| 1 | Supply, fixing, commissioning and testing of CPRI approved outdoor cubical type LT Feeder pillar box suitable for 415volts 3 phase 4 wire, 50 HZ AC supply system, floor mounted, outdoor type factory fabricated duly power coated inside and outside, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6 mm covered from all side with front and back openable, weather proof including suitable size rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embedded in brickwork in CM 1:4 with suitablefoundation for fixing panel of required size in ground with nuts, bolts and washer etc. including comprising of following including taking out the old unserviceable panel complete all as specified and directed .Incoming:-(a) ACB 630 Amp 4 pole 50 KA,Manual draw out type with Microprocessor release, Ics=100% of Icu, LCD display, Thermal memory, Zone selectivity, Current & Voltage Measurement, Advance protection, over temperature protection, fault history, V/V and O/V release - 01 No.(b) Alum bus bar 1000 Amp TPN - 01 Set(c) Digital Multifunctional meter Showing V, I, PF, HZ etc with suitable CT ratio(d) Indicator lamp LED type (RYB) complete with bakelite fuse fitting- 01 setOutgoing :-(a) MCCB 4 Pole, 250 Amp, 35 KA, Adjustable Thermal &Magnetic setting , Ics = 100% of Icu-04 No.s(b) MCCB 4 Pole, 200 Amp, 35 KA Adjustable Thermal & Magnetic setting , Ics = 100% of Icu - 02 No.s(c) MCCB 4 Pole,100 Amp,25 KA ,Adjustable Thermal &Magnetic setting , Ics = 100% of Icu - 02 No.s |
| 2 | Supply, fixing, commissioning and testing of CPRI approved outdoor cubical type LT Feeder pillar box suitable for 415volts 3 phase 4 wire, 50 HZ AC supply system, floor mounted, outdoor type factory fabricated duly power coated inside and outside, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6 mm covered from all side with front and back openable, weather proof including suitable size rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embedded in brickwork in CM 1:4 with suitablefoundation for fixing panel of required size in ground with nuts, bolts and washer etc. including comprising of following including taking out the old unserviceable panel complete all as specified and directed by Engineer-in-Charge.Incoming:-(a) ACB 630 Amp 4 pole 50 KA,Manual draw out type with Microprocessor release, Ics=100% of Icu, LCD display, Thermal memory, Zone selectivity, Current & Voltage Measurement, Advance protection, over temperature protection, fault history, V/V and O/V release - 01 No.(b) Alum bus bar 1000 Amps TPN - 01 Set(c) Digital Multifunctional meter Showing V, I, PF, HZ etc with suitable CT ratio-01 No.(d) Indicator lamp LED type (RYB) complete with bakelite fuse fitting- 01 setOutgoing :-(a) MCCB 4 Pole, 250 Amp, 25 KA, Adjustable Thermal & Magnetic setting , Ics = 100% of Icu-03 No.s(b) MCCB 4 Pole, 200 Amp, 25 KA Adjustable Thermal & Magnetic setting , Ics = 100% of Icu - 02 No.s(c) MCCB 4 Pole, 100Amp,16 KA ,Adjustable Thermal & Magnetic setting , Ics = 100% of Icu - 01 No. |
| 3 | Supply, installation and commissioningand testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricatedduly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partitionmade out of 2 mm thickCRCAsheet with angle iron 45 mm x 45 mm x 6mmcovered from all side with front and back openable, weather proof including suitable rating aluminium busbar for 3 phase 4 wire system, wiring with suitable size coppercable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground withnuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed by Engineer-in-ChargeIncoming:-(a) MCCB 100 Amp 4 pole 16 KA 415 volts AC, Adjustable Thermal and Fixed Magnetic setting with Ics = 100 %Icu , - 01 No.(b) Alumbus bar 200 Amp TPN - 01 Set(c) Digital voltmeter 0-500 volts with selector switch - 01 No(d) Digital Amp meter0-500 Amp with selector switch & CT - 01 No(e) Indicator lamp LED type (R, Y, B) complete with bakalite fuse fitting - 01 Set(f)On load change over switch, 100 Amp capacity, 3 phase, 4 pole, 415 volts, 50Hz-01 No.Outgoing :-(a) MCCB 4 pole, 63 Amp, 16 KA, 415 volts Adjustable Thermal and Fixed Magnetic setting with Ics = 100 %Icu - 04 Nos(b) Fully automatic Star Delta Starter for 30 HP Motors ,22 KW 415 V 50 HZ,40 Amps, ML-2 -03 Nos(c)Single phase preventor (Relay scale 20-32 Amps)-03 Nos |
