| 1 | M&L for servicing of AMF /DG elect control panel including replacement of existing unserviceable power contractors, MCCB\"s and making incoming, outgoing elect connections, replacement of burnt wires, thimbles, lugs, nut bolts & washer etc complete all as per specified and directed with following items:-Note:-All miner spare parts shall demad to be included in the quoted unit rate.Contactor 4 pole160 A, MCX 32 with 2NO+ 2NC ,auxiliary contact. |
| 2 | Ditto all as per item No 01 here-in-before but for contactor 4 pole325 A, MCX 41 with 2NO+ 2NC ,auxiliary contact. |
| 3 | Ditto all as per item No 01 here-in-before but for contactor 4 pole255 A, MCX 34 withadd on block |
| 4 | Ditto all as per item No 01 here-in-before but for contactor 4 pole63 A, MCX 12 complete |
| 5 | Ditto all as per item No 01 here-in-before buut for contactorMNX 32 complete |
| 6 | Ditto all as per item No 01 here-in-before but for contactor 4 pole130 A, MCX 23 complete all as specified and directed. |
| 7 | Ditto all as per item No 01 here-in-before but for contactor 4 pole125 A, ML6 complete all as specified and directed. |
| 8 | Ditto all as per item No 01 here-in-before but for contactor 4 pole100 A, ML4 complete all as specified and directed. |
| 9 | Ditto all as per item No 01 here-in-before but for contactor MNX 18 complete all as specified and directed. |
| 10 | Ditto all as per item No 01 here-in-before but for contactor MX0 40E complete all as specified and directed. |
| 11 | Ditto all as per item No 01 here-in-before but for Side Mounting Add-on aux. Contact Block left/right side, 1 NO + 1 NC suitable for contactor MCX 32-47 complete all as specified and directed. |
| 12 | Ditto all as per item No 01 here-in-before but for Mechanical interlock Kit For Contactor MCX 32 to 41 complete all as specified and directed. |
| 13 | Ditto all as per item No 01 here-in-before but for MO / MO C Spreader Link Kit 200 to 300 Amp complete all as specified and directed. |
| 14 | Ditto all as per item No 01 here-in-before but for MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA |
| 15 | Ditto all as per item No 01 here-in-before but for MCCB 3 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA |
| 16 | Ditto all as per item No 01 here-in-before but for MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA |
| 17 | Ditto all as per item No 01 here-in-before but for MCCB 4 Pole, 415 V, Adjustable type, 125 Amps with breaking capacity16 KA |
| 18 | Ditto all as per item No 01 here-in-before but for MCCB 4 Pole, 415 V, Adjustable type, 63 Amps with breaking capacity16 KA |
| 19 | Ditto all as per item No 01 here-in-before but for MCCB 4 Pole, 415 V, Adjustable type, 100 Amps with breaking capacity16 KA |
| 20 | Supply and fxing MPU (Magnetic Pickup unit / Magnetic Sensor unit)for DG set of capacity up to 250 KVA complete all as specified and directed. |
| 21 | M&L for replacement of Engine oil as per existing grade of DG sets ( 5 to 250 KVA)including draining out the old existing used engine oilcomplete all as specified & directed. |
| 22 | M&L for replacement / top upcoolant premixture DFC-50 in radiator of DG sets 05 to 250 KVA DG sets complete all as specified& directed. |
| 23 | M& L for cleaning, scraping, removing out old rusty paint from Engine & Alternator outer body of DG set 15 KVA to 250 KVA capacity by wire brush, emery paper, cleaning agents & Spray painting two coat of super enamelled paint as per existing colour coding complete as specified and directed. |
| 24 | M&L for hot air blower 1000 / 2000 Watts adjustable compact design suitable for working on single phase 220V, 50 Hz Ac supply complete all as specified & directed.Make- Bajaj / Orient / Havells. |
| 25 | Shifting of DG set (capacity up to 100 KVA) from existing platform to a new location including disconnecting electrically and mechanically, carefully removing the set, transporting and re-installing it on a new platform, reconnecting electrically and mechanically, testing and commissioning complete, all as specified and directed.The work shall also include construction of PCC foundation (1:2:4) type B-1 using 20mm graded stone aggregate for the DG set, with foundation height not less than 300 mm above ground level. The length and breadth of the foundation shall each be at least 500 mm larger than the corresponding dimensions of the DG set enclosure..Note:-(a) The unit rates quoted is deemed to be included for hydra, men power and other items required for energization of DG Set. |
| 26 | S&F in replacement of DG set display KG934 VI, digital controller as per existing make / mode for 30 KVA to 250 KVA Dg sets complete all as specified and directed. |
| 27 | S&F in replacement of Deep Sea 4520 Genset Controller (DSE4520 MK II), 230V AC, digital controller as per existing make / mode for 30 KVA to 250 KVA Dg sets complete all as specified and directed. |
