| 1 | COPPER WIRING IN MS CONDUIT (SURFACE/RECESS) Wiring for Light/Fan/call bell point in 1.5 sqmm FRLS PVC insulated copper conductor cable in 1.6 mm thick MS conduit pipe. Group B |
| 2 | Wiring for Twin control light point with 2 nos , 2-ways, 5 amp. switch in 1.5 sqmm FRLS PVC insulated copper conductor cable in 1.6 mm thick MS conduit pipe. Group B |
| 3 | Wiring in MS conduit system for 3-pin 5amp. Plug point by using 2 no 1.5 sqmm FRLS copper wire and 1 no 1.5 Sqmm FRLS copper wire , including providing 1 no 5/6 Amp 3/5 pin socket and 1 no 5/6 Amp switch required MS Box etc complete as required Group B |
| 4 | Wiring in MS conduit system for 3-pin 15amp. Plug point by using 2 no 4 sqmm FRLS copper wire and 1 no 4 Sqmm FRLS copper wire for earthling , including providing 1 no 15/16 Amp 3/6 pin socket and 1 no 15/16 Amp switch required MS Box etc complete as required Group B |
| 5 | Wiring main ,sub mains and Circuit wiring in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in MS Conduit etc as required.1 run of Size 1.50 Sqmm(1/1.40mm) |
| 6 | 1 run of Size 4 Sqmm(1/2.24mm) |
| 7 | Supply and erection of MS conduit pipe 1.6 mm thick , ISI marked surface/recessed in slab/wall/ceiling etc. including cost of MS bends, inspection box and all other material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. MS pipe of 25 mm dia. |
| 8 | Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 25 mm dia. |
| 9 | PVC pipe of 32 mm dia. |
| 10 | FITTING AND ACCESSORIES Providing and fixing Piano type accessories of approved make in existing box and Bakelite sheet including fixing and making necessary connections, complete in all respect.Switch 5 amp. on existing sheet. |
| 11 | Wall socket 5 amp on existing sheet. |
| 12 | 15 amp. switch on existing sheet. |
| 13 | 6 pin 15 multi socket on existing sheet |
| 14 | Call bell 220/230 volts musical type |
| 15 | Bakelite angle/straight button holder large size. |
| 16 | Socket size rotary step type Electronic regulator for A.C. ceiling fan |
| 17 | Supply and erection of suitable MS/GI Box covered with 3 mm thick Bakelite sheet as below 200 mm X 150 mm X 60 mm deep metal box |
| 18 | Supply and erection of 10.5 cm dia M.S.Fan box including 8 mm dia 30 cm long M.S. Road made into suitable suspension hook and erected in R.C.C. slab for the erection of fan complete with all labour and material required to complete the job. |
| 19 | Erection of exhaust fan in existing opening, complete with necessary earthling of fan including carriage from PWD store to the site of work. |
| 20 | Making suitable hole in the wall suitable for exhaust fan up to 450 mm sweep including finishing the same and fixing of Stainless stell wire mesh 2 mm thick having about 50 meshes per inch at exhaust side complete as required |
| 21 | Providing and fixing outdoor duty Ply of 8 mm thick frame suitable for exhaust fan up to 450 mm sweep etc complete as required |
| 22 | Fixing of LED Tube light/ 2*2 ft square panel fitting directly on wall /ceiling or false ceiling including making connections etc as required. |
| 23 | MCCB ,DISTRIBUTION BOARDS, MCB\"s, RCCB\"s, CHANGE OVER etc. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. Triple pole MCCB 16 to 100 Amp, 25 KA |
| 24 | 4 pole MCCB 200 to 250 amp, 25 KA |
| 25 | Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to to the entire satisfaction of the Engineer-in-Charge of the work. SPN DB Double Door 12 way ( 2 incoming and 10 outgoing) |
| 26 | TPN DB Horizontal type Double Door 4 way ( 8 incoming and 3phase*4 outgoing) |
| 27 | TPN DB Horizontal type Double Door 8 way ( 8 incoming 3phase*8 outgoing) |
| 28 | Supply and erection of miniature circuit Breaker/isolator 240/415 V in the existing distribution board including making necessary connections:-6 amp. to 32 amp Single Pole |
| 29 | 6 amp. to 32 amp Double Pole |
| 30 | 40 amp to 63 amp. MCB\"s Four Pole |
| 31 | Supply and erection of blanking sheet in existing distribution board. |
| 32 | Supply of GI pipe (B-Class) for suspension rod of ceiling fan including threading if required. 15 mm dia |
| 33 | Supply and erection of M.S. angle iron frame duly welded for housing M.S. sheet & main switches etc. on it, fixed on wall by means of suitable size of rag bolts with cement concrete, duly painted with three coats of approved paint including one coat of red oxide. |
| 34 | Supply, installation, testing and commissioning of load bank with digital meter module cost of digital Amp./ volt meter with selector switch wiring (but excluding cost of incoming and outgoing MCCB’s) etc. suitable for operation of 240/415 volts A.C. Supply with both side cable allay, inter connection and fixing the same in existing MS pedestal/ wall complete with all labour and material required for the same up to the entire satisfaction of Engineer-in charge of work. Load Bank 8 way 250 A |
| 35 | Supply and erection of MS cable tray , duly pained as required including erection of the same on wall or ceiling with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work.MS perforated cable tray painted with powder coating 375 X 50 X 2 mm3 |
| 36 | Supply and erection of Medium Voltage caution notice plate of size 200*150 mm in three languages. |
| 37 | Supply and erection of cable tray cover made of 1.25 mm thick GI sheet as required including erection of the same on existing cable tray with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in charge of the work. GI cable tray cover suitable for cable tray of 375*50*2 mm |
| 38 | Earthing with G.I. earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required. |
| 39 | Extra for using salt and char coal/coke for pipe earth electrode as required. |
| 40 | Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material. |
| 41 | Supply and erection of suitable compression type brass cable glands for underground Cable :- 25 sqmm to 50 sqmm Cable 2 to 4 Core |
| 42 | S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Mtr below ground level including diging and refilling of earth including cost of suitable size socket/cuppler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 120/105 mm outer dia/ inner dia |
| 43 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%, THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted..other specifications as per DNIT in PDF. 100 watt |
| 44 | Erection of ceiling fan complete with necessary earthing of fan and regulator including carriage from local railway station /goods transport /PWD store to the site of work. |
| 45 | Designing, fabricating, transporting, unloading, storing, fixing in position, testing and commissioning the following sheet steel cubicle type panels fabricated from 1.6mm thick CRCA sheet, dead-front construction, dust and vermin proof, indoor type TPN Panels with hinged lockable doors fabricated from 2mm thick CRCA sheet, suitable for 415V, 3 phase 4 wire 50Hz AC supply with separate cable alley and lockable bus-bar chamber including supplying and fixing following switchgears and accessories, inter-connections, bonding to earth, powder coated painting as per following specifications :- Incomer 630 Amps TPN (3 pole + external neutral link) MCCB 36KA with OC, S/C, Protection Thermal Magnetic release with speader linkRotary Operating Handle, (Make: ABB /Siemens/ Schneider/ L&T)= 1 no. Phase indicating lamp LED type Red - 240V AC Make L&T/ESSBEE/FTC = 1 no.other specifications as per DNIT in PDF. Please Enable Macros to View BoQ information |