| 1 | Supply, laying jointing & testingXLPE insulated armoured heavy duty electric cable with aluminium conductor1100 volts grade in trenches through DWCP pipe, fixed along pole,under floor &conforming to IS- 7098 (Part-I) with latest amendments including suitable size of thimbling at connection, laying under trench, road, walls, poles of 185 Sqmm 3.5 core sizes completed all as specified and directed |
| 2 | All as per Srl Item No. 1 here-in-before but 150 Sqmm 3.5 core |
| 3 | All as per Srl Item No. 1 here-in-before but 25 Sqmm 3.5 core |
| 4 | All as per Srl Item No. 1 here-in-before but 16 Sqmm 4 core |
| 5 | All as per Srl Item No. 1 here-in-before but 10 Sqmm 4 core |
| 6 | Supply, install, testing and commissioning CPRI approved weather and vermin proof LT feeder pillar box (Panel board) factory fabricated outdoor type totally enclosed made out of 3.15 mm thick sheet metal enclosure of suitable size, with angle iron frame of MS angle 50 X 50 X 6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting suitable and sufficient Nos circular cable entry holes at bottom only with suitable PVC/rubber bushes to prevent ingress of water/vermin etc, inside the enclosure, the required Nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated (15 micron) grey hammer tone with one coat of including connecting with LT armoured incoming and outgoing cables and including required sizes of cable lugs and angle iron stand of height not less than 2.5 Feet from AGL with earth work PCC foundation and other connected items complete all specified and directed and consisting of following :-(a) Aluminium bus bar of 600 Amp current rating capacity, length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator(b) MCCB 400 Amps 4 Pole 36 KA, 415 V - 01 No for incoming.(c) MCCB 315 Amps 4 Pole 36 KA, 415 V - 01 No for outgoing.(d) MCCB 63 Amps 4 pole16 KA, 415 V - 09 for outgoing .(e) MCB TPN 40 Amp 10 KA 415 Volt 4 Pole -02 Nos(f) 3 phase digital timer switch with contactors for auto switch on-off of street lights- 01 Set(g)Digital multifunction meter for indicating of current, voltage etc with necessary CTs - 01 No(h)LED type indicator lamp Red/Yellow/Blue colour-01 set(j)Necessary internal wiring with copper conductor incl lugs and thimbles. |
| 7 | Supply, install, testing and commissioning CPRI approved weather and vermin proof LT feeder pillar box (Panel board) factory fabricated outdoor type totally enclosed made out of 3.15 mm thick sheet metal enclosure of suitable size, with angle iron frame of MS angle 50 X 50 X 6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting suitable and sufficient Nos circular cable entry holes at bottom only with suitable PVC/rubber bushes to prevent ingress of water/vermin etc, inside the enclosure, the required Nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated (15 micron) grey hammer tone with one coat of including connecting with LT armoured incoming and outgoing cables and including required sizes of cable lugs and angle iron stand of height not less than 2.5 Feet from AGL with earth work PCC foundation and other connected items complete all specified and directed and consisting of following :-(a) Aluminium bus bar of 400 Amp current rating capacity, length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator (b) MCCB 315 Amps 4 Pole 36 KA, 415 V - 01 No for outgoing. (c) MCCB 100 Amps 4 pole16 KA, 415 V - 10 for outgoing .(d) MCB TPN 40 Amp 10 KA 415 Volt 4 Pole -02 Nos(e) 3 phase digital timer switch with contactors for auto switch on-off of street lights- 01 Set(f)Digital multifunction meter for indicating of current, voltage etc with necessary CTs - 01 No(g)LED type indicator lamp Red/Yellow/Blue colour-01 set(h)Necessary internal wiring with copper conductor incl lugs and thimbles |
