| 1 | Excavation in trenches (soft/loose soil) n.exc. 1.5 m wide and n.exc.1.5m in depth for laying of UG Cable including getting out all as specified & directed by Engr-in-Charge |
| 2 | Returning filling in includingspreading leveling watering and well ramming in layers not exceeding 25 cm all as specified and directed. |
| 3 | Removing excavated material n.exc. 50m and depositing where directed at a level n.exc 1.5 m above starting point all as directed by Engineer in Charge. |
| 4 | M&L for spreading & leveling dry clean Ganga sand in trenches for cushioning UG cable complete all as specified and directed. (Note: For Payment purpose punned thickness of sand shall be measured) |
| 5 | M&L for sub class \"B\" old size of brick laid in trenches with width of brick equal to length of bricks for cable protection of LT Cables complete all as specified and directed. ( Note : Bricks must be layed across the cable all as directed ) |
| 6 | M& L for boring through existing road with trench less method for passing of UG cable all as specified and directed. |
| 7 | Supply and laying in replacement XLPE insulated , armoured heavy duty electric cable with alumnium conductor ,1100 volts grade ,corss sectional area 10 sqmm 2 core complete all as specified and directed by Engr-in-Charge. |
| 8 | All as per ser item No.7 here-in-before but 10 Sqmm 4 core |
| 9 | All as per ser item No.7 here-in-before but 16 Sqmm 4 core |
| 10 | All as per ser item No.7 here-in-before but 25 Sqmm 4 core |
| 11 | All as per ser item No.7 here-in-before but 35 Sqmm 3½ core |
| 12 | All as per ser item No.7 here-in-before but 50 Sqmm 3½ core |
| 13 | All as per ser item No.7 here-in-before but 70 Sqmm 3½ core |
| 14 | All as per ser item No.7 here-in-before but 95 Sqmm 3½ core |
| 15 | All as per set item No.7 here-in-before but 120 Sqmm 3½ core. |
| 16 | All as per set item No.7 here-in-before but 150 Sqmm 3½ core. |
| 17 | All as per set item No.7 here-in-before but 185 Sqmm 3½ core. |
| 18 | All as per set item No.7 here-in-before but 240 Sqmm 3½ core. |
| 19 | All as per set item No.7 here-in-before but 300 Sqmm 3½ core. |
| 20 | S & F in replacementGI pipe light grade 100mm bore for cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc complete all as specified & directed. |
| 21 | All as per seritem No.20 here-in-before but 80mm bore. |
| 22 | All as per seritem No.20 here-in-before but 50mm bore. |
| 23 | M& L for cutting of floor/wall/road/footpath for removal of HT U/G cable of any size/description and making good the same as per existing specification after relaying the same or new cable and all as specified & directed. |
| 24 | Taking down & Re-laying of serviceableHT/LT cable obtained of any size and discription . ( Note:-Excavation , earth work, sand cushionning, bricks etcshall be measured seperatly under respective item of Sch.) |
| 25 | S &F LT PVC adhesive electrical insulation tape roll 3/4\" x 8 Yards x 0.125 mm thickness on Panels/ Cables/ Transformers all as directed by Engineer in Charge. |
| 26 | Supply, installation, commissioning and testing in replacementpowdercoated factory made panel board outdoor type CPRI approved confirming to IP 64 protaction, of suitable size made of Robust steel sheet construction made from min 3.15 mm steel sheet with countersunk holes at bottom for base mounting brackets and sheet steel gland plates for cable entry, formed gasket arround doors, with provision of Lock inserts, earthing straps, door stay and grouted in ground by using angle iron frame of size 50mm x 50mm x 6mm, PCC (1:2:4) type C-1 with 20mm graded stone aggregate.(Note :- Old unserviceable Panel Board is property of department and deposited to MES store yard.Trasportation of old panel is included in quoted rates.)The panel will be prewired with suitable size PVC insulated copper conductor cable, multistranded housed with the following accessories:- |
| 27 | (a) Aluminium bus bar of capacity 800 Amp for phase and 400 Amps for neutral. |
| 28 | (b) Incoming MCCB 4 pole 630 Amp 50 KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU)– 02 Nos |
| 29 | (c) Outgoing MCCB 4 pole 400 Amp 36KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU)– 01 Nos |
| 30 | (d) Outgoing MCCB 4 pole 350 Amp 35KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU)– 01 Nos |
| 31 | (e) Outgoing MCCB 4 pole 250 Amp 35KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU)– 02 Nos |
| 32 | (f) Outgoing MCCB 4 pole 200 Amp 25 KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) – 03 Nos |
