| 1 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm |
| 2 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm |
| 3 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 4 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 5 | Supplying and fixing following rating, Four pole,415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (b) 63 amps |
| 6 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (b) 63 amps |
| 7 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 8 | Providing and Fixing FRP Fencing rust proof, shock proof, anti- corrosive, selfextinguishing, ultra violet stabilized, VOUL94, weather proof, flame retardant, environment friendly, yellow in color installed at electrical installations with necessary concreting for grouting vertical post, hardware, accessories, fitting etc. with minimum 300mm grouting in ground along with 1 number of FRP almirah type double door gates with necessary hardware accessories like stainless steel heavy duty L-Drop, Hinges, screws, nut and bolt, lock fittings, etc. with vertical post of size 50x50x3mm, sub-frame of 50x25x3mm, pickets of size 38x15mm, Cylindrical rods of 12mm dia, hollow section size of not more than 5x5inch and also providing 1 number MS danger plate of size 250x200x2mm,1 number MS name plate of property of MCD and sponsors name as per site requirement. The product should comply the various standards for FRP fencing like IS 13410-ASTM D 2584, D792, D570, D256, D638, D695, D790, D495, D149, D648, IS13360, IS6746. The compliance report of above national/international standard may be referred if required. |
| 9 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.lKV grade conforming to IS- 7098 of following size:- (a) 2x10 sqmm |
| 10 | LED Streetlight fixture, powdercoatedpressurediecast aluminumbody(Systemlumen efficacy≥120 <135 lm/Watt)- Supplying,installation,Testing&CommissioningofStreetlightLED fixturepowdercoatedpressurediecastaluminumbodywith driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5KVL,N,EasperIEC61000-4-5,Driver efficiency >85%,THD< 10%asperIEC61000-3-2,P. F.≥0.95,IP 66,IK-10,CRI>80,undervoltageandovervoltageprotection,EMI EMCAsper CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) ofminimum 50000BurningHourswith70%ofinitial Lumenmaintained tilllife ends as per LM80 extrapolation IES TM-21-11 report,CCT 3000°K / 4000°K/ 5700°K/6000°K/6500°K (AsperANSIBin), SDCM(Standard Deviation Color Matching) <5, Maximumpowerconsumption should not more than the specified rating and Fixture shall be of relevant BIS standard completeinallrespecti/cconnectionswith1.5sqmmFRLS,PVCinsulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy ≥120 <135lm/Watt output . LM79 & LM80 Test reportfromNABLlab foralltestingrequired forLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management:heatsinkofaluminumhousing such that LED junction temperature shall not rise above 90°C)- 150 Watt |
| 11 | Supplying, lowering, testing and commissioning of vertical type, multistage, totally enclosed water filled deep well submersible pumping set complete i/c connection etc. as reqd. Single Phase 1.5 HP having discharge of 72 LPM Approx. at 49 M Head. |
| 12 | Supply, Installation, testing and commissioning of cubical type control panel board for single phase & Three Phase submersible pumping set of following rating complete with contactor, relay , MCB ,condenser ,voltmeter, ammeter and indication lamp etc including connections etc as reqd. 1.5 HP (Single Phase) |
| 13 | Development of tube well with suitable capacity of air compressor i/c lowering of the necessary induction pipe or linei/c cost of fuel, hire charges of compressor etc as reqd. The development shall be considered complete when Gravel stop sinking, Discharge ceased to improve and the sand contents are not more than 10 PPM after 20 minutes of starting the pump complete as reqd. |
| 14 | P&F following sizes of PVC insulated & PVC sheathed copper conductor 3 core submersible cable confirming to IS.694/1990 etc. as reqd. a 3x 2.5 sq.mm |
| 15 | Supply, lowering and fixing following size of G.I. Pipe (M-Class) i/c cutting threading on both sides etc. ISI marked etcas reqd. b) 40 mm(Nominal Bore) |
| 16 | S & F following size of G.I. Socket. as reqd. 40 mm |
| 17 | S & F following size of G.I. Elbow. as reqd.40 mm |
| 18 | S & F MS clamp made up of iron flat of size 50X6 mm with 4 nut bolt for holding the GI pipe pipe as reqd. 50 mm |