| 1 | Excavation in trenches n.exc 1.5 m wide and n.exc 1.5 m in depth for foundation of pole and laying of UG cable and getting out in soft/loose of soil complete all as specified and directed. |
| 2 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm complete all as specified and directed. |
| 3 | Removing excavated material to a distance n.exc50m and depositing where directed at a level n.exc 1.5M above the starting point complete all as specified and directed. |
| 4 | M&L for PCC 1:3:6 type C-2 (using 40 mm graded stone aggregate) as in foundation of pole and stay complete all as specified and directed. |
| 5 | M&L for PCC 1:2:4 type B-1 (using 20 mm graded stoneaggregate) for coping of pole and as in benching and finished exposed surfaced even and smooth without wiring extra cement including necessary form work complete all as specified and directed. |
| 6 | Supply, laying, testing & commissioning UG cable XLPE insulated,armoured heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross section area 120 sq mm 3.5 core including taking down of ACSR/old cable complete all as specified and directed. |
| 7 | Supply, laying, testing & commissioning UG cable XLPE insulated,armoured heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross section area 50 sq mm 3.5 core including taking down of ACSR/old cable complete all as specified and directed. |
| 8 | Supply, laying, testing & commissioning UG cable XLPE insulated,armoured heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross section area 35 sq mm 3.5 core including taking down of ACSR/old cable complete all as specified and directed. |
| 9 | Supply, laying, testing & commissioning UG cable XLPE insulated,armoured heavy duty electric cable with aluminium conductor, 1100 Volts grade cross section area 25 sq mm 4.0 core including taking down of ACSR/old cable complete all as specified and directed. |
| 10 | Supply, laying, testing & commissioning UG cable XLPE insulated,armoured heavy duty electric cable with aluminium conductor, 1100 Volts grade cross section area 16 sq mm 4.0 core including taking down of ACSR/old cable complete all as specified and directed. |
| 11 | Supply & filling sand for cushioningto the under ground cable 8 cm before laying the electric cable and 15 cm after laying the cablecomplete all asspecified and directed.Note: Punned thickness shall be measured and paid under this item. |
| 12 | M&L for common burnt clay building bricks (locally available best quality), sub-class ‘B’ designation 75 of size 230x115x75 mm to cover LT underground cables, laid dry and flat complete all as specified and directed. |
| 13 | Supply and fixing/laying GI tubing light grade of size 40 mm bore with all fittings laid in trenches or fixed to wall for protection of cable complete all as specified and directed. |
| 14 | Supply and fixing/laying GI tubing light grade of size 50 mm bore with all fittings laid in trenches or fixed to wall for protection of cable complete all as specified and directed. |
| 15 | Supply and fixing/laying GI tubing light grade of size 80 mm bore with all fittings laid in trenches or fixed to wall for protection of cable complete all as specified and directed. |
| 16 | Supply and fixing/laying GI tubing light grade of size 100 mm bore with all fittings laid in trenches or fixed to wall for protection of cable complete all as specified and directed. |
| 17 | S&F aluminium strip of earthig and making proper earth testing point from pole, panels and transformer (size not less than 25x3.15mm) complete all as specified and directed. |
| 18 | M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 m below normal ground level, connecting to the Galvanised iron earth wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron and earth wire protected by provision of GI medium grade pipe 15mm bore including provision of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone agregates with 40mm thick cover of RCC (1:2:4) type B-1 including reinforcement and one handle of 6mm dia MS bar made to shape, GI light grade 20mm bore pipe for watering , perforated at bottom. 1.75 metre long placed on top edge of earth plate, charcoal and common salt filled 150 mm thick all around the earth plate with fixing arrangement, funnel wire mesh and earth work in any type of soil returning filling in and removal of surplus soil to a distance not exceeding 50 m all as per electical plate No 3 of SSR-2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion. |
| 19 | M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5m below normal ground level, connecting to the Galvanised iron earth strip 32x6mm size by means of bolls, nuts, check nuts and washers of galvanised iron and earth wire protected by provision of GI medium grade pipe 40mm bore including provision of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone agregates with 40mm thick cover of RCC (1:2:4) type B-1 including reinforcement and one handle of 6mm dia MS bar made to shape, GI light grade 20mm bore pipe for watering , perforated at bottom 1.75 m long placed on top edge of earth plate, charcoal and common salt filled 150 mm thick all around the earth plate with fixing arraangement, funnel wire mesh and earth work in any type of soil returning filling in and removal of surplus soil to a distance not exceeding 50 meters all as per electical plate No 3 of SSR-2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion. |