| 33 | (f) Outgoing MCCB 4 pole 100 Amp 25 KA alongwith Spreader terminals with adjustable thermal setting ( ICS= 100% ICU) – 04 Nos |
| 34 | (g) On load change over switch of capacity 630 Amp– 01 Nos |
| 35 | (h)Digital volt meter 0 to 500 volt with selector switch – 02 No |
| 36 | (j)Digital Amp meter 0 to 800 Amp with CT of suitable ratio and selector switch – 02 No |
| 37 | (k) Phase Indicator Lamp RYB with sheds LED Type - 01 Set of three |
| 38 | (l) Digital timer switch (Astronomical) along with contractor/MCB and suitable accessories. |
| 39 | (m) Phase Indicator Lamp RYB with sheds LED Type - 01 Set of three |
| 40 | M&L for preparing old painted surface of panel board by cleaning removing of the old paint by scracthing with wire bursh/sand paper etc and including denting/patching of brocken/rusted surfaces etc and apply two coat of synthetic enamel paint by spray painting on inside/outside surface of panel,all as specified and directed by Engr-in- charge. |
| 41 | M&L in replacement for fabrication of door/surfaces of LT panel indoor/outdoor as per existing size / thickness/shape and fitted in the panel with door handle, formed gasket around doors, lock insets, earthing strips, door stay, hinges,rivetsetc. including two coat of synthetic enamel paint by spray painting on inside/outside surface of panel,all as specified and directed by Engr-in- charge. |
| 42 | Supply and fix in replacement copper bus bar in the panel/Transformer LT side of exsiting size and capacity for phase and neutral with heat shrinkable including PVCsleeves in different colour codes for phase indication all as per directed by Engr-in-charge. |
| 43 | All as per item No 29 Above but aluminium bus bar |
| 44 | S & F in replacementLED type phase indication lamp of Red /blue/Yellow colour for phase indication in existing panels complete all as specified and directed by Engr-in-charge . |
| 45 | S & F in replacement selector 3 way for checking of Amps in 3 phase at different position in existing panels complete all as specified and directed by Engr-in-charge . |
| 46 | All as per item No 32 Above but for checking of voltage. |
| 47 | Supply and fixing in replacement of Power Contactor MNX 650, 3 pole , 415 volts, 50 Hz AC supply all as per sample andspecified and directed by Engr-in-charge. |
| 48 | Supply and fixing in replacement of Power Contactor MNX 110, 3 pole , 415 volts, 50 Hz AC supply all as per sample andspecified and directed by Engr-in-charge. |
| 49 | Supply and fixing in replacement of Power Contactor MCX 45, 4 pole , 415 volts, 50 Hz AC supply all as per sample andspecified and directed by Engr-in-charge. |
| 50 | S & F in replacement MCCB 415 Volts 4 pole 630 Amps 50 Hz 50 KA of existing make model and typealonwith spreader terminal with adjustable thermal setting( ICS= 100% ICU) including lugs/thimbles of suitable size in existing panels complete all as specified and directed by Engr-in-ChargeNote : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 51 | All as per item no. 37 here in before but forMCCB 415 Volts 4 pole 500 Amps 50 Hz 36 KA. of existing make model and typealonwith spreader terminal with adjustable thermal setting ( ICS= 100% ICU). |
| 52 | All as per item no. 37 here in before but for of MCCB, 4 pole adjustable type 36 KA, 400 Amps.Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 53 | M & L for replacement of MCCB, 4 pole adjustable type 36 KA, 350 Amps. Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.. |
| 54 | M & L for replacement of MCCB, 4 pole adjustable type 25 KA, 250 Amps.Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 55 | M & L for replacement of MCCB, 4 pole adjustable type 25 KA, 200 Amps.Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.. |
| 56 | M & L for replacement of MCCB, 4 pole adjustable type 25 KA, 160 Amps. Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 57 | M & L for replacement of MCCB, 4 pole adjustable type 25 KA, 100 Amps. Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 58 | M & L for replacement of MCCB, 4 pole adjustable type 16 KA, 63 Amps.Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 59 | S& F in replacement Digital volt meter 0 to 500 volt with CI 1 |
| 60 | S& Fin replacementDigital Amp meter 0 to 800 Amp with CT of suitable ratio CI 1 |
