| Sl. No. | Item Description |
| 1 | Note: Please refer Schedule \"A\" Notes given on serial page No. 19 to 24 of tender documents. |
| 2 | LUMPSUM/ OTHER PRE-PRICED PROVISIONAL SCHEDULES OF WORKS |
| 3 | Lump sum price worked out by the contractor for BUILDING WORKS as listed in Schedule \"A\" Part-I brought forward from serial page No. 25. |
| 4 | Lump sum price worked out by the contractor forSITE CLERANCE AND EARTHWORKS as listed in Schedule \"A\" Part-II brought forward from serial page No. 26. |
| 5 | Lump sum price worked out by the contractor for INTERNAL WATER SUPPLY WORKS Schedule \"A\" Part-III brought forward from serial page No. 27. |
| 6 | Lump sum price worked out by the contractor for INTERNAL ELECTRIFICATION WORKS Schedule \"A\" Part-IV brought forward from serial page No. 28. |
| 7 | Lump sum price worked out by the contractor for SEWAGE DISPOSAL WORKS as listed in Schedule \"A\" Part-V brought forward from serial page No. 30. |
| 8 | Lump sum price worked out by the contractor for ROAD/ PATH/ CULVERT WORKS as listed in Schedule \"A\" Part-VI brought forward from serial page No. 32. |
| 9 | Lump sum price worked out by the contractor for AREA DRAINAGE WORKS as listed in Schedule \"A\" Part-VII brought forward from serial page No. 33. |
| 10 | Lump sum price worked out by the contractor for EXTERNAL ELECTRIFICATIONWORKS as listed in Schedule \"A\" Part-VIII brought forward from serial page No. 34. |
| 11 | Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLYWORKS as listed in Schedule \"A\" Part-IX brought forward from serial page No. 38. |
| 12 | Lump sum price worked out by the contractor for BOUNDARY WALL / FENCING / GATE listed in Schedule \"A\" Part-X brought forward from serial page No. 39. |
| 13 | Lump sum price worked out by the contractor for WASTE WATER COLLECTIONTANK AND LECHATECOLLECTION PITS WORKS listed in Schedule \"A\" Part-XI brought forward from serial page No. 41. |
| 14 | Lump sum price worked out by the contractor for COMPOSIT PITS WITH COVER AND EXISTING COMPOSIT PITS listed in Schedule \"A\" Part-XII brought forward from serial page No. 42. |
| 15 | MISCELLANEOUS ITEMS OF WORKS -SCH\"A\" PART-XIII |
| 16 | INTERNAL ELECTRIFICATION WORKS |
| 17 | Supply & fixofLED Street Light Luminaire 25 watt 6000K with .high power LED cool white,CRI 75,+/- 5% supply voltage 220/240/50 Hz, light engine driver base.pole adapter,powder coated pressure die cast aluminium with heat resistant toughened glass with lens.complete all as specified and directed. |
| 18 | Supply and fixingof security lightmounting bracket made out of GI pipe 40 mm dia medium Grade not less than with 1.2 m.long in any shape with 2 nos ofpole fitting clamps made out of MS flat of size 40 x 6 mm and nutsand boltsand painting with aluminium paint,all as direced by Engr in Charge. |
| 19 | EXTERNAL ELECTRIFICATION WORKS |
| 20 | Supply Install, testing and commissioningof LT Distribution Panel (CPRI type tested ) cubicle type IP-65,outdoor type confirming to IS-61439, factory fabricated prewired made out of 3.15 mm thick CRCA sheet outer & 2 mm thick CRCA sheet inner of suitable size to accommodate all accessories / fittings compartmentalized in construction to accommodate the incoming/outgoing MCCB and TPN bus bars and outgoing feeders . The TPN bus bars shall be insulted with colour coated heat shrinkable sleeve and shall be mounted on DMC support. The incoming as well as outgoing MCCBs shall have extensionlinks of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC support having provision for termination of incoming and outgoing cables. All extension links/ interconnections shall be colour coated sleeves. The cubicle shall have frame work at bottom of MS channel MC 100 fixed to the top of plateform. The plateform of LT panel shall be pedestal type of suitable width and 600 mm height above ground level and minimum 400 mm below the ground level constructed with bricks (sub class\"B\") work duly plastered in CM 1:3 and PCC copping (1:2:4) not less than 50 mm thick