| 28 | S&F in replacement of DG Start Stop Relay Card, voltage range 12/24 volt as per existing make / mode for 30 KVA to 250 KVA Dg sets complete all as specified and directed. |
| 29 | Supply and Fixing in replacement of Speed control unit model No ESD5111 with following features:- (a) The ESD5111 Speed Control Unit is an all electronic device designed to control engine seed with fast and precise response to transient load changes. (b) The engine STARTING FUEL and SPEED RAMPING adjustment. (c) All proportional actuators except the ACB2000 electric actuator. (d) Electric actuator, the DROOP adjustment range will be less due to this actuator’s low current demand (e) Engine Governor Controller for Diesel Generator Simplicity of installation and adjustment was foremost in the design. Non-interacting performance controls allow near optimum response to be easily obtained. (f) The primary features is engine STARTING FUEL and SPEED RAMPING adjustment. The use of these features will minimize engine exhaust smoke experienced prior to attaining engine operating speed complete all as specified and directed. |
| 30 | Supply, laying, jointing and testing in trenches or passing through pipe, 1100 Volts grade XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cable conforming to IS:7098 (Pt-I)-1988, heavy duty with aluminium conductor of cross sectional area 70 Sqmm 3.5 core with necessary fixing arrangements such as lungs, glands and terminal etc. complete all as specified as directed. |
| 31 | Excavation in trenches not exc. 1.5 m wide and not exc 1.5 m deep in soft/loose soil) for laying of cables or GI pipe and getting out including levelling of bottom suface to required level complete all as specified and directed. |
| 32 | Returning filling in, including spreading, levelling, watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed. |
| 33 | Removing excavated material (ie soil) from site to a distance n. exc 50 m away and depositing where directed at a level n. exc. 1.5 m above the starting point complete. |
| 34 | Supply and laying Sand coarse dry as in cushioning of under ground electric cable in trenches, laid to a uniform thickness of 23 cm (15 cm under the cable & 8 cm over the cable) and gently punned down to 18 cm thickness all complete as specified and as directed. |
| 35 | Supply & lay in replacement unreinforced precast concrete cable cover class LV, Type 1, flat size 250 mm x 150 mm x 40 mm as a cable protection on LT underground cables complete all as specified and directed. |
| 36 | S&F in replacement Generator Battery Charger 12 V& 24V10 amps Fully Automatic Battery Charger 7AH to 220 AH per exiting make or model complete all as specified and directed. |
| 37 | S & F in Replacement for Generator Canopy Door Locks, hinges complete as per existing make and model complete all as specified and directed. |
| 38 | Supply and Fixing in replacement Fuel Injector assembly of any make and any type of DG sets of capacity 30 KVA to 250 KVA complete all as specified and directed. |
| 39 | S & F Automotive or Commercial Multi Battery Charger 6-24 volt, main 230 volt, charging current 12 volt DC complete all as specified and directed. |
| 40 | S & F In repair Oil seal for any make & model ofDG set of capacity 30 KVA to 250 KVA DG complete all as specified and directed. |
| 41 | S & F In repair Exh. Manifold for any make & model ofDG set of capacity 30 KVA to 250 KVA DG complete all as specified and directed. |
| 42 | Supply, installing, testing and commissioning of outdoor type double door AMF panel , plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminum bus bars four pole installed on porcelain/SMC insulator. The panel shall be dust and vermin proof IP-54 class protection and outer shell made of of 3.15 mm MS sheet, inner shell made of 1.6 mm thick CRCA MS sheet , 50mm x 50mm x 6mm thick MS angle iron frame work, the cubical have bottom channel of size 75mmx40mm duly powder coated , front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated multi-strained, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size ( but not less than 2.5 Sq.mm), The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer and comprising of the following :-160 KVA AMF Panel :-(a) Incoming :-(i) MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 25 KA, with thermal magnetic release - 02 Nos.(ii) 250A Contactor 4P - 02 Nos.(ii) Digital VAF+PF meter -01No(iii) CT’s ratio 250/5 -01 set.(iv) Indicating lamp- 01 set of three(v) Four Pole , Aluminum bus bar 300 Amps insulated with color coded heat shrinkable sleeve and shall be mounted on suitable DMC insulators.(vi) Battery Charger 12 Volt – 01 No.(vii) PLA Relays 12V – 01 No.(viii) PLA Relay 240V – 01 No.(ix) VMR Relay – 01 No.(x) Control 6A SP MCB – 06 Nos.(xi) 16A DP MCB – 01 No.(xii) On Delay timer – 02 Nos..b) Outgoing:-(i) 250 A, 4 pole, ON LOAD Change Over Switch - 02 Nos. |