| 4 | Supply, installation and commissioningand testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricatedduly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partitionmade out of 2 mm thickCRCAsheet with angle iron 45 mm x 45 mm x 6mmcovered from all side with front and back openable, weather proof including suitable rating aluminium busbar for 3 phase 4 wire system, wiring with suitable size coppercable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground withnuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed by Engineer-in-ChargeIncoming :-(a)MCCB 100 Amp 4 pole 16 KA I415 volts AC, Adjustable Thermal and Fixed Magnetic settingwith Ics = 100 %Icu - 01 Nos(b) Alumbus bar 200 Amp TPN - 01 Set(c) Digital voltmeter 0-400 volts with selector switch - 01 No(d) Digital Amp meter0-400 Amp with selector switch & CTs - 01 No(e) Indicator lamp LED type (R, Y, B) complete with bakalite fuse fitting - 01 Set(f)On load change over switch, 100 Amp capacity, 3 phase, 4 pole, 415 volts, 50Hz-01 No.Outgoing :-(a) MCCB 3 pole, 100 Amp, 16 KA, 415 volts AC- 03 No(b)MCCB 3 pole, 63 Amp, 16 KA, 415 voltsAC- 01 No(c)Fully automatic Star Delta Starter for 40 HP Motors,30 KW 415 V 50 HZ,55 Amps, ML-3 complete-01 No prewired-03 Nos(d)Single phase preventor (Relay scale 28-42 Amps)-03 Nos |
| 5 | Supply, installation and commissioningand testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricatedduly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partitionmade out of 2 mm thickCRCAsheet with angle iron 45 mm x 45 mm x 6mmcovered from all side with front and back openable, weather proof including suitable rating aluminium busbar for 3 phase 4 wire system, wiring with suitable size coppercable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground withnuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed by Engineer-in-ChargeIncoming :-(a) MCCB 63 Amp 4 pole 16 KA 415 volts AC, AdjustableThermal and Fixed Magnetic settingwith Ics = 100 %Icu- 01 Nos(b) Alumbus bar 200 Amp TPN - 01 Set(c) Digital voltmeter 0-500 volts with selector switch - 01 No(d) Digital Amp meter0-500 Amp with selector switch & CT - 01 No(e) Indicator lamp LED type (R, Y, B) complete with bakalite fuse fitting - 01 Set(f)On load change over switch, 63 Amps, 4 pole, 415 volts, 50Hz-01 No.Outgoing :-(a) MCCB 4 pole, 40 Amp, 16 KA, 415 volts Adjutable Thermal and Fixed Magnetic setting with Ics = 100 %Icu- 04 Nos (b) Fully automatic Star Delta Starter for 20 HP Motors ,15 KW 415 V 50 HZ,28 Amps, complete with contactors and pre-wired -03 Nos (c)Single phase preventor (Relay scale 10-16 Amps)-03 Nos |
| 6 | Supply, installation and commissioningand testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricatedduly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partitionmade out of 2 mm thickCRCAsheet with angle iron 50 mm x 50 mm x 6mmcovered from all side with front and back openable, weather proof including suitable rating aluminium busbar for 3 phase 4 wire system, wiring with suitable size coppercable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground withnuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed by Engineer-in-ChargeIncoming :-(a) ACB 630 Amp 4 pole 50 KA,Manual draw out type with Microprocessor release, Ics=100% of Icu, LCD display, Thermal memory, Zone selectivity, Current & Voltage Measurement, Advance protection, over temperature protection, fault history, V/V and O/V release - 01 No.(b) Alum bus bar 1000 Amp TPN - 01 Set(c) Digital Multifunctional meter Showing V, I, PF, HZ etc with suitable CT ratio-01 No.(d) Indicator lamp LED type (RYB) complete with bakelite fuse fitting- 01 set(e)On load change over switch 630 Amps, 4 pole, 415 volts, 50Hz-01 No.Outgoing :-(a) MCCB 4 pole, 400 Amp, 36 KA, 415 volts Adjutable Thermal andMagnetic settingwith Ics = 100 %Icu- 01 No.(b) MCCB 4 pole, 250 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic settingwith Ics = 100 %Icu- 03 Nos |