over brick pedestal with adequate opening for entry of cable complete as per manufacture recommendation and directed by the Engr-in-charge. A detachable gland plate of thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size compression glands, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY Structure after seventank phosphate treatment front & back opening type and fixing 2 Nos danger notice plan with letter figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter and shall have louvers and air vent gasket for natural flow of air Neoprene adhesive type gasket shall be used to make panel vermin proof and comprising of following:-Note : (i ) LT panel board should be Type Tested from CPRI (A copy of valid CPRI type test report to be enclosed while obtaining approval from GE)(ii)SLD diagrame for LT panel will be got approved from GE before placing the order and final diagram will be fixed on the front and rear door.(iii)Rate for the same deemed to include in the quoted rates. (Main LT Panel) |
| 21 | Incomer : (a)MCCB 4 pole 415 Volt, 100 Amps, 35 KA, with fixed magnetic & thermal adjustable-01 Nos(b) Bus bars: 100A TPN +E busbars running throughout the length of panel.Outgoing feeders :(i) MCCB 4 pole 415 Volt 100 Amps,35 KA,with fixed magnetic & thermal adjustable -01 Nos(ii) Volt meter0 to 500 volts digital type with selectorswitch = 01 Nos (iii) Ampere meter 0 to 400 Amps digital type with selector switch = 01 Nos (iv) LED Phase indicator lamp = Set of three(v)All connections from MCCBs to bus bar & bus bar to MCCB shall be madewith suitable size of aluminium strip thimble lugs.(vi) Pre-wired with copper conductor cable single core strand PVC insulated with aluminium thimble lugs etc all as specified & directed. |
| 22 | Supply Install, testing and commissioningof Main LT Distribution Panel (CPRI type tested ) cubicle type IP-65,outdoor type confirming to IS-61439, factory fabricated prewired made out of 3.15 mm thick CRCA sheet outer & 2 mm thick CRCA sheet inner of suitable size to accommodate all accessories / fittings compartmentalized in construction to accommodate the incoming/outgoing MCCB and TPN bus bars and outgoing feeders . The TPN bus bars shall be insulted with colour coated heat shrinkable sleeve and shall be mounted on DMC support. The incoming as well as outgoing MCCBs shall have extensionlinks of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC support having provision for termination of incoming and outgoing cables. All extension links/ interconnections shall be colour coated sleeves. The cubicle shall have frame work at bottom of MS channel MC 100 fixed to the top of plateform. The plateform of LT panel shall be pedestal type of suitable width and 600 mm height above ground level and minimum 400 mm below the ground level constructed with bricks (sub class\"B\") work duly plastered in CM 1:3 and PCC copping (1:2:4) not less than 50 mm thick over brick pedestal with adequate opening for entry of cable complete as per manufacture recommendation and directed by the Engr-in-charge. A detachable gland plate of thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size compression glands, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY Structure after seventank phosphate treatment front & back opening type and fixing 2 Nos danger notice plan with letter figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter and shall have louvers and air vent gasket for natural flow of air Neoprene adhesive type gasket shall be used to make panel vermin proof and comprising of following:-Note : (i ) LT panel board should be Type Tested from CPRI (A copy of valid CPRI type test report to be enclosed while obtaining approval from GE)(ii)SLD diagrame for LT panel will be got approved from GE before placing the order and final diagram will be fixed on the front and rear door.(iii)Rate for the same deemed to include in the quoted rates.Incomer : (a) MCCB4 pole 415 volts,100amps,25 KA with fixed magnetic & thermal adjustable -01 Nos. |