| 61 | M&L Repairs & overhauling to LT ACBs of any capacity(400 A to 1000 A) of any make by removing out the breaker from the respective panels after taking proper electric shut down & disconnecting the breaker, checking it thoroughly for the defects & tripping system of the ACB and rectifing them, lubrication of moving contacts, overhauling of the ACB, replacement of wornout minor spares like springs, washers, levers, nuts & bolts etcreassembling , re-installation ,testing & commissioning of ACB complete all as directed by Engineer-in- chargeNote :(i) Cost of lubricants, cleaning agents, testing tools and minor spares shall be deemed to be including in quoted rates |
| 62 | Supply and fixing in replacement of Moving Arcing contacts and adjust the contact pressure of LT ACB of any make any capacity all as directed by Engineer in Charge. |
| 63 | Supply and fixing in replacement of fixed Arcing contact and adjust the contact pressure of LT ACB of any make any capacity all as directed by Engineer in Charge. |
| 64 | M&L for replacement of main shaft assembly with crank & cam spacer ofexisting capacity LT ACB of existing make & model and testing for proper operation complete all as directed by Engineer-in-charge |
| 65 | M&L for replacement of Trip coil of LT ACB of any make any capacity all as specified and directed by Engr-in-charge |
| 66 | M&L for grouting of LT/APFC Panel by using angle iron frame of size 50mm x 50mm x 6mm, PCC (1:2:4) type C-1 with 20mm graded stone aggregate and including shifting of existing LT/APFC panel with disconeection of existing cables and reconnecting it after grouting of panel complete all as specified and directed by Engr-in-charge. |
| 67 | M & L for hardcore of broken stone or boulders gauge of 40mm to 63 mm , deposited, spread and levelled in layers n exc. 15cm thick complete all as specified |
| 68 | Supply and fix in repair ofLT sides porcelain bushing with brass stud with nuts, bolts and washers of exisiting transformer of 100 to 500 KVA including decanning & refilling the same of transformer oil,connection & reconnection of cable opening of top cover replacement of nut bolts complete all as specified and directed. |
| 69 | Supply and fix in repair of HT sides porcelain bushing with brass stud with nuts, bolts and washer of exisiting transformer of 100 to 500 KVA including decanning of transformer oil,connection & reconnection of cable opening of top cover replacement of nut bolts complete all as specified and directed. |
| 70 | Supply and fix ruber seal/gland on HT/LT studs of transformer including decanning of transformer oil,connection & reconnection of cable opening of top cover replacement of nut bolts complete all as specified and directed. |
| 71 | Clearing away all grass vegetation ,saplings, shrubs, brush wood undergrowth roots and trees not exceeding 30 CM girth (measured one metre above ground level) and removing rubbish upto a distance of 50 metres outside the periphery of the area under clearancesoft/loose soiland getting out including sprinkling anti vegitation chemical for complete area with spray machinecomplete all as specified & directed. |
| 72 | S & F in replacement of PVC insulated heavy duty electric weather proof flat twin core cable with aluminium conductor 1100 Volts grade, cross sectional area 6 Sqmm all as directed by Engineer in Charge. |
| 73 | S & F in replacement of PVC insulated heavy duty electric weather proof flat twin core cable with aluminium conductor 1100 Volts grade, cross sectional area 10 Sqmmall as directed by Engineer in Charge.. |
| 74 | S & F in replacement of PVC insulated heavy duty electric weather proof flat twin core cable with aluminium conductor 1100 Volts grade, cross sectional area 16 Sqmmall as directed by Engineer in Charge. |
| 75 | M & L fabrication of MS busbar chamber of nominal dimension 900 mm x 600 mm x 300 mm duly provided with aluminimum busbar of size 50 mm x 6mm dixed on porcelain insulators TPN type out door weather/vermin proof with both way open ing duly provided with neoprene rubber gasket along the doors openings pedestal type duly painted powder coated on CRCA steel sheet encloser with one No incommer MCCB 200 Amp 25 KA complete all as sepcified and directed incl making connection /thimbles etc complete.(Note :- Old unserviceable Panel Board is property of department and deposited to MES store yard.Trasportation of old panel is included in quoted rates.) |
| 76 | All as per srl item No 66 here-in-before but of size 600 mm x 600 mm x 300 mm and without MCCB(Note :- Old unserviceable Panel Board is property of department and deposited to MES store yard.Trasportation of old panel is included in quoted rates.) |