| 7 | Supply, installation and commissioningand testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricatedduly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partitionmade out of 2 mm thickCRCAsheet with angle iron 50 mm x 50 mm x 6mmcovered from all side with front and back openable, weather proof including suitable rating aluminium busbar for 3 phase 4 wire system, wiring with suitable size coppercable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground withnuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed by Engineer-in-ChargeIncoming :-(a) MCCB 315 Amp 4 pole 36 KA 415 volts AC,Adjutable Thermal and Fixed Magnetic setting with Ics = 100 %Icu- 01 No.(b) Aluminium bus bar 500 Amps TPN - 01 Set(c) Digital voltmeter 0-500 volts with selector switch - 01 No(d) Digital Amp meter0-500 Amp with selector switch & CTs - 01 No(e) Indicator lamp LED type (R, Y, B) complete with bakalite fuse fitting - 01 Set(f)ON load change over switch, 315 Amps, 4 pole, 415 volts, 50Hz-01 No.Outgoing :- (a) MCCB 4 pole, 250 Amp, 25 KA, 415 volts AdjustableThermal and Magnetic settingwith Ics = 100 %Icu- 03 Nos(b) MCCB 4 pole, 100 Amp, 16 KA, 415 volts Adjutable Thermal andMagnetic setting with Ics = 100 %Icu- 02 Nos |
| 8 | S&F commissioning and testing of CPRI approved outdoor cubical type LT Feeder pillar box suitable for 415volts 3 phase 4 wire, 50 HZ AC supply system, floor mounted, outdoor type factory fabricated duly power coated inside and outside, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6 mm covered from all side with front and back openable, weather proof including suitable size rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embedded in brickwork in CM 1:4 not less than 45 cm above ground level with suitablefoundation for fixing panel of required size in ground with nuts, bolts and washer etc. including comprising of following incluidng taking out the old unserviceable panel complete all as specified and directed by Engineer-in-Charge.Incoming :-(a) ACB 630 Amp 4 pole 50 KA,Manual draw out type with Microprocessor release, Ics=100% of Icu, LCD display, Thermal memory, Zone selectivity, Current & Voltage Measurement, Advance protection, over temperature protection, fault history, V/V and O/V release - 01 No.(b) Alum bus bar 800 Amps TPN - 01 Set(c) Digital voltmeter 0-500 volts with suitable PT and selector switch - 01 No(d) Digital Amp meter 0-1000 Ampwith selector switch & suitable CT - 01 No(e) Indicator lamp LBD type (RYB) complete with bakelite fuse fitting- 01 setOutgoing :-(a)MCCB 4 Pole, 400 Amp, 36 KA,Adjustable Thermal &Magnetic setting , Ics = 100% of Icu- 01 Nos(b)MCCB 3 Pole, 250 Amp, 25 KA, Adjustable Thermal & Magnetic setting , Ics = 100% of Icu- 02 Nos(c)MCCB 3 Pole, 160 Amp, 25 KA, Adjustable Thermal & Magnetic setting , Ics = 100% of Icu - 02 Nos |
| 9 | Supply, installation and commissioningand testing of LT panel cubical type suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricatedduly powder coated inside and out side, outer cover made out of 3mm thick CRCA sheet, internal cover and partitionmade out of 2 mm thickCRCAsheet with angle iron 50 mm x 50 mm x 6mmcovered from all side with front and back openable, weather proof including suitable rating aluminium busbar for 3 phase 4 wire system, wiring with suitable size coppercable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground withnuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed by Engineer-in-Charge. Incoming:-(a) MCCB 4 pole, 250 Amp, 25 KA, 415 volts AC with adjustable thermal and fixed magnetic setting- 01 No.(b) Aluminiumbus bar 400 Amps TPN - 01 Set(c) Digital voltmeter 0-500 volts with selector switch - 01 No.(d) Digital Amp meter0-300 Amp with selector switch & CTs - 01 No(e) Indicator lamp LED type (R, Y, B) complete with bakalite fuse fitting - 01 SetOutgoing:-(a) MCCB 4 pole, 160 Amp, 25 KA, 415 volts AC adjustable thermal and magnetic setting - 02 Nos(b) MCCB 4 pole, 125 Amp, 25 KA, 415 volts AC adjustable thermal and magnetic setting- 01 No.(c) MCCB 4 pole, 100 Amp, 16 KA, 415 volts AC adjustable thermal and magnetic setting- 02 Nos |
