| 1 | Supply & installation of LT panel |
| 2 | MCC Panel 01 & Other details as per technical specifications and SLD (for DYKE-4, UG tank & Boiler house). |
| 3 | Supply |
| 4 | Installation |
| 5 | PCC Panel 01 & Other details as per technical specifications and SLD ( for Zone-7, TRAP). |
| 6 | Supply |
| 7 | Installation |
| 8 | MCC Panel 02 & Other details as per technical specifications and SLD (for Removable Extension panel,TRAP). |
| 9 | Supply |
| 10 | Installation |
| 11 | Modification & Upgradation of Star delta and DOL starters |
| 12 | Supply & Installation of Double door Pushbutton station outdoor type |
| 13 | Laying & installation of Power cable 1.1 kV grade, single strend copper conductor, XLPE insulated, ex-truded FRLS PVC inner sheathed, GI wire armoured, extruded FRLS PVC ST2 outer sheathed, conforming to IS: 7098 (Part-I), 1988 . |
| 14 | 10C X 1.5Sq.mm, 2XWY Cable. |
| 15 | 4C x 6sq. mm, 2XWY cable. |
| 16 | 4C x 25mm2, 2XWY cable. |
| 17 | 3.5C x 400mm2, 2XWY cable. |
| 18 | Excavation in all types of soil shall be carried out manually, with the use of JCBs or any other machinery prohibited. However, for breaking PCC and road surfaces, a drilling hammer may be used. The excavation will have a width of 500 mm and a depth of up to 1000 mm below ground level, to accommodate LT cable laying with sand bedding, and the placement of baked bricks on the sides and top. The process includes backfilling, dewatering, consolidation, shoring, and disposal of excess earth. The scope of work also includes the supply of river sand and Class-1 bricks. |
| 19 | 300mm RCC hume pipe NP2 class( light duty ) including road cutting of suitable width and depth 1000 mm complete with RCC collars, jointing with cement mortar 1:2( 1 cement: 2 fine sand ), 100mm thick encasing the pipe with concrete of 1:2:4 grade, backfilling and concreting (1:2:4 ) with M30 grade. |
| 20 | Supply ofRCC hume pipe |
| 21 | Installation of RCC hume pipe |
| 22 | Providing and laying in position Reinforced Cement concrete (RCC) of Grade M-30 using 20mm maximum size aggregates and river sand of approved quality. |
| 23 | 300mm RCC hume pipe NP2 class( light duty ) including road cutting of suitable width and depth 1000 mm complete with RCC collars, jointing with cement mortar 1:2( 1 cement: 2 fine sand ), 100mm thick encasing the pipe with concrete of 1:2:4 grade, backfilling and concreting (1:2:4 ) with M30 grade. |
| 24 | 10C X 1.5Sq.mm, 2XWY Cable |
| 25 | 4C x 6 sq. mm, 2XWY cables. |
| 26 | 4C x 25mm2,2XWY cables. |
| 27 | 3.5C x 400mm2,2XWY cables. |
| 28 | Installation of 300 mm perforated Cable tray with all accessories such as Tee, vertical & horizontal bends, reducer’s crossings etc. |
| 29 | Installation of earthing materials along with all accessories. |
| 30 | 25 x 3 mm Cu earthing strip |
| 31 | (12 SWG), Cu. earth wire |
| 32 | Fabrication of Plate earth pits using 600mm X 600mm X 3.15mm Tinned copper earth plate, with 2 X 25mm X 3mm copper earth strip raiser, with Class B GI watering pipe with funnel & mesh, 600mm X 600mm CI Cover, brick masonry, salt, charcoal etc. excluding excavation but including back filling.Note: Supply of all materials in the scope of Supplier |
| 33 | Fabrication of Rod earth pits using 25mm Φ, 3000mm long Tinned copper rod, with copper bracket for connecting the rod with 2 X 25mm X 3mm copper earth strip, with Class B GI watering pipe with funnel & mesh, 600mm X 600mm CI Cover, brick masonry, salt charcoal etc. excluding excavation but including back filling. Note: Supply of all materials in the scope of Supplier |
| 34 | Supply & installation of Cu Earth pit test links. |
| 35 | Supply, Fabrication & installation of Concrete anchor fastener- M12 Effective anchorage depth : 100mm, HSA stud anchor. |
| 36 | Supply, Fabrication & installation of ISA 50 x 50 x 6 MS angle |
| 37 | Supply of Voltage scanner |
| 38 | Supply of Overload relay, Aux. Suply: 380-440V AC |
| 39 | 12way MCB Distribution Board Suitable for Outdoor use Waterproof PVC Enclosure |
| 40 | Supply |
| 41 | installation |
| 42 | 18way MCB Box with Enclosure and Open-Type Cover for Outdoor Power Distribution |
| 43 | Supply |
| 44 | installation |
| 45 | Switchgear for EOT crane |
| 46 | Supply and Installation of Radio Remote Control,(12 Pushbutton Double speed) |
| 47 | Supply and Installation of Selenium type bridge rectifier panel suitable for Size of the brake: 200mm/1X8\" and input voltage: 415v |
| 48 | Supply and Installation of Rotory Gear Limit Switch, Type: FG-100P2 and input voltage: 415V |
| 49 | Supply and Installation of Cross bar limit switch, Volts:240v, current:3A |
| 50 | Supply of SMPS unit, Input voltage: 415V, Output Voltage: 24V & 30V, Current: 10A |
| 51 | Supply of DSL indicating lamp, input power:415 Volts AC, 50Hz, 4 Watts |
| 52 | Miscellaneous Items |
| 53 | Supply and installation of Miniature Circuit Breaker |
| 54 | 63A MCB, 2P, D-Curve |
| 55 | 40A MCB, 2P, D-Curve |
| 56 | 32A MCB, 2P, D-Curve |
| 57 | Supply and installation of MPCB with 1 NO + 1 NC |
| 58 | 3.2 - 5A MPCB |
| 59 | 5.5 - 8A MPCB |
| 60 | 9 - 12.5A MPCB |