| 77 | Cleaning and preparation of old painted surface of HT/LT/street light pole complete and painting with one coat of aluminium paint including channels/ brackets, street light brackets, cross arms and making blue& white strips with synthetic enamelled paint of 30 cm height, eachalternative strip upto 1.5 mtr height and writing pole numbers with yellow synthetic enamelled paint after making circular basewith black synthetic enamelled paint complete all as specified. |
| 78 | Supply ,fixing ,commisioning and testing of Naturetimer switch control StreetLights complete with MCB,Power and Panel duly complete with wiring Model : SWADEEP-02EC8 KW 3P, three phase ,max load 8-12 KW Manufactured by KAKATIYA ENERGY SYSTEMS LTD HYDERABADor equivalent of other make complete all as specified and directed.Note:- CA No & date of installations shall be painted/marked on all timer switch provided by the contractor |
| 79 | Supply ,fixing ,commisioning and testing of Naturetimer switch control StreetLights complete with MCB,Power and Panel duly complete with wiring Model : SWADEEP-02EC8KW 1P, single phase ,max load 8-10 KW Manufactured by KAKATIYA ENERGY SYSTEMS LTD HYDERABADor equivalent of other make complete all as specified and directed.Note:- CA No & date of installations shall be painted/marked on all timer switch provided by the contractor |
| 80 | M&L for earthingcomplete with galvanised or steel earth plate electrode of size 60cm x60cmx6mm thick burried directly in ground vertically ( to a depth not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected tostrip 32x 6 mm size with nuts, bolts , check nuts , washers, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick all around, top & bottom watering pipe 20mm bore of GI mediumgrade with funnel and wiremesh all as shown in electrical plate No. 3 of SSR -2009 Part I and connecting to arthingtest point,main switch board and testing oncompletion including PCC chamber concrete 1:3:6 typeC-2 and RCC cover 75mm thick with MS TMT bar 8mm dia @ 150mm c/c both ways in cement concrete(1:2:4) type B-1 all asshown in electrical plate in No 3 of SSR (Pt-I)2009 complete all as specified anddirfected by Engineer-in-charge.Note:- Up to 3 mtr earth strip shall be included with quoted unit rate. |
| 81 | Supply and fixing/laying of galvanized iron strip of size 32x6 mm as earth continuity conductor provided in between earth test point terminal and upto the equipment incl nuts, bolts and washers complete all as specified and directed. |
| 82 | Supply and fixing in replacement of danger notice plate of 1.6mm thick, MS sheet, vitreous enamelled white, with letters, figuers and conventional skull and bones in signal red colour and fixed with MS clamps made out offlat iron 25x3 mm, nuts-bolts, of approved size for LT 20 x 15 cm. |
| 83 | Supplying and laying in replacement of synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m all as specified and directed. |
| 84 | M&L for in replacement of bus bar chamber, fixed on wall, 4 ways, 100 Amps ,415 V powder coated, water & vermin proof , IP-66 protection duly provided with front openable door incl provision of TPN copper bus bar heat shrinkable colored PVC sleeve coated for phase and neutralcomplete all as specified and directed. |
| 85 | M&L for in replacement of bus bar chamber, fixed on wall, 4 ways, 63 Amps ,415 V powder coated, water & vermin proof , IP-66 protection duly provided with front openable door incl provision of TPN copper bus bar heat shrinkable colored PVC sleeve coated for phase and neutralcomplete all as specified and directed. |
| 86 | Supply and fixing Isolator 4pole 63 Amps,415 Volts all as specified and directed. |
| 87 | Supply and fixing Isolator 4pole 100 Amps,415 Volts all as specified and directed. |
| 88 | Supply and fixing Isolator 2 pole 40 Amps,220 Volts all as specified and directed. |
| 89 | Supply and fixing in replacement of HT 11 KV busbar outdoortype weather and vermin proof factory fabricated CPRI approved duly painted with two coat of enamelled paint,pedestal type made out of mild steel sheet 3.15 mm thick,factory made using angle iron 40 mm x 40 mm x 6 mm and 500 mm high,front opening double door shutter weather proof,rust proof, dust proof with provision of rubber gasket and locking arrangement including HT bush,insulator & busbar (80 x6 mm) with colour code - 03 Nos and making connection with suitable size of thimbles, nuts, bolts and washers etc incl necessary earth work to fix 60 cm above ground level complete all as directed by Engineer in charge. |
| 90 | Supply and Fix HT insulation tapes ( 25 mm x 9 Mtr) rubber electrical tape - Black ISI Marked for terminating high voltage cables for insulation sealing of connection of wire and cable for bus bar insulation, transformer terminal insulation etc complete all as specified and directed. |
