| 1 | SCHEDULE \"A\" PART-I: B/R WORKS |
| 2 | Supply & installation and commissioning of Extrusion for the components of rolling shutters shall be conforming to 53000 (NES) or 64430 (HE30) of IS:733 and IS 6248 Size of 01 shutters 5.0 x 5.0 mtr Including dismantling of old shutters complete all as specifiedand directed by the Engineer-in-charge. |
| 3 | (a)Shutters Curtain Slats - 0.9 mm / 1.2 mm thick Galvanized Steel Slats of convex corrugation (Zinc Coated Finish). |
| 4 | (b)Side Guide Channel - 3.15mm thick pressed mild steel with fixing cleats (Wall Fitment). |
| 5 | (c)Bottom lock plate - 3.15 mm mild steel with bend resistant angle stiffeners 35*35*5mm thick. |
| 6 | (d)Brackets (End Plates) - Mild steel plates made of 5mm thickness (minimum with suitable stiffeners and reinforced framework for appropriate load bearing strength (RCC Fitment) Support Bracket Flanges to be anchored to the RCC Beam with \"HILTI\" Make Anchor Fasteners. |
| 7 | (e)Barrel Shafting - Mild steel Heavy Duty Pipe of 5mm thickness and outer diameter to carry torsional load with acceptance deflection tolerance (Spring - less Shaft). |
| 8 | (f)Hood Cover - 0.9 mm Galvanised Steel for Shafting Barrel & Automation Drive. |
| 9 | (g)Finish - Only Mild Steel Parts will be spray primed with of Further Finishing / Painting after Installation in MES Contractor scope. |
| 10 | (h)Locking Arrangements - Sliding Steel Hasps on Bottom Lock Plate. |
| 11 | (j)Automation : Electric Operation and Control Box - \"SWASTIK\" MAKE SWD - Side Motor - Three Phase - (CE Certified) with Indirect Drive Chain Transmission with Inter - Build Mechanical Rotary Cut Off Limit Switches with High Precision Reduction Gearbox, with Up-Stop-Down-Push Button Switch Control Station with 2 meter wires with provision of Emergency Manual Override Chain Operation in case of power failure Push Button Switch to be enclosed with metal key lock box. |
| 12 | -Ditto- all as per item No.1 above but size 3.0M X 3.50M |
| 13 | -Ditto- all as per item No.1 above but size 4.0M X 4.0M |
| 14 | -Ditto- all as per item No.1 above but size 3.0M X 4.0M |
| 15 | -Ditto- all as per item No.1 above but size 2.5M X 3.5M |
| 16 | -Ditto- all as per item No.1 above but size 3.5M X 4.0M |
| 17 | Taking down cement plaster onbrick work, racking out joints, hacking for key scrubbing down with water etc complete and removing outside MD land . |
| 18 | M&L for providing 10 mm thick one component chloride free thixotropic fibre reinforced polymer modified repair mortar with alkali resistant synthetic fibres for exceptional resistance cracking complies ASTMC 109 with flexural strength ASTM C 348 @ 7 days meeting 7N/mm2, tensile strength @ 7days (ASTM C 307)> 3 N/mm2, compressive strength of 35Mpa at 7 day and 45Mpa at 28 days, Adhesion bond strength> 2 N/mm2 ,Creep Strain Reduction- 10% at the outer or inner RCC ceiling surface.cement and sand can be used for finishing purpose. It should be specially adhered to BS 6319 having specific gravity of 1.025 to 1.04, minimum 43% solid contents complete all as specified and as directed.Make : Thermax Ltd, Tiki tar Danosa(Pvt)Ltd,M/s Torchtar menbranes & bitumen products Pvt. Ltd or Equivalent. |
| 19 | M& L for preparing newly plastered surfaces of walls and applying two coats of white wash. |
| 20 | SCHEDULE \"A\" PART-II: E/M WORKS |
| 21 | Supply and fixing Factory made sheet metal enclosure MCB DB SPN 4 way, 240 volt, double door, IP-42 protection with suitably rated bus bar (fixed flush to the wall and making good disturbed surfaces) complete all as specified. [Note: Incoming and outgoing MCBs will be measured and paid separately under relevant items in the schedule] |
| 22 | Supply and fixing of MCB 6 to 32 Amp, 240 Volt, SPN, breaking capacity 10 KA \"C\" series, complete all as specified |
