| 1 | Part A- Creation of 05 no. 1 MVA Substations & 05 no. Servo Stablizers along with HT network |
| 2 | Supply, Installation, testing and commissioning of 11/0.433kV, 3-phase 1 MVA Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2 (Level-1 BIS post amendment), (Copper wound ), normal Tap Changer (OCTC) on HV side and with LV Cable Box having detachable Aluminium Gland plate |
| 3 | Supply,installation, testing and commissioning of Gapless Surge Arrestor, 9 kV, 10 kA, Lighting Arrestor Set Heavy duty with Plymer Housing, Station type conforming to IEC-99-4 Capable of withstanding Maximum continuous operating voltages (M.C.O.V) |
| 4 | Supply, installation, testing and commissioning of 11KV 200 Amperes, Triple pole switches Gang Operated (G.O. Set) conforming: IS-2544, IS: 5340 (Part-III) and SS: 9921 (Part-I -V) |
| 5 | Supply, installation, testing and commissioning of 11 KV Horn, Gap (fuse 3-phase 200A) as per Relevant IS. |
| 6 | Supply, fabrication & installation of GI Channel/Angle/Flat of sizes including including Back clamps/Collars for 1. L.A Set/G.O Set/Horn Gap = 150 kg x 5 = 750 kg2. Transformer Pad/G.I Channel Bedding = 600 kg x5 = 3000 kg3. Covered Cable trays along with Galvanised Steel Structure for proper routing of cables = 200 kg x 5 = 1000 kg4. Support Galvanised angle frame and legs (50mm x 50 mm x 6 mm) for Distribution Feeder Pillar , leg height 1m with 0.3m in soil approx 7m @4.50Kg per mtr = 31.5 kgx5 = 157.5 kg5. HT network - 460 kg |
| 7 | Supply, fabrication & installation of G.I Pipe of 150 mm dia 2 mtr long for Pole Butts (6\") |
| 8 | Supply, Installation, testing and commissioning of S.T. poles 9.0 Meter long swaged Type conforming to ST 410 SP-33, IS: 2713 amended up-to date well finished and coated with black bituminous paint upto plant depth and Red-Oxide coated above ground level with earthing arrangement through bolt welded on pole of 14 mm diameter, provided at height of 300mm above the planting depth which should be 1.5 mtr (SP 33). Top plate 3mm thick fully welded & bottom plate 35cm*35cm, 5mm thick fully welded. 1. Substations - 2x5 = 10 no.2. HT network - 20 no. |
| 9 | Supply, laying, installation, testing and commissioning of 630 mm² single core un-armoured Cable (3 Ckt),1.1kV Grade, XLPE Insulated Stranded Conductor FRLS type including lugs/thimbles/Clamps |
| 10 | Supply, installation, testing and commissioning of 11KV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 11 | Supply, installation, testing and commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 12 | Supply,installation, testing and commissioning of 1600 Amp 4P ACB Drawal type, Breaking Capacity 50kA with enclosure panel and stand complete |
| 13 | Supply,installation, testing and commissioning of Distribution feeder Pillar suitable for outdoor installation, made out of CRCA sheet painted through 7-tank process with PU painted Main Busbars 4P Tinned Copper (100x14 mm) with 3 no. MCCB 630 Amp adjustable type 4P 36 KA with heat shrinkable sleeves and adequate capacities complete with all accessories (as per enclosed drawing). |
| 14 | Supply, laying, testing and commissioning of 50 mm² ACSR Conductor |
| 15 | Supply, laying, testing and commissioning of 100 mm² ACSR Conductor |
| 16 | Supply & Fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2 Nos.), anchor plate (200x 200 x 6)mm, nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
| 17 | Supply and fixing of Anti Climbing devices (GI Barbed Wire (12 SWG) |
| 18 | Providing and laying of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm1. ST Poles - 2 No.x5 = 10 no.2. Distribution Feeder Pillar - 1 no. x 5 = 5 no.3. HT Network STpoles 20 |
| 19 | Providng and laying of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts, including baby insulators, refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 20 | Supply and fixing of Danger Plate With Clamps as per Standards wih writing in English & Urdu. |
| 21 | Supply and fixing of Wedge Connectors/PG Clamps |
| 22 | Supply and fixing of Galvanized Nuts and Bolts full thread of sizes as per IS |
