| 1 | Dismantling the existing old L.T cubicle distribution board at TH Colony 11KV Substation including unwanted cables from the cable trench and reconnect the old working in good condition cables and new cables to new LT panel, Existing old street light cables removed from the earth level to junction box at street light post and keep in the opening of pit and closing/refilling, Damaged and unserviceable cables shall be shifted and handed over to CH.P.A. RSA yard. as per Schedule ‘A’. |
| 2 | Dismantling the existing old L.T panels and Wall mounted boards from various Electrical rooms of No.4,9,10,18,DLB (West).CISF MESS, CH.P.A Hr. Sec. School and Corporation School same shall be shifted, loading, transporting, Unloading and handed over to RSA Yard as per Schedule ‘A’. |
| 3 | Removing of existing damaged street light foundation and newly strengthening of foundation to M.S. street light posts by using of M 20 concrete for 3 feet a foundation measurement 450 mm X 450 mm in square shape in build to provide the 2 mtrs. suitable size HDPE hose for cable entering. (foundation 1 feet below ground level and 2 feet above the street light post). |
| 4 | Dismantling the existing old and damaged Feeder pillars at various location and same shall be shifted, loading, Transporting, Unloading and handed over to RSA Yard as per Schedule ‘A’. |
| 5 | Supplyof 3½ Core x 300 Sq.mm. XLPE, L.T, UG, Alu. armoured cable with cable route marker from 11KVSub-station to Electrical switching rooms in various locations as detailed in Schedule ‘A’. |
| 6 | Laying of 3½ Core x 300 Sq.mm. XLPE, L.T, UG, Alu. armoured cable with cable route marker from 11KVSub-station to Electrical switching rooms in various locations as detailed in Schedule ‘A’. |
| 7 | Supplyof 3½ Corex185 Sq.mm. XLPE, L.T, UG, Alu. armoured cable with cable route marker from 11 KV Substation to Electrical switching rooms in various location and Electrical switching room to feeder pillar boxes in various locations as detailed in Schedule ‘A’. |
| 8 | Laying of 3½ Corex185 Sq.mm. XLPE, L.T, UG, Alu. armoured cable with cable route marker from 11 KV Substation to Electrical switching rooms in various location and Electrical switching room to feeder pillar boxes in various locations as detailed in Schedule ‘A’. |
| 9 | Supplyof 3½ Core x 50 Sq.mm. XLPE, L.T, UG, Alu. armoured cable from Electrical switching rooms and Feeder Pillar Boxes to Individual Residential Blocks in various location as detailed in Schedule ‘A’. |
| 10 | Laying of 3½ Core x 50 Sq.mm. XLPE, L.T, UG, Alu. armoured cable from Electrical switching rooms and Feeder Pillar Boxes to Individual Residential Blocks in various location as detailed in Schedule ‘A’. |
| 11 | Supplyof 4 Core x 25 Sq.mm. XLPE, L.T, UG, Alu. armoured cable from electrical switching room to street light post loop in & loop out in various locations as detailed in Schedule ‘A’. |
| 12 | Laying of 4 Core x 25 Sq.mm. XLPE, L.T, UG, Alu. armoured cable from electrical switching room to street light post loop in & loop out in various locations as detailed in Schedule ‘A’. |
| 13 | Earth excavation of 0.75 mtr. depth x 0.30.mtr breadth for laying the L.T, UG 300 sq. mm, 185 Sq.mm, 50.Sq.mm and 25 Sq. mm. cables from 11 KV Substation to Electrical switching rooms, Electrical switching rooms to Feeder Pillar boxes, Electrical switching room and Feeder pillars to Residential blocks and street light posts (loop in & loop out) and re-closing the earth excavation with excavated soil and make it original level (including concrete /Asphalt road cutting, trees root and any other obstruction etc.,) detailed in Schedule ‘A’. |
| 14 | Concrete / Asphalt Road / Brick floor cutting for depth of 200 mm x 300 mm breadth including Providing of Suitable size of G.I Pipes for the various sizes of the cables and rebuild the road to original condition with concrete. |
| 15 | Rebuild of 50 mm thickness cement floor plastering. |