| 23 | Supply and fixing ofMCB 6 to 32 Amp, 415 Volt, Triple pole , breaking capacity 10 KA \"C\" series, complete all as specified |
| 24 | Material and labour for point wiring with 2.5 Sqmm PVC insulated and unsheathed copper cable 1100V, FRLSgrade multi-stranded drawn in and including suitable size of PVC conduit totally concealed/surface conduit in walls/ceiling with tee , bend, elbows, junction box etc. with provision of PVC insulated 2.5 sqmm copper conductor cable as earth continuity including prefabricated modular galvanised boxes with white modular frame and cover plate of suitable size for fixing modular switches, sockets regulator and connected the earth wire to common earth dollyfor5A socket point on independent board controlled by one switch complete all as specified and as directed. [Note:-(i) Thequoted rate shall includes all the cost of cutting, chasing, cementing work where required and makingall the disturbed surfaces of wall / ceiling good to match the existing wall / ceiling with same colour.] |
| 25 | M&L for modular switch 1way 16 Amps, 1 module 230V of 1 module complete all as specified and directed. |
| 26 | M&L for modularsocket outlet 3 pin, 15/16 Amp 2module 230V complete all as specified and directed. |
| 27 | M & L for Sub main/ circuit wiring with one run of four core 2.5 sqmm PVC insulated and unsheathed multi-stranded copper cable 1100 V grade, un-armoured and overall PVC sheathed, drawn in and including suitable size of PVC conduit totally concealed/ surface in walls/ ceiling with tee , bend, elbows, junction box etc. (for connecting motor starter with motor) complete all as specified. |
| 28 | M & L for Sub main/ circuit wiring with 2 runs of single core 6.0 sqmm FR PVC insulated and unsheathed multi-stranded single core copper cable 1100 V grade, drawn in and including suitable size of PVC/ steel conduit totally concealed/ surface in walls/ ceiling with tee , bend, elbows, junction box etc. alongwith provision of one run of 6.0 sqmm FR PVC insulated unsheathed multi-stranded copper cable as earth continuity conductor connected to common earth dolly complete all as specified. |
| 29 | M & L for Sub main/ circuit wiring with 4 runs of single core 6.0 sqmm FR PVC insulated and unsheathed multi-stranded single core copper cable 1100 V grade, drawn in and including suitable size of PVC/ steel conduit totally concealed/ surface in walls/ ceiling with tee , bend, elbows, junction box etc. alongwith provision of 2 runs of 6.0 sqmm FR PVC insulated unsheathed multi-stranded copper cable as earth continuity conductor connected to common earth dolly complete all as specified. |
| 30 | M & L for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level and cut tapered at the bolt omconnected with earthing lead of 4mm dia galvanised iron or steel wire all as shown in Plate No. 2 to the earthing test point all as specified and indicated including testing on completion (Earth lead wire 4.0 mmwill be protected by GI pipe 15 mm, Medium Grade for earthing lead protection to the extent of maximum 7.5m, Earth Plate Electrode surrounded by 150 mm thick packed layers of Charcoal and Common Salt filled in alternate layers and funnel and wire mesh complete all as per Electrical Plate No 2 of SSR Part - I, Pit cover PCC (1:2:4, Type B1) Pit with RCC 1:2:4, Type B1 Cover, 50mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS Funnels, watering Pipe, funnel, Wire Mesh, Earth Work excavation, return filling, removal of surplus soil etc. of any description complete all as specified and directed. |
| 31 | M & L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in and including conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire |
| 32 | M & L for Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos 8 mm dia 25mm long hex. head screw |