| 1 | Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 95 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing including taking down complete all as specified and as directed. |
| 2 | S & F XLPE cable end termination, heat shrinkable, indoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core 50 sqmm to 95sqmm complete all as specified and as directed. |
| 3 | S & F XLPE cable end termination, heat shrinkable, outdoor type complete with jointing material and accessories suitable for voltage 11 kV (Earthed), 3 core 50 sqmm to 95 sqmm complete all as specified and as directed. |
| 4 | Supply & laying unreinforced precast concrete cable cover class HVP type 1, with peak shape, dimension 300 mm X 180 mm X 40 mm and 65 mm peak thickness as per IS 5820: 1970 complete all as specified and directed. |
| 5 | M & L for cross arms, bracings, supports, clamps, back plates and stay clamp fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed. |
| 6 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or water supply pipes lines etc or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed. |
| 7 | Excavating in trenches not exceeding 1.5 m wide and exceeding 1.5 m but not exceeding 3.0 in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and exceeding 1.5 m but not exceeding 3 m in depth and getting out in soft/ loose soil complete all as specified and as directed. |
| 8 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed. |
| 9 | Removing excavated material (excluding hard rock) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. |
| 10 | Supply & laying Sand coarse dry as in cushioning of underground electric cable in trenches, laid to a uniform thickness of 23cm (15cm under the cable & 8cm over the cable) and gently punned down to 18cm thickness complete all as specified and as directed. Note :- Only punned down sand shall be measured. |
| 11 | Supplying & laying in trenches 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. |
| 12 | Supply and fixing of Air break gang operated switch triple pole mechanically operated out door with all fitting/ accessories mounted on and including 11 KVporcelain insulator and steel channel frame GI operating rod 25 mm dia of suitable length with operating mechanism worked from ground level vertically or horizontal operated as per site requirement including locking arrangement for operating handle complete suitable for current rating 200 Amps11 KVworking pressure with 9 Insulators complete all as specified and directed. |
| 13 | Supply and erection in replacement of lightning arrestor (set of 03), explusion type suitable for 11 kV continuous operating voltage (3 phase) with rated voltage 24 kV (rms) with nominal discharge capacity of 65 kA and complete with galvanised clamping arrangements, GI bolts, nuts, washers etc. complete as specified and as directed. Note- Lightning attester shall be able to withstand wind load of 196Kg/Sqm and seismic acceleration of 0.39g. |
| 14 | M & L for steel tubular swaged pole 410 SP-55 (11.0 metre long) seamless type, including CI base plate, finial taper plug, bolts, nuts & screws as per IS 2713 Part -I & II including painting with two coats of bituminious paint over a coat of red oxide zinc chrome primer on exposed portion and making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and two coats of anticorrosive paint over a coat of red oxide primer to embedded portion of pole including making good to match existing area complete all as specified and as directed. Note- Earthwork and PCC shall be measured and paid seperately. Volume occupied by steel pole shall be deducted to derivethe quantity of PCC. |
| 15 | M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 16 | M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs, slab staging for water tanks, filling of pressed steel door frame, fixing of hold fasts and the like including weathering, slightly rounded or chamfered angles and throating including necessary formworks complete all as specified and directed. |
| 17 | M & L for auguring under road, pavement, hard standing, railway lines by trenchless technology using latest boring technique and necessary machine including insertion of HDPE pipe of 150 mm dia complete all as specified and as directed. |