| 8 | Supply, install, testing and commissioning CPRI approved weather and vermin proof LT feeder pillar box (Panel board) factory fabricated outdoor type totally enclosed made out of 3.15 mm thick sheet metal enclosure of suitable size, with angle iron frame of MS angle 50 X 50 X 6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting suitable and sufficient Nos circular cable entry holes at bottom only with suitable PVC/rubber bushes to prevent ingress of water/vermin etc, inside the enclosure, the required Nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated (15 micron) grey hammer tone with one coat of including connecting with LT armoured incoming and outgoing cables and including required sizes of cable lugs and angle iron stand of height not less than 2.5 Feet from AGL with earth work PCC foundation and other connected items complete all specified and directed and consisting of following :-(a) Aluminium bus bar of 600 Amp current rating capacity, length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator(b) MCCB 400 Amps 4 Pole 36 KA, 415 V - 01 No for incoming. (c) MCCB 250 Amps 4 Pole 16 KA, 415 V - 02 No for outgoing.(d) MCCB 100 Amps 4 pole16 KA, 415 V - 04 for outgoing(e) MCCB 63 Amps 4 pole16 KA, 415 V - 06 for outgoing .(f) MCB TPN 40 Amp 10 KA 415 Volt 4 Pole -02 Nos(g) 3 phase digital timer switch with contactors for auto switch on-off of street lights- 01 Set(h)Digital multifunction meter for indicating of current, voltage etc with necessary CTs - 01 No(i)LED type indicator lamp Red/Yellow/Blue colour-01 set(j)Necessary internal wiring with copper conductor incl lugs and thimbles |
| 9 | Supply, install, testing and commissioning CPRI approved weather and vermin proof LT feeder pillar box (Panel board) factory fabricated outdoor type totally enclosed made out of 3.15 mm thick sheet metal enclosure of suitable size, with angle iron frame of MS angle 50 X 50 X 6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting suitable and sufficient Nos circular cable entry holes at bottom only with suitable PVC/rubber bushes to prevent ingress of water/vermin etc, inside the enclosure, the required Nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated (15 micron) grey hammer tone with one coat of including connecting with LT armoured incoming and outgoing cables and including required sizes of cable lugs and angle iron stand of height not less than 2.5 Feet from AGL with earth work PCC foundation and other connected items complete all specified and directed and consisting of following :-(a) Aluminium bus bar of 400 Amp current rating capacity, length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator(b) MCCB 250 Amps 4 Pole 16 KA, 415 V - 01 No for outgoing.(c) MCCB 100 Amps 4 pole16 KA, 415 V - 02 for outgoing . (d) MCCB 63 Amps 4 pole16 KA, 415 V - 04 for outgoing .(e) MCB TPN 40 Amp 10 KA 415 Volt 4 Pole -01 Nos(f) 3 phase digital timer switch with contactors for auto switch on-off of street lights- 01 Set(g)Digital multifunction meter for indicating of current, voltage etc with necessary CTs - 01 No(h)LED type indicator lamp Red/Yellow/Blue colour-01 set(i)Necessary internal wiring with copper conductor incl lugs and thimbles |
| 10 | Supply, install, testing and commissioning CPRI approved weather and vermin proof LT feeder pillar box (Panel board) factory fabricated outdoor type totally enclosed made out of 3.15 mm thick sheet metal enclosure of suitable size, with angle iron frame of MS angle 50 X 50 X 6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting suitable and sufficient Nos circular cable entry holes at bottom only with suitable PVC/rubber bushes to prevent ingress of water/vermin etc, inside the enclosure, the required Nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated (15 micron) grey hammer tone with one coat of including connecting with LT armoured incoming and outgoing cables and including required sizes of cable lugs and angle iron stand of height not less than 2 Feet from AGL with earth work PCC foundation and other connected items complete all specified and directed and consisting of following :-(a) Aluminium bus bar of 200 Amp current rating capacity, length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator having arrangement for 03 outgoing LT cables(b) MCCB 63 Amps 4 Pole 50 KA, 415 V - 01 No for incoming.(c)LED type indicator lamp Red/Yellow/Blue colour-01 set(d)Necessary internal wiring with copper conductor incl lugs and thimbles |
| 11 | Excavating in trenches,not exceeding 1.5 m wide and not exceeding 1.5 m in depth manual excavation for laying of cables, DWCP pipes etc. and getting out soft/loose soil including making good disturbed surfaces of interlocking tiles, road etc complete all as specified and directed |
