| 1 | Excavation in trenches in any type of soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth and getting out all as required for laying of cables,foundation filling of poles or stays and for rerouting of cables. |
| 2 | Returning filling, in including spreading ,leveling, watering and well ramming in layers not exc 25 cm each all as required. |
| 3 | Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point. |
| 4 | M&L for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm, thick after laying, stretchingand testing the cable |
| 5 | M&L for Sub class ‘B’ bricks old size. laid dry flat over the cable abutting each other, length of cable equal to width of brick all as required. |
| 6 | M&L for cement concrete(1;3;6) type1 ,M-10 using 12.5mm mm graded coarse aggregate for repairing surfaces completeincluding surface dressing and leveling by surface excavation wherever required complete in all respect or as directed. |
| 7 | M&L for cutting of PCC/Hard standing/WBM road for passing cable including making good with PCC work all as specified and directed . |
| 8 | Supply and laying in replacement to wall or poles or fixing or passing through pipe, in replacement of 1100 volts grade heavy duty cable with XLPE insulated aluminium multistranded conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and overall PVC sheathed16 sq. mm nominal cross section 2 core in service connections all as required and directed. |
| 9 | All as per srl item No 08 but cable of size 16 Sqmm 4 core. |
| 10 | All as per srl item No 08 but cable of size 10 Sqmm 2 core. |
| 11 | All as per srl item No 08 but cable of size 10 Sqmm 4 core. |
| 12 | Supply and laying in replacement of trenches or fixing to wall/pole or passing through pipe in replacement of XLPE insulated heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 25 Sqmm 3.5 core. (Note : Incl making good all distributed wall surfaces/ flooring/tilling to match with existing specification) |
| 13 | All as per srl item No 12 but cable of size 35 Sqmm 3.5 core. |
| 14 | All as per srl item No 12 but cable of size 50 Sqmm 3.5 core. |
| 15 | All as per srl item No 12 but cable of size 70 Sqmm 3.5 core. |
| 16 | All as per srl item No 12 but cable of size 95 Sqmm 3.5 core. |
| 17 | All as per srl item No 12 but cable of size 120 Sqmm 3.5 core. |
| 18 | All as per srl item No 12 but cable of size 150 Sqmm 3.5 core. |
| 19 | All as per srl item No 12 but cable of size 185 Sqmm 3.5 core. |
| 20 | All as per srl item No 12 but cable of size 240 Sqmm 3.5 core. |
| 21 | All as per srl item No 12 but cable of size 300 Sqmm 3.5 core. |
| 22 | Supply and laying in trenches or fixing to wall/pole PVC insulated heavy duty electric cable with copperconductor 1100 volts grade cross sectional area 10 Sqmm 4 core. (Note : Incl making good all distributed wall surfaces/ flooring/tilling to match with existing specification) |
| 23 | S&F in replacement of cable jointing kit for 1100 volt grade cable for straight through termination heat shrinkable type complete with jointing material and accessories suitable for XLPE/PVC armoured aluminium conductor cable of size 10 to 16 Sqmm 3.5/4 core. |
| 24 | All as per item No 23 but for 25 to 50 Sqmm size. |
| 25 | All as per item No 23 but for 70 to 150 Sqmm size. |
| 26 | All as per item No 23 but for 185 to 300 Sqmm size. |
| 27 | Supplying and fixing in replacment of 1100 volts grade heavy duty cable PVC insulated aluminium stranded conductor of size 6 sqmmtwin core, served with inner sheathing of PVC tape and overall PVC sheathed in service connectionsconnection complete all as specified. |
| 28 | Supply, errecting and installation of steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9 metres long)duly painted with two coat of black bituminous paint through out, internally and externally up to planning depth and painting remaining portion of pole with two coat of aluminium paint to the entire exposed surfaces over one coat of red oxide primer making/painting three Nos circular strips each of 30 cm wide with one yellow and 02 Nos black colour strip synthetic enamel paint and marking pole number with black paint including excavation, earth work, PCC work complete all as spfd and directed |
| 29 | M&L for cross arms, bracings, supports, clamps and back plates fabricated from steel section including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape ors size as indicated or directed and inclusive ofoneprimer coat, one under coat and one finishing coat of alumn paint. |