| 23 | (b) Bus bars: 150A TPN +E busbars running throughout the length of panel.Outgoing feeders :(i) MCCB 4 pole 415 Volt 63 Amp16 KA with fixed magnetic & thermal adjustable-02Nos (For Feeder Piller For Wet Waste Shed -01 Nos and Feeder Piller For Dry Waste shed -01 Nos.(ii) MCCBTP,16 Amp , 10 KA -01 Nos (For Street Light)(iii) MCB SPN, 16 amp/10KA -04 Nos (For Hazarods Waste DB,Zero Fuel Incinerator,Office Building DB,Office Building Toilet DB)(iv) Contractor 32 Amp TPN,Capacity and MCB Outgoing 16 amp -02 Nos (For Street Light Feeders)(v)Digital Timer Switch with astronomical function for switchingON/OFF street lights 2 module-01 Nos(vi) Volt meter0 to 500 volts digital type with selectorswitch = 01 Nos(vii) Ampere meter 0 to 100 Amps digital type with selector switch = 01 Nos(viii) LED Phase indicator lamp = Set of three(ix) All connections from MCCBs to bus bar & bus bar to MCCB shall be madewith suitable size of aluminium strip thimble lugs. (x) Pre-wired with copper conductor cable single core strand PVC insulated with aluminium thimble lugs etc all as specified & directed. |
| 24 | Supply Install, testing and commissioningof Feeder Piller LT Distribution Panel (CPRI type tested ) For Wet Waste Shedcubicle type IP-r65,outdoor type confirming to IS-61439, factory fabricated ralprewired made out of 3.15 mm thick CRCA sheet outer &2 mm thick CRCA sheet inner of suitable size to accommodate all accessories / fittings compartmentalized inrlconstruction to accommodate the incoming/outgoing MCCB and TPN bus bars and outgoing feeders . The TPN bus bars shall be insulted with colour coated heat shrinkable sleeve and shall be mounted on DMC support. The incoming as well as outgoing MCCBs shall have extensionlinks of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC support having provision for termination of incoming and outgoing cables. All extension links/ interconnections shall be colour coated sleeves. The cubicle shall have frame work at bottom of MS channel MC 100 fixed to the top of plateform. The plateform of LT panel shall be pedestal type of suitable width and 600 mm height above ground level and minimum 400 mm below the ground level constructed with bricks (sub class\"B\") work duly plastered in CM 1:3 and PCC copping (1:2:4) not less than 50 mm thick over brick pedestal with adequate opening for entry of cable complete as per manufacture recommendation and directed by the Engr-in-charge. A detachable gland plate of thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size compression glands, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY Structure after seventank phosphate treatment front & back opening type and fixing 2 Nos danger notice plan with letter figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter and shall have louvers and air vent gasket for natural flow of air Neoprene adhesive type gasket shall be used to make panel vermin proof and comprising of following:-Note : (i ) LT panel board should be Type Tested from CPRI (A copy of valid CPRI type test report to be enclosed while obtaining approval from GE)(ii)SLD diagrame for LT panel will be got approved from GE before placing the order and final diagram will be fixed on the front and rear door.(iii)Rate for the same deemed to include in the quoted rates. |
| 25 | Incomer :(a) MCCB4 pole 415 volts,63 amps,16 KA with fixed magnetic & thermal adjustable -01 Nos.(b) Bus bars: 100A TPN +E busbars running throughout the length of panel.Outgoing feeders :(i) MCB TPN 10 Amp 10 KA -08Nos (For WetWaste of BIN MGB)(ii) MCB TP 16AMP,10KA-01 Nos (For Churner)(iii) MCB SPN, 16 amp/10KA -04 Nos (For Hazarods Waste DB,Zero Fuel Incinerator,Office Building DB,Office Building Toilet DB)(iv) MCB TP 20 AMP,10KA -01 Nos (For Shredder)(v) MCB SPN 10 AMP,10KA-02 nos.(For Screw Conveyor and Wet waste Shed DB)(vi) Volt meter0 to 500 volts digital type with selectorswitch = 01 Nos (vii) Ampere meter 0 to 100 Amps digital type with selector switch = 01 Nos (viii) LED Phase indicator lamp = Set of three(ix) All connections from MCCBs to bus bar & bus bar to MCCB shall be madewith suitable size of aluminium strip thimble lugs.(x) Pre-wired with copper conductor cable single core strand PVC insulated with aluminium thimble lugs etc all as specified & directed. |