| 16 | Design, Fabrication, Supply of new indoor L.T cubicle main switch board. comprising 23ways 1600 Amps rating at T.H. Colony 11 KV Substation. as detailed in Schedule ‘A’. |
| 17 | Installation, Testing and commissioning of new indoor L.T cubicle main switch board. comprising 23ways 1600 Amps rating at T.H. Colony 11 KV Substation. as detailed in Schedule ‘A’. |
| 18 | Design, Fabrication, Supply of new indoor L.T. APFC Capacitor Panel at TH Colony Substation. as detailed in Schedule ‘A’. |
| 19 | Installation, Testing and commissioning of new indoor L.T. APFC Capacitor Panel at TH Colony Substation. as detailed in Schedule ‘A’. |
| 20 | Design, Fabrication, Supply of new Indoor LT cubical 8 ways, main switch board.Electrical Room No. 4 (Wall mounting type), comprising of 2 Nos. 400 Amps, 4 Pole, 35 KA, MCCB as incoming feeder, 4 Nos. 250 Amps, 4P, 35 KA, 2 Nos. 100 A, 4P, 25 KA, MCCB as outgoing feeder, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 300 Amps digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 21 | Installation, testing and commissioning of new Indoor LT cubical 8 ways, main switch board.Electrical Room No. 4 (Wall mounting type), comprising of 2 Nos. 400 Amps, 4 Pole, 35 KA, MCCB as incoming feeder, 4 Nos. 250 Amps, 4P, 35 KA, 2 Nos. 100 A, 4P, 25 KA, MCCB as outgoing feeder, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 300 Amps digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 22 | Design, Fabrication, Supply of new Indoor LT cubical 16 ways, main switch board.Electrical Room No. 9 (Floor mounting type), comprising of 4 Nos. 400 Amps, 4 Pole, 35 KA, MCCB as incoming feeder, 6 Nos. 250 Amps, 4P,35KA, 6 Nos. 100 A, 4P, 25 KA, MCCB as outgoing feeder, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 300 Amps digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 23 | Installation, testing and commissioning of new Indoor LT cubical 16 ways, main switch board.Electrical Room No. 9 (Floor mounting type), comprising of 4 Nos. 400 Amps, 4 Pole, 35 KA, MCCB as incoming feeder, 6 Nos. 250 Amps, 4P,35KA, 6 Nos. 100 A, 4P, 25 KA, MCCB as outgoing feeder, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 300 Amps digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 24 | Design, Fabrication, Supply of new Indoor LT cubical 8 ways, main switch Board.Electrical Room No. 10 (Floor mounting type), comprising of 2 Nos. 400 Amps, 4 Pole, 35 KA, MCCB as incoming feeders, 2 Nos. 250 Amps, 4P,35KA, 4 Nos. 100 A, 4P, 25 KA, MCCB as outgoing feeders, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 300 Amps digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 25 | Installation, testing and commissioning of new Indoor LT cubical 8 ways, main switch Board.Electrical Room No. 10 (Floor mounting type), comprising of 2 Nos. 400 Amps, 4 Pole, 35 KA, MCCB as incoming feeders, 2 Nos. 250 Amps, 4P,35KA, 4 Nos. 100 A, 4P, 25 KA, MCCB as outgoing feeders, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 300 Amps digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 26 | Design, Fabrication, Supply of new Indoor LT cubical 12 ways, main switch board.Electrical Room DLB (West) (Floor mounting type), comprising of 3 Nos. 400 Amps, 4 Pole, 35 KA, MCCB as incoming feeders, 4 Nos. 250 Amps, 4P,35KA, 5 Nos. 100 A, 4P, 25 KA, MCCB as outgoing feeders, 1 No. 440 V digital Volt meter withselector switch, 1 No. 0 to 300 Amps digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 27 | Installation, testing and commissioning of new Indoor LT cubical 12 ways, main switch board.ElElectrical Room DLB (West) (Floor mounting type), comprising of 3 Nos. 400 Amps, 4 Pole, 35 KA, MCCB as incoming feeders, 4 Nos. 250 Amps, 4P,35KA, 5 Nos. 100 A, 4P, 25 KA, MCCB as outgoing feeders, 1 No. 440 V digital Volt meter withselector switch, 1 No. 0 to 300 Amps digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 28 | Design, Fabrication, Supply of new Indoor LT cubical 10 ways, main switch board.ElEElectrical Room CISF MESS Building. (Wall mounting type), comprising of 2 Nos. 400 Amps, 4 Pole, 35 KA, MCCB as incoming feeders, 6 Nos. 100 A, 4P, 25 KA, 2 Nos. 63 A,4P, C - Series MCB as outgoing feeders, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 300 Amps CT type digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 29 | Installation, testing and commissioning of new Indoor LT cubical 10 ways, main switch board.ElEElectrical Room CISF MESS Building. (Wall mounting type), comprising of 2 Nos. 400 Amps, 4 Pole, 35 KA, MCCB as incoming feeders, 6 Nos. 100 A, 4P, 25 KA, 2 Nos. 63 A,4P, C - Series MCB as outgoing feeders, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 300 Amps CT type digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 30 | Design, Fabrication, Supply of new Indoor LT cubical 12 ways, main switch board.Electrical Room. Hr. Sec. School (Wall mounting type), comprising of 2 Nos. 250 Amps, 4 Pole, 35 KA, MCCB as incoming feeder, 8 Nos. 100 A, 4P, 25 KA, 2 Nos. 63 A,4P, C - Series MCB as outgoing feeder, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 300 Amps CT type digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector50switches as detailed in Schedule ‘A’. |
| 31 | Installation, testing and commissioning of new Indoor LT cubical 12 ways, main switch board.Electrical Room. Hr. Sec. School (Wall mounting type), comprising of 2 Nos. 250 Amps, 4 Pole, 35 KA, MCCB as incoming feeder, 8 Nos. 100 A, 4P, 25 KA, 2 Nos. 63 A,4P, C - Series MCB as outgoing feeder, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 300 Amps CT type digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector50switches as detailed in Schedule ‘A’. |
| 32 | Design, Fabrication, Supply, Installation, testing and commissioning of new Indoor LT cubical 06 ways, main switch board.ElElectrical Room No:18 (Wall mounting type), comprising of 1 No. 250 Amps, 4 Pole, 35 KA, MCCB as incoming feeder, 2 Nos. 200A, 4P, 25KA, 3Nos. 100 A, 4P, 25 KA outgoing feeder, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 250 Amps CT type digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 33 | Installation, testing and commissioning of new Indoor LT cubical 06 ways, main switch board.ElElectrical Room No:18 (Wall mounting type), comprising of 1 No. 250 Amps, 4 Pole, 35 KA, MCCB as incoming feeder, 2 Nos. 200A, 4P, 25KA, 3Nos. 100 A, 4P, 25 KA outgoing feeder, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 250 Amps CT type digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. b) Installation, Testing & Commissioning |
| 34 | Design, Fabrication, Supply of new Indoor LT cubical 06 ways, main switch board.Corporation School Electrical Room.(Wall mounting type), comprising of 1 No. 200 Amps, 4 Pole, 35 KA, MCCB as incoming feeder, 4 Nos. 100 A, 4P, 25 KA, 1 No. 63 A,4P, C - Series MCB as outgoing feeder, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 200 Amps CT type digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 35 | Installation, testing and commissioning of new Indoor LT cubical 06 ways, main switch board.Corporation School Electrical Room.(Wall mounting type), comprising of 1 No. 200 Amps, 4 Pole, 35 KA, MCCB as incoming feeder, 4 Nos. 100 A, 4P, 25 KA, 1 No. 63 A,4P, C - Series MCB as outgoing feeder, 1 No. 440 V digital Volt meter with selector switch, 1 No. 0 to 200 Amps CT type digital Ammeter with selector switch, 3 Nos. R Y B lamp indicators and phase selector switches as detailed in Schedule ‘A’. |
| 36 | Supply of CRCA sheet out door type, 800Amps. Feeder pillar boxes at various locations as per Schedule ‘A’.(i) 10 Ways - |
| 37 | Installation of CRCA sheet out door type, 800Amps. Feeder pillar boxes at various locations as per Schedule ‘A’.(i) 10 Ways - |
| 38 | Supply of CRCA sheet out door type, 800Amps. Feeder pillar boxes at various locations as per Schedule ‘A’.(ii) 8 Ways - |