| 10 | Supply, installation and commissioningand testing of LT panel cubical type suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricatedduly powder coated inside and out side, outer cover made out of 3mm thick CRCA sheet, internal cover and partitionmade out of 2 mm thickCRCAsheet with angle iron 50 mm x 50 mm x 6mmcovered from all side with front and back openable, weather proof including suitable rating aluminium busbar for 3 phase 4 wire system, wiring with suitable size coppercable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground withnuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed by Engineer-in-Charge.Incoming:-(a) MCCB 4 pole, 400 Amp, 36 KA, 415 volts AC with adjustable thermal and fixed magnetic setting- 01 Nos(b) Aluminiumbus bar 600 Amp TPN - 04 Nos(c) Digital voltmeter 0-500 volts with selector switch - 01 No(d) Digital Amp meter0-500 Amp with selector switch & CT - 01 No(e) Indicator lamp LED type (R, Y, B) complete with bakalite fuse fitting - 01 SetOutgoing:-(a) MCCB 3 pole, 250 Amp, 25 KA, 415 volts AC, adjustable thermal and magnetic setting- 02 Nos(b) MCCB 3 pole, 200 Amp, 25 KA, 415 volts AC, adjustable thermal and magnetic setting- 01 No.(c) MCCB 3 pole, 100 Amp, 16 KA, 415 volts AC, adjustable thermal and magnetic setting- 02 Nos |
| 11 | S & Fin Feeder piller box out door type ‘factorymade’ made out from 16 SWG MS sheet supported with legs of 45cm long made of iron angle 25x25x4mm thick of size 75cm x60cm x45 cm with 04 Nos aluminiumbus bar of400 Amps mounted on porcelain insulatorduly drilled hole for cable connection including front and rear side opening with locking arrangement, with MCCB FP 250 Amp, 36 KA, 415 Volts 50 Hz with adjustable thermal and adjustable magnetic setting and provn for incoming and outgoing cables withglands including painting with two coat of smoke grey synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge |
| 12 | S & F in Feeder piller box out door type ‘factorymade’ made out from 16 SWG MS sheet supported with legs of 45cm long made of iron angle 25x25x4mm thick of size 75cm x60cm x45 cm with 04 Nos aluminiumbus bar of250 Amps mounted on porcelain insulatorduly drilled hole for cable connection including front and rear side opening with locking arrangement, with MCCB FP 200 Amp, 36 KA, 415 Volts 50 Hz with adjustable thermal and adjustable magnetic setting and provn for incoming and outgoing cables withglands including painting with two coat of smoke grey synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in-ChargeNote for item No. 01 to 12:- 1.Feeder pillar box shall be mounted on brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation, rendering 15 mm in CM 1:6 and two coats of cement base paint and the rates shall be inclusive in the quoted rate. 2.Old cables shall be refixed in panels with suitable size of glands, lugs, nut bolts and washers as required at site to be provided by the contractor is deemed to be included in the item rate. |
| 13 | M&L for earthing complete in replacement with galvanized steel earth plate electrode of size 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters below ground level) with top edge of earth plate not less than 1.5 meters below ground level surrounded on all sides by 150 mm thick charcoal & common salt startingfrom ground below earth plateupto 150mm above GI plate in alternate layersconnected to galvanized earth strip 25X4 mm by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel,PCC (concrete chamber of size 300 mm x 300 mm x 300 mm inside dimension) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate with fair finish ,internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire mesh of 22 gauge,80 mm thick PCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI pit all as shown in electrical plate No 5 of MES SSR Part-I (2009) as specified includingprovision of 40mm dia medium grade GI pipe for earth strip protection and 20 mm dia for watering complete ,all excavation andearth work & connecting the earthing to an earthing test point /LT Panel as specified and testing on completion for desired result complete all as specified and directed by Engr-in-charge. Note:- Earth strip up to 7.5 mtr from the earth plate is included in the item rate. |