| 26 | Supply Install, testing and commissioningof Feeder Piller LT Distribution Panel (CPRI type tested ) For Dry Waste Shedcubicle type IP-r65,outdoor type confirming to IS-61439, factory fabricated ralprewired made out of 3.15 mm thick CRCA sheet outer &2 mm thick CRCA sheet inner of suitable size to accommodate all accessories / fittings compartmentalized inrlconstruction to accommodate the incoming/outgoing MCCB and TPN bus bars and outgoing feeders . The TPN bus bars shall be insulted with colour coated heat shrinkable sleeve and shall be mounted on DMC support. The incoming as well as outgoing MCCBs shall have extensionlinks of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC support having provision for termination of incoming and outgoing cables. All extension links/ interconnections shall be colour coated sleeves. The cubicle shall have frame work at bottom of MS channel MC 100 fixed to the top of plateform. The plateform of LT panel shall be pedestal type of suitable width and 600 mm height above ground level and minimum 400 mm below the ground level constructed with bricks (sub class\"B\") work duly plastered in CM 1:3 and PCC copping (1:2:4) not less than 50 mm thick over brick pedestal with adequate opening for entry of cable complete as per manufacture recommendation and directed by the Engr-in-charge. A detachable gland plate of thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size compression glands, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY Structure after seventank phosphate treatment front & back opening type and fixing 2 Nos danger notice plan with letter figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter and shall have louvers and air vent gasket for natural flow of air Neoprene adhesive type gasket shall be used to make panel vermin proof and comprising of following:-Note : (i ) LT panel board should be Type Tested from CPRI (A copy of valid CPRI type test report to be enclosed while obtaining approval from GE)(ii)SLD diagrame for LT panel will be got approved from GE before placing the order and final diagram will be fixed on the front and rear door.(iii)Rate for the same deemed to include in the quoted rates. |
| 27 | Incomer :(a)MCCBTPN 63 Amp,10 KA, with fixed magnetic & thermal adjustable-01 Nos(b) Bus bars : 100 A TPN + Ebusbars running throughout the length of panelOutgoing feeders :(i) MCB ,TP 20 Amp/10 KA -01Nos (For Dry Remover Machine)(ii) MCB ,TP 25 Amp/10KA -01 Nos (For Plastic Waste Shredder)(iii) MCB SPN, 10 amp ,10 KA -02 Nos (For Flat conveyour,Dry waste Shed DB)(iv) Volt meter0 to 500 volts digital type with selectorswitch = 01 Nos(v)Ampere meter 0 to 100 Amps digital type with selector switch = 01 Nos (vi) LED Phase indicator lamp = Set of three(vii) All connections from MCCBs to bus bar & bus bar to MCCB shall be madewith suitable size of aluminium strip thimble lugs. |
| 28 | S & F junction box poly corbonatesize with glass fibre reinforced , environment friendly, recylable, UV resistant , halogen and silicon free anti acid and anti corrosive IP 66/67 in accordancewith IE rule internally embedded gasket, junction box including 3 phase 415 volt aluminium bus bar and one No. MCB SP 6A 10KA to control the street light including necessary clamps, nuts bolts to fix the junction box with poles all specified and directed. |
| 29 | Supply and fixing of three core PVC insulated cable with stranded copper conductor of size 1.5 Sqmm complete all as specified. |
| 30 | Supply & fixing GI pipe bracket of 1.5 mtr lomg made out of GI pipe light grade 32 mm dia and bend to shape with suitable cut at bend point & welded as per standard Engg. practice, two Nos MS clamps made out of MS flat iron of size 32X6 mmthick with nuts & bolts, washers complete and drilling of holes for nuts & bolts etc all as specified and directed. |
