| 1 | Excavation in trenches n.exc.1.5 mtr depth for foundation and getting out for laying of pipes/foundation for RMU/cable in any type of soil complete(Hard dense soil) all as specified and directedby Engr-in-charge. |
| 2 | Returning filling in including spreading levelling, watering and well ramming in layers not exc. 25cm in any type of soil |
| 3 | Removing exavated materials not exc 50 mtr and depositing where directed at a level not execeeding 1.5 mtr above the starting point. |
| 4 | Earth cushining to UG cables using excavated soil riddled by using large sleave to separte the composite particles/roots etc and refilling in trenches all as specified |
| 5 | Supply and lay burnt bricks sub-class \"B\" designation 75 for cable protection all as specified and as directed. |
| 6 | Dismantling of steel poles/struts any size and transporting from site and making good the disturbed area and cutting the poles at below the griound level approx 30 cm in depth complete all as directed |
| 7 | Supply, layig, connecting, testing and commissioning of 16 Sqmm 4 Core under ground LT cable XLPE insulated screened, PVC bedded, armoured heavy duty electric cable confirming to IS : 7098-1985 with stranded aluminium conductor 1100 volts laid in trenches, floor, fixed to walls/drawn through pipe, duct or along the pole and incl the disturbence surface of road making good with using PCC, fixing the cable with suitable size glands, crimping type lugs etc all as specified and directed including taking down unserviceable cable all as directed .Make: Havells/Polycab/Finolex/Paragon/Gloster/Nicco |
| 8 | All as per Item No 07 here - in - before but 16 Sqmm 2 core complete. |
| 9 | All as per Item No 07 here - in - before but 10 Sqmm 2 core complete. |
| 10 | All as per Item No 07 here - in - before but 25 Sqmm 4 core complete. |
| 11 | Supply and laying GI pipe light grade 50 mm bore including all type fitting such as bends, elbows, tee etc fixed on walls/to poles/laid in trenches as cable protection all as specified and as directed. |
| 12 | All as per Item No 10 here in before but 40 mm dia |
| 13 | M&L for dismantling / cutting of existing road / path / hard standing cement concrete (unreinforced) in ground floors and pavings n.exc 15 cm thickness (below or above ground level) suitable for laying cable protection pipe 80 / 50 mm dia under the road / path / hard standing complete. |
| 14 | Material and labour for PCC (1:4:8) type D-2 (using 40 mm graded crushed stone aggregate) for making good the disturbed surface of road/path/hard standing/ foundation of pole by using cement contrete mortar 1:2:4 type B1, using 40 mm graded stone aggregate 0.45 mtr wide and 0.15 mtr thick complete all as specified and directed. including demolition of old PCC and removing the debris from site complete all as specified and as directed at site by the Engr-in-Charge. |
| 15 | All as per item No 14 Above but for copping of poles Type C1 1:3:6 20 mm graded stone aggregate all as directed |
| 16 | Supply and fix steel tubular swaged poles complete with cast iron base plate, final taper plug, bolts nts & screws as specified type 410 SP -22 8.5 mtr long including taking down old poles all as directed |
| 17 | Supply and fixGI bracketof size40 mm dia 1.20 Mtr long GI pipe light grade bent to shape ncluding neccessary fixing arrangement such as nuts, bolts, washers, MS clamps made of 20x5 mm and making connection etc including taking down old brackets all as directed |
| 18 | Supply only Energy saving and environmental friendly long life 45/48 W LEDstreet light made up of pressure die cast aluminium housing with high efficiency LED as lighting source and lens embedded PC cover having bottom opening separate drive compartment with IP66and impact resistance of IK08 with motion sensor bright/dim mode complete Cat No LST 48 SEN including taking down old unserviceable lights all as specified and directed Make : Havells, Bajaj ,Crompton, Luker |
| 19 | All as per Item No 18 Above but 70/72 wattsCat No LST 72 SEN |
| 20 | Supply only Energy saving and environmental friendly long life ecxclusive innnovative die-cast aluminium IP66 flood light150/160W LED with driver unit Cat No LFL160 complete including taking down old unserviceable lightsall as directed Make : Havells /Bajaj/ Crompton/Luker |
| 21 | All as per Item No 20 Above but 100 wattsCat No LFL 100 |
| 22 | Supply and fixCable junction box IP66 halogen free and weather proof for out door installation made of thermoplastic material of size 195 mm x135 mm x 90 mm, suitable for upto 16 sqmm cable entry & cable out opening , fitted with 01 Nos MCB , SP 6 to 32 amps for street light complete internally pre-wired fitted with terminals,connectors etc and including neccessary fixing arrangement such as nuts, bolts, washers, MS clamps made of 20x5 mm and painting etc including making connection complete including taking down old unserviceable boxes all as directed. Make: Hensel, Sintex, Array |
| 23 | All as per Item No 22 here - in - before of size 295 mm x 195 x 100 mm complete. |
| 24 | Supply and fix street light timer panel outdoor type IP 54 protection internal wiring with FRLS cable of suitable capacity, inbuilt short circuit protection Supply, CPRI approved outdoor type suitable for 415V, 3 Phase, 4 wire, 50 Hz, AC supply system fabricated from CRCA sheettotally enclosed, dust, weather & vermin proof, front openable, single door system lockable / openable by keys fancy locksair vent gasket for natural flow of air, the bottom of the shell contains a detacheable plate having provision for entry of adequate size with glands, 3.0 mm thick for outer shell confirming to IS/IEC 61439/60529 suitable to mounting on walls/floor with necerssary clamp with nut bolt washer etcincluding connecting up all incoming and outgoing cable withcable gland with following accessaries for three phase max load 12 KW, contactor 65 Amps TP. MCB 63 Amps TPN 2 Nos, digital/analog 24 hrs time switch, on/off , phase indication lights including taking down old unserviceable timers all as directed:- (Make - Havells/L&T CPRI approved manufacture) |
| 25 | Supply and lay reinforced precost concrete cable cover class LV type 1 flat size 250 x 180x 40 mm all as directed. |