| 20 | M&L for painting to 9 m LT tubular pole with one coat of aluminium paint and one coat of synthetic enamel paint upto 1.0 m height above the ground level with black and yellow colour alternatively at 25cm interval including numbering of pole with white colour on black background complete all as specified and directed. |
| 21 | S&F fabricated junction box, out door type comprising of enclosure made out of 3 mm thick CRCA sheet of size 300mmx300mmx200mm powder coated, front openning, with locking arrangement alongwith 4 Nos of aluminium busbar of 200 amps 1100 volt grade, busbar duly fixed and including post insulators with provision of 02 Nos cable gland holes suitable for 01 incoming/ 01 outgoing cable and providing with rubber bushingand 01 No MCB SP 6Amp with provision of earthing connection nuts, bolts including clamp testing complete all as specified and directed. |
| 22 | S&F submain wiring of three run 1.5sqmm FRLSH wire PVC insulated copper conductor, single core cable in non metallic PVC conduit as per colour coding on pole/surface as required complete all as specified and as directed. |
| 23 | M & L for trimming /cutting tree branches with clearing space upto 1 m all around the security light polecomplete all as specified and directed. |
| 24 | M & L for re-shifting of LT pole from one location to another along with removing from ground, dismantling of PCC and transportation from one side to another complete all as specified and directed.Note: Earthwork and PCC shall be measured and paid separately. |
| 25 | Supply, install,testingand commissioning outdoor type LT panel/feeder panel ofsize 0.6mx0.6mx0.45m , CPRI approvedfactory made totally encloseddust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, angle iron frame size 50x50x6mm and minimum staging height not less than 0.5m duly fabricated and having proper locking arrangement in both front and rear door painted with powder coated paint and provision of aluminium bus bar 300 amps suitable for 415 volts, 50 Hz , 3 phase 4 wire system and comprising with and including following accesories and mounted on PCC platform having offset of 1m all around the panel board complete with the following items:- Incoming :-(a) MCCB, 4 Pole, 250A, 415 V, 25 kA.- 01 No. (b) Aluminium bus bar 4 strip of 300 amps(c)Internal connection by aluminium strip from MCB/MCCB to busbar and busbar to MCCB/MCB etc. |
| 26 | Supply, install,testingand commissioning outdoor type LT panel of suitable size , CPRI approvedfactory made totally encloseddust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, angle iron frame size 50x50x6mm and minimum staging height not less than 0.5m duly fabricated and having proper locking arrangement in both front and rear door painted with powder coated paint and provision of aluminium bus bar 525 amps suitable for 500 volts, 50 Hz , 3 phase 4 wire system and comprising with and including following accesories and mounted on PCC platform having offset of 1m all around the panel board complete with the following items:-Incoming :-(a) MCCB, 4 Pole, 315A, 415 V, 35 kA .- 01 No. (b) LCD Multifunction meter - 01 No.(c) CTs 320/5 A, set of 3 - 01 Set(d) Phase indicator lamps (RYB), set of 3 - 01 Set(e) Aluminium bus bar 4 strip of 525 Amps(f)Internal connection by aluminium strip from MCB/MCCB to busbar and busbar to MCCB/MCB etcOutgoing :-(a) MCCB, 4 Pole, 100 A,415 V, 35 kA - 03 Nos.(b) MCCB, 4 Pole, 200 A,415 V, 35 kA - 01 No.(b) MCB, 4 Pole, 63 A,415 V,16 kA - 01 No. |
| 27 | S&F in repair LED street light fittings of 60 Watt in aluminium PDC housing, toughened glass cover, individual LED with secondary optics, covered with IP66 protection with inbuilt surge protection of minimum 10 KV, suitable to fix in 40mm GI bracket complete all as specified and directed. |
| 28 | S&F 32 mm dia GI tubing light grade bracket over all 1.2 mtr length with cutting as required and bend to shape with flat iron clamp of size 32 mmx4mm-02 Nos, suitable size of nut bolts and washers completefor fixing street light fittings on electric poles including taking down old unserviceable/fully rusted existing unserviceable one complete all as specified and directed. |
| 29 | S&F in repair/replacement nature switch in enclosure made out of UV stablized, FR grade special moulding compound, rust proof, electric shock proof, vermine proof outdoor pole mountable with mounting bracket made out of FI and nut, bolts, washers including cable glands, openable door with lock comprising with nature switch sensor,power contactor three phase-03nos rating, 32 amps per phase , 06 nos of MCBfor max load 12-15kw including taking down existing nature switch,Ip 66 enclosure complete all as directed. Make:- Kakatiya Energy System Ltd.cat No. SWADEEP-66-12kw3p, IP-66 enclosure or equivalent of make Indo Asian/Legrand. |
| 30 | S&F VTPN (Vertical Three Pole and Neutral) Distribution Board with provision of MCCB as incommer 100A DD04 way, IP 43, ISI marked complete all as specified and directed. |
| 31 | S&F MCCB 100Amp, 4 pole, suitable with VTPN (Vertical Three Pole and Neutral) with all connected accessories complete all as specified and directed. |
| 32 | M&L for straight through LT joint kit suitable for LT cable, 1100 volt, heat shrinkable type joint complete with all jointing material and accessories suitable for 3.5 corecable of size 50 sqmm to 120 sq mm complete all as specified and directed. |