| 39 | Installation of CRCA sheet out door type, 800Amps. Feeder pillar boxes at various locations as per Schedule ‘A’.(ii) 8 Ways - |
| 40 | Supply of CRCA sheet out door type, 800Amps. Feeder pillar boxes at various locations as per Schedule ‘A’. (ii) 6 Ways - |
| 41 | Installation of CRCA sheet out door type, 800Amps. Feeder pillar boxes at various locations as per Schedule ‘A’.(ii) 6 Ways - |
| 42 | Supply of Outdoor type modular control panel for Street light control as per detailed in Schedule ‘A’. |
| 43 | Installation of Outdoor type modular control panel for Street light control as per detailed in Schedule ‘A’. |
| 44 | Supply of 1x 30 Watts LED flood light for all Residential Block entrance light with 3 run of 1.5 sq.mm PVC insulated copper wire from ceiling rose to LED fitting for all Residential Block, EB Rooms and Pump Rooms entrance light. As per detailed in Schedule ’A’. |
| 45 | Installation of 1x 30 Watts LED flood light for all Residential Block entrance light with 3 run of 1.5 sq.mm PVC insulated copper wire from ceiling rose to LED fitting for all Residential Block, EB Rooms and Pump Rooms entrance light. As per detailed in Schedule ’A’. |
| 46 | Supply of distributionboard with enclosures made up of FRP/PC.Each Distribution board comprising of1 No. 100 Amps C-series 4 Pole MCCB asincomer and 3 Nos. 32A, C-series, 4 PoleMCCBs as outgoing, with suitable Copperwire/bus bars for each phase and neutralalong with all other components andaccessories etc. to be mounted in thedistribution boards including makingproper wiring etc., for all the Pump Rooms.complete as detailed in Schedule ‘A’. |
| 47 | Installation of distributionboard with enclosures made up of FRP/PC.Each Distribution board comprising of1 No. 100 Amps C-series 4 Pole MCCB asincomer and 3 Nos. 32A, C-series, 4 PoleMCCBs as outgoing, with suitable Copperwire/bus bars for each phase and neutralalong with all other components andaccessories etc. to be mounted in thedistribution boards including makingproper wiring etc., for all the Pump Rooms.complete as detailed in Schedule ‘A’. |
| 48 | Supply of all materials and accessories tocarry out the surface PVC Conduiting with3 runs 1.5 sq.mm for phase, Neutral andearth PVC insulated FR rated copper wirefor ceiling fans, LED tube light fittings, LEDentrance lights etc., through connectedjunction box along with 5A modular flushtype control switch, base plates and ceilingrose including terminations wherevernecessary from modular type switch boardto individual points. For all ElectricalSwitching rooms and Pump Rooms in TH.Colony. As detailed in Schedule ‘A’. |
| 49 | Supply of 5A flush type socket outlet alongwith base plates and switch box as detailedin Schedule ‘A’ |
| 50 | Supplyof LED 1x 20 Watts 230 V batten type cool white tube light as detailed in Schedule ‘A’ |
| 51 | Installation of LED 1x 20 Watts,230 V batten type cool white tube light asdetailed in Schedule ‘A’ |
| 52 | Supply of FRP/PC Junction box comprising of Bakelite connector plate 63Amps, 4 Bolt Type suitable to connect the 50 Sq.mm.Aluminium Armoured XLPE cabletermination as incoming and 25 Sq. mmCopper wire as outgoing to connect into the Distribution Board in residential Blocks. |
| 53 | Installation of FRP/PC Junction box comprising of Bakelite connector plate 63Amps, 4 Bolt Type suitable to connect the 50 Sq.mm.Aluminium Armoured XLPE cabletermination as incoming and 25 Sq. mmCopper wire as outgoing to connect into the Distribution Board in residential Blocks. |
| 54 | Supply of 25 Sq. mm multistrand PVCinsulated FRLS copper wire for connectingfrom FRP/PC Junction box Bakeliteconnector to Distribution board inresidential blocks. |
| 55 | Supply of Provision of Maintenance freeearthing for L.T panels and Feeder pillarsas per Schedule ‘A’. |
| 56 | Fire buckets with M.S. angle stands, withsand as detailed in Schedule ‘A’. |