified and as directed. |
| 36 | Supply and fixing of Junction box made out ofthermo plastic material of size 240x130x110 mm with provision of three phase cable connector incomming and out going with MCB SP 6-32 amps for security light fitting/PTLIP 54 protection totally enclosed weather proof with cable entryalong with GI clamps nut bolts & washer fixed on pole including dismantling/taking out old unserviceale one all as directed. |
| 37 | Supply and fixing in reapir LEDflood light fitting 210 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal anagement in multiple optics complete with IP 65/66 protection complete all as specifired and as directed by Engr-in-Charge. |
| 38 | All as per item No.37 above but of Capacity 170Watt. |
| 39 | All as per item No.37above but of Capacity 120Watt. |
| 40 | Supply and fixing in reapir post top lantern LED 50 Watt with die cast aluminium spigot and lid cover high efficient LED and clear acrylic cover conforming to IP 65 ptrotection with clear acryliccover and incl necessary fixing arrangement complete all as specified including taking down old unserviceable fittings of any size/ wattage complete all as directed by Engr-in-Charge. |
| 41 | Supply and fixing in reapir LED bollard 10Wattwith die cast aluminium housing with polycarbonate housing and cylinder diffuser IP 65 conforming with 12 watts LED, Driver and surge protectorincluding making new connection with three core PVC copper flexible cable of size 23/.0076 complete all as directed by Engr-in-Charge. |
| 42 | Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium, with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspensionwire, two core cables cable flat or circularof size 10 Sqmm stranded conductor for sevice connection. |
| 43 | All as per item No. 42 above but of size 6 Sqmm. |
| 44 | All as per item No. 42 above but of size 4 Sqmm. |
| 45 | Disconnection and removing the U/S timer and S&F install digital timer switch in sheet metal encloser havig the contact rating : 16A AC1 usb key version : EG103E. 1 channel weekly cycle 56 adjustment pre recording programme two moudules with impulse and holiday function having the contactors rating all for AC 7A lead only (Coil voltage 230V 50Hz). for remote switch control a power circuit 3 No, 63 A 3 modules complete all as per manufacturer\"s specificationsincluding taking down old unserviceable fittings of any size/ wattage complete all as directed by Engr-in-Charge. |
| 46 | Supply and fixing PVC insulated copper wire FRLS of size 2.5 Sqmm (nominal area) 3 core for repair of street light wherever required at site and as directed by Engr -in-charge. |
| 47 | Disconnection and removing the unserviceable auxilary contactors and S&F Auxilary Contactors (Existing type) 3 pole, 30 to 32 Amp with logic units complete all as directed by Engr-in-Charge. |
| 48 | All as per item No. 47 above but capacity 3 pole, 40Amp. |
| 49 | All as per item No. 47 above but capacity 3 pole, 18Amp. |
| 50 | Disconnecting U/S Change Over and S&F Change over switch fuse type 100A, 440Volts complete all as directed by Engr-in-Charge. |
| 51 | Disconnection and removing the u/s Earthing andM&L for earthing complete with galvanized steel earth plate, electrode 60cm x 60cm x 6.0mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to using galvanised GI wire 4mm dia as earthing lead as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel, connected to earthing test point, earth plate electrode surrounded by mixer of common salt and charcoal dust, including 20mm dia GI watering pipe ‘medium grade’, funnel with wire mesh, earthing chamber with cement concrete (1:2:4) type B-1, RCC chamber cover 40mm thick (1: 1 ½: 3) type B1, excavation & earth work all as shown in electrical plate No 5 of SSR (Part-I) and testing on completion, complete all as specified and directed. |
| 52 | S&F in repair LED Inverter street light90 W RTC Street light with inbuilt RTC (Real time clock) for Auto ON Auto off and must have Dimming facility from 10 to 100% of rated watage as per user defiend timeline housing made of pressure Die cast Aluminium, top maintainable and with clear heat Resistant toughened glass, should have secondary lens for better optics, should have LM 80 certified LED of CREE, Seoul Make only with constant current rtc enabled electronic driver with 5KV SPD, IP66. Street light shall have 1.5 to 2.0 hrs battery backup at inverter load in case of power failure, Efficancy 100LPW, Pf 0.95 Cut of voltage at 300 volt, and Suitable for 50mm mounting pipe complete all as directed by Engr-in-Charge. |
| 53 | All as per item No 52 above butstreet light 60W . |
| 54 | Repair and servicing of Trolley mounted 4 Wheel extendable ladder including winch operating system assembly & replacement of following parts as per existing size and shape.Note : - (a) Steel wire rope (As per sample) -30RM.(b) Ruberised wheel heavy duty (As per sample)- 04Nos. (c) Wheel bearing 04 Nos. Note:- Repair should include cost of oiling, greasing, topping up of oil in winch/gear box including welding of broken steel members, denting, penting of the lader complete all as directed by the Engr-in-Charge. |
| 55 | Supply and fixingin repair twin LED aviation obstruction light 120 watts red colouron 16 Mtr high High Mast pole suitable for operating voltage 175 VAC to 275 VAC ,and should withstand to the following Operating conditions :-(a )Temperature ranging from - -20⁰C to +55⁰ C(b) Wind pressure- more than 240 (kph)(c) Visibility-should be visible in Fog and rain.(d)Humidity-more than 80 %Note : Cost of T&P required for fixing of lightning finial on top of high mast is deemed to be included in the quotd rates |
| 56 | Note: For the purpose of arriving at lumpsum amount, the amount of credit schedule i.e Sch \"A\" section II (i.e Rs 79,698.00 shall be deducted from the total amount arrived. |
| 57 | Total of Schedule \"A\" Rs. |