| 91 | S & F in replacement sheet metal enclosure suitable for fixing 4 pole MCCB upto 160 amp capacity mounted type with fixing arragement in existing wall / angle iron frame incl welding work etc including making electrical connections complete all as specified and directed. |
| 92 | S & F in replacement on load change over switch, 800 Amps, 4 pole with sheet metal enclosure, panel mounted type with fixing arragement in existing wall angle iron frame 50x50x4mm with welding work and PCC works etc including making electrical connections complete all as specified and directed. |
| 93 | S & F in replacement on load change over switch, 630 Amps, 4 pole with sheet metal enclosure, panel mounted type with fixing arragement in existing wall angle iron frame 50x50x4mm with welding work and PCC works etc including making electrical connections complete all as specified and directed. |
| 94 | Attending complaints from Complaint Section / JE / Engr-in-charge by any mode of communication & attending the same within 4 hours like opening of connections, checking for supply, transportation of necessary tools and labour, assessing the nature of complaints, rectifying minor issues, removing carbon deposits (if any), cleaning of lugs/glands etc., meggering of cables, making temporary connections (as required), and restoring back the power supply all as directed at site.Note:- The occurance of fault if any, will be communicated to the contractor and he shall rectify the same within 4 hrs of reporting, failing to which a recovery @ Rs 500/= per complaint per day and maximum of Rs. 10,000 /= per day shall be recovered from contractor\"s payment. |
| 95 | M&L for detection of HT/LT fault by using fault locator machine highering from civil authority complete all s specified and directed by Engr-in -Charge. Note :- In one length of cable from Panel/DB/Transformer to Panel/Transformer all faults considered as single job. replacement heat shrinkable type end termination joint suitable for cable of size 25 to 400 Sqmm, 3.5 Core, 1100 Volts grade complete all as specified and directed. |
| 96 | Supply Joining , commissioning and testingin replacement of Heat Shrinkable straight though joint suitable for cable of size 120 to 185 sqmm 3 core complete with all fittings and jointing materials suitable for HT11 KV ( E ) XLPE cable all as specified and directed. |
| 97 | Supply Joinging , commissioning and testingin replacement of Heat Shrinkable end termination jointOut doortype and suitable for cable of size 240 to 300 sq mm 3 core complete with all fittings and jointing materials suitable for HT11 KV ( E ) XLPE cable all as specified and directed. |
| 98 | Supply Joinging , commissioning and testingin replacement of Heat Shrinkable straight through joint suitable for cable of size 240 to 300 sq mm 3 core complete with all fittings and jointing materials suitable for HT11 KV ( E ) XLPE cable all as specified and directed. |
| 99 | M&L for replacement heat shrinkable type straight through joint suitable for cable of size 25 to 50 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 100 | M&L for replacement heat shrinkable type straight through joint suitable for cable of size 70 to 120 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 101 | M&L for replacement heat shrinkable type straight through joint suitable for cable of size 150 to 185 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 102 | M&L for replacement heat shrinkable type straight through joint suitable for cable of size 240 to 300 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 103 | M&L for replacement heat shrinkable type straight through joint suitable for cable of size 400 to 500 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 104 | M&L for replacement heat shrinkable type End joint suitable for cable of size 25 to 50 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 105 | M&L for replacement heat shrinkable type End joint suitable for cable of size 70 to 120 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 106 | M&L for replacement heat shrinkable type End joint suitable for cable of size 150 to 185 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 107 | M&L for replacement heat shrinkable type End joint suitable for cable of size 240 to 300 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |
| 108 | M&L for replacement heat shrinkable type End joint suitable for cable of size 400 to 500 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed. |