| 31 | Supply and fixing LED street Light45 Watt,230V AC outdoor type with high pressure die cast aluminium hosing with modular lens having efficifiencey of 110 lm/watt and heat resistant complete with driver ,lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 Protection complete all as specified and directed. |
| 32 | Supply,laying & fixing in replacement double wall corrugated (DWC) pipes made of high density polythyline (HDPE) with all accessories i.e. all type of joints, Sockets, Elbows, bends and End caps etc. allas specified and directed ofsize 63mm outer dia and 50 mm inner dia. |
| 33 | Supply,laying & fixing in replacement double wall corrugated (DWC) pipes made of high density polythyline (HDPE) with all accessories i.e. all type of joints, Sockets, Elbows, bends and End caps etc. allas specified and directed ofsize 80 mm outer dia and 63 mm inner dia. |
| 34 | M & L for drilling hole under the road, pavment, hardstanding by Mechanically or mannually by boringg with bockee for making suitable size of holes for passing LT cable of any size with provn of DWC HDPE pipe of suitable sizescomplete all as specified and directed. |
| 35 | DG SET WORKS |
| 36 | Supply, installation, commissioning and testing of eco-friendlyDiesel Engine driven generating set silent type confirming to CPCBIV+ condition/norms, 58.5 KVA (46.8 KW) rating as per BS-5514, 04 Cylinder /inline, 4 stoke cycle, Liquid cooled turbocharged, at 1500 RPM, 415 volts (AC 3 phase,4 wire system of supply) 50 Hz at 0.8 power factor directly coupled alternator & engine, water cooled, mounted on common base plate of rigid fabricated mild steel frame platform with floor mounted fuel tank of suitable capacity(minimum 12 hrs capacity of consumption) & including all excavation PCC foundation, anti-vibration pads/ dampers including standard control panel other accessories as per manufacturer\"s design. The Gen set should be fitted with integrated acoustic enclosure manufactured by the OEM of the Generating set .The Generating Set and acoustic enclosure shall confirm to emission norms and noise level. The acoustic enclosure shall be type tested and certificate obtained for the type approved from approved agencies listed in Govt Notification. Specifications of DG set shall be as specified and comprising of the following:-Make of OEM:- (i)M/s KOEL Green (ii)M/s Sudhir power Ltd (iii) M/s Greaves power (iv) M/s Jackson Ltd(A) ENGINE (Prime mover): Diesel engine vertical type of adequate capacity for 58.5 KVA (46.8 KW), 04 Cylinder/inline, 4 stoke cycle, Liquid cooled turbocharged, at 1500 RPMunder NTP conditions of BS : 5514, turbo charged liquid cooled, compression ratio 17.3:1, Nos ofbatteries as per OEM recommendation for electric battery start, complete with fly wheel and all standard fittings/fixtures as per manufacturer instructions including suitable engine control panel/dash Board with electronic tachometer. Lubrication oil temperature & pressure gauges water temp gauge and frequency meter (digital type) including safety automatic shutdown in case of fault such as high water temperature low oil pressure, over speed etc. including self-starter, alternator, cogged, V belt, fuel tank with first fill of lub oil and coolant(as applicable) etc. complete all as specified. Make of Engine :- (i) Kirloskar (ii) Cummins (iii) Greaves power |