| 12 | Excavation in trenches by mechanical means (Hydraulic excavator) n.exc 1.5m wide for laying cables, DWCP pipes etc and getting out in soft/loose soilincl dressing of sides, ramming of bottom, getting out the excavated soil incl returning fillingand disposal of surplus excavated soil as directed within a lead of 50m, making good disturbed surfaces of interlocking tiles, road etc all as specified and directed |
| 13 | Returning filling in including spreading levelling watering and well ramming in layers n.exc 25cm all as specified and directed |
| 14 | Removing the excavated soil from the trench n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point all as specified and directed. |
| 15 | Supply and laying double wall corrugated pipe (DWC), non-metallic, Resistance to Compression : Type 450, Resistance to Impact: Normal, Resistance to Bending : Pliable, Resistance to External Influence: Ingress Protection : IP 67, Resistance against Corrosion : Without Protection, Resistance to Flame Propagation : Non Flame Propagating, Nominal outside diameter 77 mm, minimum inside dia 63 mm conforming to IS 16205 (Part 24) : 2017 complete all as specified and directed |
| 16 | Supply and laying double wall corrugated pipe (DWC), non-metallic, Resistance to Compression : Type 450, Resistance to Impact: Normal, Resistance to Bending : Pliable, Resistance to External Influence: Ingress Protection : IP 67, Resistance against Corrosion : Without Protection, Resistance to Flame Propagation : Non Flame Propagating, Nominal outside diameter 120 mm, minimum inside dia 103 mm conforming to IS 16205 (Part 24) : 2017 complete all as specified and directed |
| 17 | M&L for Earthing complete with galvanised mild steel earth plate electrode 600x600x6.0mm thick, buried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or riveted to earth plate at one end and connected to equipments at another end 20 dia bore GI pipe \"light grade\" as water pipe from earth chamber to upper edge of earth plate, test point , GI funnel with wire mesh fixed on water pipe andPCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1 completeall as specified and directed and testing on completion |
| 18 | S&F of hot press moulded SMC (Sheet Moulding Compound) junction box of inside dimension 210 mm x 190mm x 95mm including 4 Nos aluminium stud terminal of suitable size and one no MCB SP 2.5 amps and fixed on pole with clamps, bolts and nuts with pole complete with two coat of synthetic enamel paint powder coated as provided by manufacturer all as specified and directed |
| 19 | S&F PVC insulated multi stranded copper conductor cable1.5 sqmm two core and making connections of street light complete all as specified and directed. |
| 20 | M&L for repositioning of street lights on pole by replacing necessary clamp with nuts and bolts complete all as specified and directed. |
| 21 | S&F GI Pipe 80mm borelight grade and including GI Fitting in Trenches/on Wall or Laying in floors complete all as specified and directed . |
| 22 | S&F GI Pipe 50mm bore light grade and including GI Fitting in Trenches/on Wall or Laying in floors complete all as specified and directed . |
| 23 | M&L for drilling / boring of holes (horizontal) under main road pavement hard standing or any other situation my manual or trenchless technology mean for accommodate 100mm bore GI tube (light grade) in the drilling holes, including returning filling in the end working space including removal of surplus soil and making good the surface complete all as specified and directed |
| 24 | Disconnecting, dismantling and taking down carefully ACSR conductor from poles of LT incl accessories any size and setting a side complete and depositing at E/M store yard all as specified and directed |
| 25 | Dismantling/ taking down old cross arms, clamps, braces etc of any section from pole includingnuts, bolts, washers complete and depositing at E/M store yard all as specified and directed |
| 26 | M&L for cable route path indicators made out of precast PCC mark LT cable 1100 V having PCC pillar of size 700mmx220mmx80mm, embedded 300 mm below ground level with PCC 1:3:6 Type C1 using 20mm above ground level incl colour paint and written as per electricity rule above ground level incl excavation and earth work complete all as specified & directedNote :-A Sum of Rs. 77,550.00 will be deducted on account of credit for dismantling/ demolished/ taking down material. Please refer detail on srl page No. 27 (Schedule of credit) of Tender Documents. |