| 23 | Providing and painting of poles with single coat of red oxide an two coats of Aluminum Paint |
| 24 | Design, Supply, installation, testing & commissioning of 415 V, 3 Phase, 1000 KVA Servo Stabilizer oil Cooled (including Oil- 2400 Ltrs), Output Voltage Accuracy ± 1%, HV cut-off set. LV cut-off set. O/L trip set.Time delay set Operating mode (auto/manual), Response time of 10 ms, Input Voltage Range from P-P: 240-485 V P-N: 138-280 V including interconnection with system by way of providing thimbles/clamps etc. |
| 25 | Providing of material and fixing of Chainlink Fencing of Substation by way of Mass Concrete in Foundations and chainlink fencing of 6 ft height including door with proper handle and lock arrangement. |
| 26 | Construction of Cement concrete bed 6x4x6 ft, 5ft above ground and 1 ft below in the ratio mix of mix 1:1.5:3 (1 cement :1½ coarse sand: 3 graded stone aggregate 20 mm nominal size) including excavation, curing but excluding the cost of centring and shuttering (for Servo Stabilizers - 5 no.) |
| 27 | Providing of materia & Laying of Centering and shuttering including strutting, propping etc. |
| 28 | Providing of material and fixing of Cover Shed with angle frame (steel structure) and fibre roof for Servo-Stabilizer including wire mesh fencing around the equipment made out of wire mesh 1\"x1\"square including fixing in cement 1:2:4 including welding cutting etc. Complete in all respect |
| 29 | Providing of material and laying of Cement grouting for support angle legs of Distribution Feeder Pillar |
| 30 | Providing of material and laying of Cement bottoming of poles (1:2:4 Mix as per REC Standards 0.48 M3 per Pole) |
| 31 | Part B- Laying of Three and a Half Core (Three Phase Four Wire) LT underground cable up-to Charging points for e-Buses at Bemina |
| 32 | Supply, Laying, installation, Testing & Commissioning 400 mm² 3½ Core Cable,1.1kV Grade, Armoured, XLPE Insulated Stranded Conductor FRLS including Copper thimbles/lugs for termination |
| 33 | Supply and Fixing of Straight Through Jointing Kit for 400 mm² 3½ Core Cable |
| 34 | Supply and Fixing of 1.1 kV Heat Shrinkable Cable termination with Copper lugs/thimbles/clamps for 185mm² 3½ Core Cable |
| 35 | Providing and laying of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip (25x3) mm |
| 36 | Excavation in any type of soil including hard laterite soilDetails: 5 no. Trench excavations (65.62\" x 4\" x 3\") x 5 no. = 3937.2 cft = 111.49 cum |
| 37 | Supplying and stacking at site Graded crushed stone aggregate of size 90 mm to 45 mm and Laying, spreading and compacting stone aggregate of specified sizes to WBM specifications in uniform thickness, hand picking, applying and brooming requisite type of screening /binding material to fill up interstices of coarse aggregate, watering and compacting to the required density.(65.62\"x 4\"x 0.25\")x 5 no.= 328.1 cft = 9.29 cum |
| 38 | Providing and laying in position cement concrete of specified grade 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size including curing but excluding the cost of centring and shuttering. Details:1. U/G = (65.62\"x 4\"x 0.25\")x 5 no.= 328.1 cft = 9.29 Cum2. Trench Walls - ((65.62\" x 0.5\" x 2.5\") x 2 )x 5 no.= 820.25 Cft = 23.22 CumTotal = 32.51 Cum |
| 39 | Centering and shuttering including strutting, propping etc. and removal of form work for transformer foundation((2.5\" x 65.62\") x 2) x 5 no. = 1640.5 Sft = 152.36 Sqm |
| 40 | 12 mm cement plaster of mix 1:4 (1 cement : 4 fine sand){(65.62\"x 0.5\")x 2} + {(2.5\" x65.62\")x 2} x 5 no.= 1968.6 sft = 182.89 Sqm |
| 41 | Supply and Erection of GI Angle 50x50x5 mm for Cable Trench/FrameDetails:3.5 ft long pieces after every 4 ft =19 piece x 5 no.1.158 Kg/ft x 19 piece x 5 no. = 110.01 Kg |
| 42 | Providing and laying of Chequered Plate, 2500x1220 mm, 5 mm thick (39.25 Kg/m2) Details:20 Mtr x 5 no. (100 mtr) = 40 no. Platesweight calculation = 39.25 x (40 x 3.05) = 4788.5 kg Please Enable Macros to View BoQ information |