| 37 | (B) ALTERNATOR: Alternator AC ,3 phase 415 volts 4 wire rated line current for output 58.5 KVA, PF 0.8 1500 RPM confirming to BS 5000 directly coupled with above engine.The Alternator shall be brushless type, screen protected, revolving field, self-exited, self-regulated through an AVR.The alternator has the following features :-(i) + 0.5% voltage regulation (max) in static conditions(ii) IP-23 protection with insulation class H(iii) Permissible overload of 10% for one hour in 12 hours of operation. (iv) Anti-vibration pads for mounting engine and alternator assembly on the base frame/plate or as recommended/provided by the manufacturer. (C) Base framemade out of structural steel as per manufacturer\"s recommended. design/specifications.(D) ACCOUSTIC ENCLOSUREProvision of an integral type approved/certified acoustic enclosure. It shall be made of 16 SWG or manufacturer\"s standard norms out of CRCA sheet with powder coated finish on outside and provided with non-igniting fire retardant foam as acoustic material of suitable thickness and perforated sheet of stainless steel as per manufacturer design. The doors and glass window shall be as per manufacturer\"s design. The base frame shall be of ISMC.It shall also include the following:- (i) Silencer: Suitable exhaustResidential grade silencer to reduce the noise level.(ii) Internal wiring with PVC copper cable (ISI 694marked) FRLS in conduit and for light and fan point lamp fittings including lamp.(iii) Fuel tank: Sub Base Fuel tank of 14 SWG MS sheet of capacity considered as per OEM duly powder coated.(iv) Nos of battery as per OEM recommendation maintenance free batteries.(E) The standard digital control Panel suitable to accommodate inside acoustic enclosure all as specified.(F) Base rail : Base rail with integral fuel tank is provided.Make of Alternator :- (i) Kirloskar Green (ii) Stamford (iii) Crompton Greaves |
| 38 | Control Panel : Manually operted Standard Alternator Control Panel fabricated out of sheet steel angle,iron structure,acid treated for anti-corrosion,Floor mounting,cubic pattern,powder coated dust and vermin proof,complete with internal wiring and with the followings.(i) Power Coated control panel manufactured with CRCA sheet provides(ii) Controller which display voltage,current KW,PF,Frequencey,KWH.(iii) MCCB of suitable rating with short circuit protection. (iv) Indicating lamps for \"Load On \" and \"set Running\".(v) Current Transformer of suitable ratings. (vi)Copper Cables of suitable capacity with incoming and outgoing terminations. (vii) Control fuses duly wired and ferruled. |
| 39 | Material and labour for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick, burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5m below normal ground level connected with galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete with 40mm dia GI light grade protection pipe, 20mm dia GI Medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15 type B1 in pit with angle iron (25x25x3)mm frame work with precast RCC 1:2:4 type B-1 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12mm dia MS fabricated handle, test point etc. in and including light grade GI protection pipe 40mm bore up to 5m length for drawing in earth lead wire, all as shown in electric plate No. 3 of SSR Part-I complete with necessary earth work in any type of soil, removal to a distance not exc. 50m, testing on completion complete all as specified & directed. |
| 40 | EXTERNAL WATER SUPPLY WORKS |
| 41 | M& L for taping from Existing GI40mm pipeincluding cutting, jointing and inserting Tee, and alll accessories on qouted rate. Note : Gate valve shall be measured and paid separately under respective items. |
| 42 | M & L valve pits and constructing of brick masonary pits of internal dimensions 600 mmx 600mmx 600mm(bottom PCC floor of the pit should be minimum 30 cms below the bottom surface of sluice valve flange to provide sufficient working space ), bottom floor of the pit be constructed in PCC (1:3:6) 51 cms thick with 20 mm stone aggregate , inner and exposed surfaces and bottom floor of the pit should be plastered in CM (1:4) 15 MM thick. The sluice valve and other fittings should be housed in center of the pit. The verticesof the pit should in right angle and champhered. The top cover of the pit will be made out of MS sheet min 2 mm thick with angle iron frame made out of MS angle 50 mm x50 mm x 6mm with galvanized steel hindges two nos and locking arrangements duly painted with two coats of water resistant synthetic enamelled paint over one coat of red oxide. |
| 43 | EQUIPMENTS |