| 30 | M&L in replacement for stay assy complete with MS stay plate of size 300x300x6mm thick, stay rod 16mm dia, stay bow, loop type insulator, nuts, bolts and check nuts of GI all as shown in EP No 01 of SSR Part-I of 1991 including excavation, earth work,PCC work complete all as specifeid & directed by Engr-in-charge |
| 31 | S&F Pin type, porcelain, vitreous, brown insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade |
| 32 | M&L in replacement of for GI tubing light grade 80mm bore with fittings laid for protection of cable under road crossing fixed to walls or pole complete all as specified and as directed.(clamps for fixing pipe, nuts, bolts washers shall be measured separately ) |
| 33 | All as per srl item No 32 but 50mm bore |
| 34 | All as per srl item No 32 but 40mm bore |
| 35 | S&F in replacement of bus bar chambers 300 mm longiron clad with 4 Nos 400 Amp rated Aluminium strips complete fixed flush wall and making good the disturbed wall surfaces all as a requiredat site or directed. |
| 36 | All as per srl item No 35 but with 4 Nos 200 Amp. |
| 37 | All as per srl item No 35 but with 4 Nos 100 Amp. |
| 38 | Repair, maint and of broken doors for LT panel and bus bars by welding and incl fixing ofnew hinges and other material as required at site complete all as spfd and directed. |
| 39 | Removal of unwanted vegetation/bushes/small plants shrubs around the water/electric supply installations/ inside the valve pit and surface excavation not esceeding 15 cm depth leveling the ground and removing the excavated material to a distance exceeding 50 M. |
| 40 | M&L for cutting, trimming of branches along the OH conductor of LT/ HT line/street light polewithin 2 mtr distance along both side of line and strictly all branches in one place as directed by Engineer-in-Charge. |
| 41 | S&F in replacement of MCCB 4 Pole 415 Volts3 phase 400 Amps 36 KA, thermal magnetic release connection complete all as specified |
| 42 | All as per item No 41 but MCCB 630 Amps 50 KA. |
| 43 | All as per item No 41 but MCCB 250 Amps 35/36 KA. |
| 44 | All as per item No 41 but MCCB 160 Amps 25 KA. |
| 45 | All as per item No 41 but MCCB 100 Amps 16 KA. |
| 46 | All as per item No 41 but MCCB 63 Amps 16 KA. |
| 47 | All as per item No 41 but MCCB 3 pole 100 Amps 16 KA. |
| 48 | All as per item No 41 but MCCB 3 pole 160 Amps 25 KA. |
| 49 | Detection of any type of fault in HT/LT underground Line (laid in soil at plane area or forest area) with the help of Cable fault locator machine. Cable fault locator with carring vehicle will be brought by the cable fault detection agencies. Span of faulty cable will be trace out by the agencies by meggering HT cable. Note : 1. Detection of fault in one span of length will be measured as one Job either machine placed from one side or both side of the cable. 2. Technicians will be employed by the working agencies. 3. Earth work and taking out will be measured and paid seperately. 4. Material for repair and replacement measured and paid saperately. 5. One job shall be measured if the fault has successfully identified by the fault locator machine or removing moisture in the cable if required. |
| 50 | M&L in replacement of earthing complete with galvanised cast iron earth plate electrode of size 600x600x6.3 mm thick as earth electrode with top edge of the earth plate not less than 1.5mtr below ground level using GI wire 4mm dia as earth continuity conductor connected to earth plate by means of GI thimbles nuts bolts washers all as directed including providing earth wire protection pipe GI light grade15mm dia from earth plate to main switch board/panel, watering pipe 20mm dia with wire mesh and funnel at top, earth pit and RCC pit cover in PCC 1:3:6 adequate quantity of charcoal dust and salt all around the erth plate, earth work in any type of soil remaing surplus excavated material all as required at site and specified in EP No 5 of SSR part I 1991 or directed incl testing on competion. |
| 51 | All as per srl item No 50 but connected to galvanised iron strip 32x6mm earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electric plate No 3connected to earth test point all as specified. |
| 52 | M&L for fixing earthing strip32 x 6 mm aluminium strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required,In Repair,complete all as specified & directed. |
| 53 | S&F cable lugs up to 50 Sqmm made up of Aluminium |
| 54 | S&F cable lugs 50 to 120 Sqmm made up of Aluminium for HT/LT |
