| 1 | PART-(A) |
| 2 | HIGH MAST SHAFT Supply & fixing of 30 mtr High mast shaft of approved make with rising system hot dip glavanized inside & out side dip,heaving pole sheet thickness 4 mm. Top dia minium 150 mm, Bottom dia 500 mm base plate 32 mm thick suitable for wind v |
| 3 | FLOOD LIGHT LUMINAIRES Supply and fixing of factory wired integral LED flood light luminaires with die cast aluminium housing built with dirver set suitable for 170 to 200 Watt. Confirming to IP 66 protection complete in all respect., CAT- AAA |
| 4 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc., 70 sq. mm 3-1/2 core |
| 5 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc., 35 sq. mm 3-1/2 core |
| 6 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc., 25 sq. mm 3-1/2 core |
| 7 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc., 16 sq. mm 4 core |
| 8 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge., 16 sq. mm 4 core |
| 9 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge., 25 sq. mm 3-1/2 core |
| 10 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge., 35 sq. mm 3-1/2 core |
| 11 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge., 70 sq. mm 3-1/2 core |
| 12 | Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge., 16 sq. mm |
| 13 | Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge., 25 sq. mm |
| 14 | Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge., 35 sq. mm |
| 15 | Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge., 70 sq. mm |
| 16 | Cubical Panel Board ( MCCB Type) Supply & Erracetion of factory fabricated & wired metal clad dust and vermin proof floor mounting, M.S. Channel Base with bottom and top cable entreis Electrical control panel with TPN MCCB\"s (Four Pole 36 KA with thermal magnatic release)Switches Complete and instrument chamber etc.complete in all respects. The instrument chamber shall be separate and shall comprise of flush type digital metering system for phase to phase voltage and single phase voltage, current and other parameters(KVA,P.F,KW etc) in each phase with touch type selector switches for different readings, instrument fuses, current transformer etc. The panel board shall have suitable capacity electrolytic alumininum busbars as per IS8623 or above istulated with heat shrink sleeving and mounted on non hygroscopic supports such as CMC/BMC support with deteachable side covers and shall be suitable for extension on the sides. The MCCB\"s shall be complete with suitable cable end boxes, compression glands and indicating lamp on incoming etc. The Job includes the grounting of the board as per directions of Engineer-in charge. All out goings of 100 Amp and above shall have an Ammeter. The panel board shall be fabricated with CRCA sheet with a minimum thickness of 1.6mm/2mm. Cubicle type switch board shall be of cat A & B Only. (Incoming - 200 Amp MCCB -1 No), Outgoing -100 Amp. MCCB-1 No & 63 Amp. MCCB-3 Nos., Cat. B. Pannel Cubicle Type |
| 17 | Supply and fixing following capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect., 25 A TPN |
| 18 | S/B of earth rod 20 mm dia 2.5 mt long including GI wire 7/16 SWG to connected earth rod and earth clamp on pole,3 mt long steel conduit to carry earth wire along the pole complite as per approved of E/Ic. |
| 19 | \"Supply, Installation, testing & commissioning of Servo Stabilizer with Isolation transformer 65KVA, 3-phase servo voltage stabilizer with isolation transformer , oil cooled, Input 300-470 VAC, 4 Wire, 50 Hz, output: 400+/-1% with oil, suitable for UNBALANCED LOAD with automatic operation (outdoor type-IP 64). The stabilizer shall comply with the following requirement: : Regulation : +/- 10 %. : Over load & Short circuit protection. : Protection cut-off against Over/Under Voltage. : Single phase protection. : 3 nos. phase indication lamps. |
| 20 | Providing, hoisting and fixing above plinth level up to floor five level precast reinforced cement concrete work in string courses, bands, copings, bed plates, anchor blocks, plain window sills and the like, including the cost of required centering, shuttering but, excluding cost of reinforcement, with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 21 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:, Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 22 | ENCAPSULATED PIPE - IN- PIPE EARTHING Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 2000mm, outer pipe 50mm, inner pipe 25, terminal Dia 12 mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25 x 3 G.I . strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. |
| 23 | PART-(B) |
| 24 | Operation of 1st Year @ 2.5 % of total estimated cost (7091209.00) |
| 25 | Operation and maintenance of 2nd Year @ 5 % of total estimated cost (7091209.00) |
| 26 | Operation and maintenance of 3rd Year @ 7.5 % of total estimated cost (7091209.00) |
| 27 | Operation and maintenance of 4th Year @ 7.5 % of total estimated cost (7091209.00) |
| 28 | Operation and maintenance of 5th Year @ 7.5 % of total estimated cost (7091209.00) Please Enable Macros to View BoQ information |