| 44 | Supply and fixing of Composting Solution for Wet Waste of capacity 4 Sets / 8 nos of My Green Bin MGB 1000 with following specifications(i) Each MGB 1000 of size – L 6.70 m x 2.0 m x 1.40 m made out of FRP Panel Including Real time monitoring system for measurement of waste composted, CH4 & CO2 emissions with automated alerts & notifications and seamless integration with user friendly Dash Board. (ii)Smart composting with real time tracking,automated alerts,and remote access.(iii)Data analytics optimize processes,while a user -friendly dashboard ensures ease (iv) Scalable,modular and API-integrated for seamless expansion and connectivity (v) Low-maintenance design reduces manual effort,enhancing efficiencey and reliability (vi) FRP Panel of thickness 5 mm with the interior of the Composter finished withadditional FRP ribs of width 200 mm with 8 mm aerator holes are made inside and outside,top and bottom,joined together with FRP Lining and SS fasteners. (vii)The Bottom tank to be height 100 mm and coverd with FRP Plates of thickness 5 mm with 8 mm holes for the Leachate to be collected. The bottom tank is provided with 20 mm Ball Valve-02 Nos. (viii)The Central portion to have FRP channels with 7 nos of 75 mm aerator pipes with 8 mm holes supported between top and bottom FRP channels with end caps. (ix) The Bin have 8 doors of rectangular shapes fixed with a door Locking system.The doors are reinforced with a metal frame of 2 mm thickness.(x) The top of the Composter is Provided with 8 lids,all of FRP of thickness 3 mm with SS stay.The Composter to be engulfed outside with 50mmx 25 mm Painted MS Section at 2 levels (xi) the Composters will beprovidedwith 1 Blowers mounted on Platform-Blowers of specification : 3 Phase ,Power Input-1.5 HP,2900 RPM, Air flow 2000 cub.mtr/hr and the blower discharge size of 200 mm x100 mm (internally) & coupled with FRP Ducting sized 150 x110 mm spaced at a distance of 400 mm. |
| 45 | (xii) The Composters are provided with an SS handle of size 250 mm and SS hinges Complete.We above package also includes Greenrich Microbes for usage of 1 month - Aerobic Microbial Composting Culture Specification- Composting agent formulated using cocopeat along with micro & macro nutrients and Cultured with Lignocellulolytic Organisms, Complete all as specified and directed Make : Greenrich .or equivalent make. |
| 46 | Supply ,testing and commosioning ofShredder Cum Predigestor of capacity 10 HP have Following Specification. (i) Predigestor with Working capacity 800-1000 Kg per Hour (ii)Motor 10 HP (5 HP+5HP) (iii) Material of the Shredder cum Predigestor is MS/Carbon steel(iv) MOC of Mesh & Hopper is Stainless Steel (ss)all as specified and directed by Engr-in-Charge.Make: Greenrich .or equivalent make. |
| 47 | Supply ,testing and commosioning of Churner of Capacity 5 HP have Following Specification-(i) Churner with Working Capacity : 800-1000 Kg per hr (ii) matreial of the outer Body is Mild Steel (MS)(iii)Material of inner Body is Stainless Stell (SS),Complete all as specified and directed byEngr-in Charge. Make : Greenrich or equivalent make. |
| 48 | Supply of Green rich microbes for 2 years (20 Ltrs Bags) ihave Following Specification-(i) Type of Bio culture-Aerobic microbial Composting Culture Specification- Composting agent formulated using cocopeat along with micro & macro nutrients and cultured with lignocelluloytic Organisms. (ii) Fungal Population Count-in the range of 105 to 106 Odour -Free Electrical Conductivity with in the range of 0.4 -3 PH With in the range of 5-6.5 For Composting Process is 30 days. Complete all as specified and directed. Make : Greenrich or equivalent make. |
| 49 | Supply ,testing and commosioning of Screw Conveyor 2.5 mtr length have Following Specification- (i) 600 mm Length x 750 mm width x800 mm Height (ii) Belt: PVC Green colour(iii) speed is 4 m/min(iv) Frames consist of Powder Coated Mild steel (MS) (v) Roller consist of Zinc coasted Mild Steel (MS) , (vi) Power Input : Single phase 230V (vii) speed is variable through VFDComplete all as specified and directed.Make: Greenrich or Equivalent make. |