| 55 | S&F cable lugs 120 to 240 Sqmm made up of Aluminium for HT/LT |
| 56 | S&F cable lugs above 240 Sqmm made up of Aluminium for HT/LT |
| 57 | Supply and fixing in replacement ofon onload changeover switch of800 Amps 4 pole 415 V, panel mouting metal enclosure type without enclosure,including labour for alterration in panel etc comlete.Make : Havells/L&T / HPL/ Indoasian |
| 58 | Supply and fixing in replacement ofon onload changeover switch of400 Amps 4 pole 415 V, panel mouting metal enclosure type without enclosure,including labour for alterration in panel etc comlete.Make : Havells/L&T / HPL/ Indoasian |
| 59 | Supply and fixing in replacement ofon onload changeover switch of200 Amps 4 pole 415 V, panel mouting metal enclosure type without enclosure,including labour for alterration in panel etc comlete.Make : Havells/L&T / HPL/ Indoasian |
| 60 | Supply and fixing in replacement ofon onload changeover switch of125 Amps 4 pole 415 V, panel mouting metal enclosure type without enclosure,including labour for alterration in panel etc comlete.Make : Havells/L&T / HPL/ Indoasian |
| 61 | Supply, fixing, connecting and testing in replacement ofACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 800 Amps including replacement of connection lead of suitable size with suitable lugs/ clamps complete all as specified and directed |
| 62 | M&L for repairs to electrical panel/ feeder pillar box by tightning all loose connections of the cable ends & replacing the damaged/ burnt aluminium lugs of required sizes, insulating/ secure the weak insulated portion of cable ends inside the panel by tapeing with good quality of insulation tape, cleaning the dust by air blower including painting the panel surface with two coat of synthatic enamel paint of approved shade over a coat of red oxide primer complete all as specified and as directed. |
| 63 | S&F in replacement digital multi function meter three phase, 415 volts having LCD Display,96 x 96 sq.mm Flush mounted case, accuracy class 1.0 capable of measuring Instantaneous, Average, Maximum and Total Current from 5A to 500A and voltage from 120V AC to 300V AC Phase to Neutral, Phase to Phase Voltage, Instantaneous, Average, Maximum and Total Active Power KW, Instantaneous, Average, Maximum and Total Apparent Power KVA, Total Power Factor, Frequency complete all as specified and as directed. |
| 64 | S&F sheet metal MCCBenclosures for TP/FP MCCBs with inbuilt neutral link for TPN system, IP 30 Protectedcomplete all as specified and as directed. |
| 65 | Material and Labour for supply, installation, commissioning and testing of outdoor type LT panel(CPRI Approved) made out of 3.15 mm thick sheet metal, double door made out of MS angle iron base frame, cubical type floor mounted 3 Phase, 4 Wire, 415 Volts properly insulated aluminium bus bar - 04 Nos having capacity 600 amps on phase &neutral, dust and vermin proof, both side open with locking arrangement comprising of comprising of multifunction meters with 3 lines LCD display of voltage, current and frequency and power factor of size 96x96 sqmm, suitable ratio CT, phase indicator-03 Sets, danger board plate, duly painted internally and externally with powder coated, fixing in position by provision of platform suitable size built with brick work in CM (1:4), 15 mm thick plastering in CM (1:6) including glands, lugs, thimbles for all incomming and out going cable including dismantling /taking out complete all as directed by the Engineer-in-Charge of suitable sizes for following :-Incoming: MCCB Cap 630 Amps, FP 415 Volts breaking capacity 36 KA- 01Outgoing : (b) MCCB Cap 250 Amps, FP 415 Volts breaking capacity 25 KA- 02 No.(c)MCCB Cap 100 Amps, FP 415 Volts breaking capacity 16 KA- 02 No. |
| 66 | M&L for preparing scraping the old painted surfaces and applying one coat of aluminium paint on steel tubular swaged poles and swan neck /bracked, chanels/angles including making/pasting three nos cricular strips of 300 mm wide yellow & black colour with synthetic reflected enamel paintand marking /stencil writing of pole numbers with black paint complete and all as specified and directed. |
| 67 | M&L for painting of outdoor/indoor LT Panel with spray painting machine with emsynthetic enamelle paint of existing colour two coat and black paint in Angle iron / MS flat or stand after scratcing with sand paper or any other suitable mean up to satisfactory level of engr in Charge and Re-clean the the existing name platevisible by any means complete all as directed. |