| 50 | Supply ,testing and commosioning ofDust Remover Machine Following Specification- (i) 10 HPMoto New Standard Company (ii) Roll heavy Duty 115 MM (iii) 45 MM pedestal Bearing Heavy duty(iv) Heavy duty machine fabrication(v) Starter have Star Delta with on /off Button(vi) Benifits of these Additions;Complete all as specified and directed.Make : Greenrich or equivalent make. |
| 51 | Supply ,testing and commosioning ofFlat Conveyor – 6 mtr length have Following Specification-(i) 600 mm Length x 750 mm width x800 mm Height (ii) Belt: PVC Green colour(iii) speed is 4 m/min(iv) Frames consist of Powder Coated Mild steel (MS)(v) Roller consist of Zinc coasted Mild Steel (MS) , (vi) Power Input : Single phase 230V (vii) speed is variable through VFDComplete all as specified and directed. Make:Greenrich or equivalent make. |
| 52 | Supply ,testing and commosioningof Plastic Waste Shredder have Following Specification- (i) Working capacity of 750-800 kg per hr(ii) Moter is 15 HP (7.5 HP +7.5 HP Dual motor) (iii)material of the outer Body consist of Mild steel (MS) (iv)material of the inner Body consist of Stain less steel (SS), Complete all as specified and directedMake: Greenrich.or equivalent make. |
| 53 | Supply ,testing and commosioningof Naturemate Zero Fuel Solid Waste Incinerator have Following Specification- (i)Capacity 100 Kg/hr(ii)Effectice height (from level )-10 mtrs (iii) Green rich Naturemate Zero Fuel Soild Waste Incinerator (400-500 Kg per day) (iv) Combustion Chambers : The Incinerator willinclude separate Combustion chambers for controlled burning of soild waste. the chamber will be designed to mximize combustion efficiencey and minimize emission. (v) diemension : dia.1000mm ,Height 1530 mm , thickness 8 mmfor combustion chamber.(vi) Material :Fine Grain free steel plates,quenched and tempered for tougher and higher impact energy.(vii) volume is 1 cubic meter /35.32 CFT(viii) Thermal insulation (a) inner core :Premium quality cement using reinforce ment TMT -V (b) outer core :Glass wool -50 mm thick protected with aluminium plate 1.00 mm .thick (ix) Other Feathers: Waste loading door,Emergencey door,Peep hole,Ash Chamber with door all as specified and directed. Make: Greenrich or United Saini Builders,Saram Enviro Services Pvt.Ltd.or equivalent make. |
| 54 | Supply ,testing and commosioning have Following Specification: (i)Chimney Material : Carbon steel pipe seamless (ii)Chimney Dimension: A 200 mm diameter Chimney will be installed with a height of 10 mtrs.The chimney will be equipped with emission control devices to ensure compliance with environmental standard. (iii) Emissiion Control devices :Wet scrubbing system with diffuser,Secondary burning with the help of additional airinlets tubes. (iv) Water consumption: 100 lts/ cycle. (v) Additional features :(a) Port hole and access ladder for routine maintenance and emission tests (b) Specially designed diffuser prevents rain water entering the chamber, complete all as specified and directed.Make: Greenrich or United Saini Builders,Saram Enviro Services Pvt.Ltd.or equivalent make. |
| 55 | SEWAGE DISPOSAL WORKS |
| 56 | S&F on site LLDPE conventional septic tak designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, Vent shaft, connection etc., completewith upflow filter including media for 10 Users, complete all as specified and directed |
| 57 | M&L soakage well of size 1.20m dia and 3.0m effective depth excavation in any type of soil foundation in PCC 1:3:6 walls of honey combed masonry with top ring M-25 concrete including intercepting chsmber made of brick masonry in CM RCC cover slab in M-25/ SFRC cover interconnecting pipes of RCC/DWC complete with brick bats complete all as specified and directed |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
| 7 | Click here to download tender document | Tender Documents |
| 8 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail