| Sl. No. | Item Description |
| 1 | Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground (earth pit not less than 2.5 metres deep below normal ground level) with top edge of plate not less than 1.5 meters below normal ground level, connecting to the galvanised earth lead wire 4.0mmdia by means of bolts, nuts, check nuts and washers of galvanised ironor steel protected by provision of GI medium grade pipe 40 mm bore upto test point including provision of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded stone aggregates with 40 mm thick cover of RCC (1:2:4) reinforced with XPM (weigth not loss than 4 Kg/Sqm) and frame of angle iron 25x25x6 mm with lugs 02 Nos and with 6mm dia MS bar handle made to shape, GI light grade 20mmbore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of 40mmx8mmFI with fixing arrangement ,funnel, wire mesh and excavation/earth work in hard dence soil, returning filling in and removal of surplus soil to a distance not exceednig 50 metre, all as per Electric Plate No 3 of SSR 2010 Part-I and connecting to earth test point, all as specified |
| 2 | S&F Earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases or burried in ground or drawn in conduit/pipe or any other indicated situation for loop earthing etc. as required 4.0 mm galvanised iron steel wire in and 20 mm dia GI pipe (in trench) and PVC conduit (on wall)complete all as specified and directed. |
| 3 | M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc as required for 32X6 galvanized iron strip, complete all as specified and directed. |
| 4 | S&F Earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases or burried in ground or drawn in coduit/pipe or any other indicated situation for loop earthing etc. as required 25x4 mm copper strip complete all as specified and directed. |
| 5 | S&F Earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases or burried in ground or drawn in coduit/pipe or any other indicated situation for loop earthing etc. as required 20x3 mm copper strip complete all as specified and directed. |
| 6 | S&F in replacement MCCB 630 Amps 4 Pole breaking capacity 50 KA microprocessor based (ICS=100% of ICU) with rotary handle includingtaking down old u/s MCCB complete all as specified and directed.. |
| 7 | S&F in replacement MCCB 400 Amps 4 Pole breaking capacity 35 KA microprocessor based (ICS=100% of ICU) with rotary handle includingtaking down old u/s MCCB complete all as specified and directed.. |
| 8 | S&F in replacement MCCB 250 Amps 4 Pole breaking capacity 35 KA microprocessor based (ICS=100% of ICU) with rotary handle includingtaking down old u/s MCCB complete all as specified and directed.. |
| 9 | S&F in replacement MCCB 200 Amps 4 Pole breaking capacity 35 KA microprocessor based (ICS=100% of ICU) with rotary handle includingtaking down old u/s MCCB complete all as specified and directed.. |
| 10 | S&F in replacement MCCB 160 Amps 4 Pole breaking capacity 25 KA Thermal magnetic release (ICS=100% of ICU) with rotary handle includingtaking down old u/s MCCB complete all as specified and directed.. |
| 11 | S&F in replacement MCCB 125 Amps 3 Pole breaking capacity 25 KA Thermal magnetic release (ICS=100% of ICU) with rotary handle includingtaking down old u/s MCCB complete all as specified and directed.. |
| 12 | S&F in replacement MCCB 25-100 Amps 3 Pole breaking capacity 16 KA Thermal magnetic release (ICS=100% of ICU) with rotary handle includingtaking down old u/s MCCB complete all as specified and directed.. |
| 13 | S&F MCB SP, C-curve, 230 V 6-32 Amps 10 KA complete all as specified and directed. |
| 14 | S&F MCB SPN, C-curve, 230 V 32 Amps 10 KA complete all as specified and directed. |
| 15 | S&F in replacementMCB TPN,32 Amp, C curve 50 Hz, 415 V with rupturing capacity 10 KA complete all as specified and directed. |
| 16 | S&F in replacementMCB TPN,40 to 100 Amp, C curve 50 Hz, 415 V with rupturing capacity 10 KA complete all as specified and directed. |
| 17 | Taking down carefully copper/Aluminium point wiring for light,Fan,Socket or power point complete including fittings and fixures such as switches, ceiling rose, pendents, regulators, sockets, light fittings etc. Removing materials to store to keeping in safe custody or taking credit (credit for above item should be made as per conditions separately) and making good disturbed surface of wall, floor as per existing etc. |
| 18 | M&L Point wiring with multistranded copper conductor PVC Insulated and unsheathed cable in existing PVC concealed conduit with1.5 SQMM FRLSH cable with all fittings /accessories and including 1.5 Sqmm PVC insulated copper earth wire connected common earth with terminal boxes for Moduler fittings including acessories as moduler surface cover plate with frame, metal flush box, for one light/Fan/Exhaust Fan point complete and making good the existing disturbed surface. |
| 19 | Ditto as per item ser No 18.00 but 5 Amp socket point indipendent. |
| 20 | M&L for one pointwiring of any length as per site requirment with PVC insulated FR LSH unsheathed copper conductor cable of size 2.5 sqmm including earth wire of size 1.5 Sqmm in and including concealedPVC conduit including MS bos suitable of modular fittings ,inner and outermodular top sheet top cover,for one 3 pin socket outlet 15 Amps independent all as specified . |
| 21 | S & Fmodular socket 6 amp-2/3 pin combined 2module complete all as specified and directed. |
| 22 | S&F Modular switch 1 way 6 Amp 1 Module complete all as specified and directed. |
| 23 | S&F Modular socket1 way 16Amp 2 Module complete all as specified and directed. |
| 24 | S&F Modular switch 1 way 16 Amp 1 Module complete all as specified and directed. |
| 25 | M&L in replacement of sub main wiring with four run of single core PVC insulated FRLSH stranded copper conductor cable of size 16 Sq mm and two run of 16 Sq mm PVC insulated FRLS copper conductor cable as earth continuity conductordrawn in and in existing surface PVC conduit concealed medium grade complete all as directed. |
| 26 | M&L in replacement of sub main wiring with four run of single core PVC insulated FRLSH stranded copper conductor cable of size 10 Sq mm and two run of 10 Sq mm PVC insulated FRLSH copper conductor cable as earth continuity conductordrawn in and in existingsurface PVC conduit concealed medium grade complete all as directed. |
| 27 | M&L in replacement of sub main wiring with two run of single core PVC insulated FRLSH stranded copper conductor cable of size 6 Sq mm and one run of 6 Sq mm PVC insulated FRLSH copper conductor cable as earth continuity conductordrawn in and in existing surface PVC conduit concealed medium grade complete all as directed. |
| 28 | M&L in replacement of sub main wiring with two run of single core PVC insulated FRLSH stranded copper conductor cable of size 2x4 Sq mm and one run of 4 Sq mm PVC insulated FRLSH copper conductor cable as earth continuity conductordrawn in and in existing surface PVC conduit concealed medium grade complete all as directed. |
| 29 | S&F in replacement energy efficient LED light fitting surface mounted 4\" long, 20 watt, 240 volts, 50 hz made out of extrunded aluminium housing with acrylic diffuser, LM 80 certified LED, costant current out put of electronic driver of operating voltage 140v to 270v and temperature - 10 digree centigrade to 50digree centigrade with ingress protection IP 20 duly pre wired with insulated copper wire, PF>0.95 with efficiency 120 lumins/watt and TDH less than 10%, CRI > 90 digree , CCT 6500 K in and including connecting up with twin core copper flexible cable of suitable size upto ceiling rose complete all as specified and directed. |
| 30 | S&F in replacement Photon Ultra LED Tubelight (Single Side Connection) LED Rod 20 watt Ultra bright LED polycarbonate Tubelight with very high efficacy suited for installation in existing T8 fittingwith G13 lamp holders complete all as specified and directed. |
| 31 | S&F in replecement energy efficient LED light fitting, slim LED panel, recessed/surface mounting 2 ftx 2 ft made out of power coated CRCA sheet with acrylic diffuser, constant current output of electronic driver operating voltage range of 150 to 270 volts AC, PF>0.95, high powder LEDs having efficiency of 100-120 lumins/watts, junction temparature less than 85 digree C and TH less than 12 % and CCT 6500K,, CRT>90 suitable for 36 watt LED, LM 80 certified LM, pri wired in and including connecting up with twin core copper flexible cable of suitable size upto ceiling rose /connector etc and testing complete all as specified and directed. |
| 32 | Supply,laying,testing and commissionnig ofLT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, Crimping type cable lugs in LT panel/ MCCBin bldg etc to suit the cablelaid in trenches/fixed to poles/drawn through pipes complete ofsizes 16 Sqmm 4 core including taking down old unserviceable cable complete all as specified and directed. |
| 33 | Supply,laying,testing and commissionnig ofLT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, Crimping type cable lugs in LT panel/ MCCBin bldg etc to suit the cablelaid in trenches/fixed to poles/drawn through pipes complete ofsizes 25 Sqmm 4 core including taking down old unserviceable cable complete all as specified and directed. |
| 34 | Supply,laying,testing and commissionnig ofLT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, Crimping type cable lugs in LT panel/ MCCBin bldg etc to suit the cablelaid in trenches/fixed to poles/drawn through pipes complete ofsizes 35 Sqmm 3.5 core including taking down old unserviceable cable complete all as specified and directed. |
| 35 | Supply,laying,testing and commissionnig ofLT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, Crimping type cable lugs in LT panel/ MCCBin bldg etc to suit the cablelaid in trenches/fixed to poles/drawn through pipes complete ofsizes 50 Sqmm 3.5 core including taking down old unserviceable cable complete all as specified and directed. |
| 36 | Supply,laying,testing and commissionnig ofLT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, Crimping type cable lugs in LT panel/ MCCBin bldg etc to suit the cablelaid in trenches/fixed to poles/drawn through pipes complete ofsizes 70 Sqmm 3.5 core including taking down old unserviceable cable complete all as specified and directed. |
| 37 | Supply,laying,testing and commissionnig ofLT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, Crimping type cable lugs in LT panel/ MCCBin bldg etc to suit the cablelaid in trenches/fixed to poles/drawn through pipes complete ofsizes 95 Sqmm 3.5 core including taking down old unserviceable cable complete all as specified and directed. |
| 38 | Supply,laying,testing and commissionnig ofLT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, Crimping type cable lugs in LT panel/ MCCBin bldg etc to suit the cablelaid in trenches/fixed to poles/drawn through pipes complete ofsizes 120 Sqmm 3.5 core including taking down old unserviceable cable complete all as specified and directed. |
| 39 | Supply,laying,testing and commissionnig ofLT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, Crimping type cable lugs in LT panel/ MCCBin bldg etc to suit the cablelaid in trenches/fixed to poles/drawn through pipes complete ofsizes 150 Sqmm 3.5 core including taking down old unserviceable cable complete all as specified and directed. |
| 40 | Supply,laying,testing and commissionnig ofLT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, Crimping type cable lugs in LT panel/ MCCBin bldg etc to suit the cablelaid in trenches/fixed to poles/drawn through pipes complete ofsizes 240 Sqmm 3.5 core including taking down old unserviceable cable complete all as specified and directed. |
| 41 | Supply,laying,testing and commissionnig ofLT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, Crimping type cable lugs in LT panel/ MCCBin bldg etc to suit the cablelaid in trenches/fixed to poles/drawn through pipes complete ofsizes 300 Sqmm 3.5 core including taking down old unserviceable cable complete all as specified and directed. |
| 42 | Supply,laying,testing and commissionnig ofLT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, Crimping type cable lugs in LT panel/ MCCBin bldg etc to suit the cablelaid in trenches/fixed to poles/drawn through pipes complete ofsizes 400 Sqmm 3.5 core including taking down old unserviceable cable complete all as specified and directed. |
| 43 | Supplying and laying synthetic rubber insulated mats 3 mm thick for voltage upto 3.3 KV (size 2 m x 1 mtr) for electrical purpose as per IS 15652-2006 suitable for electrical shock safety complete all as directed by Engr in charge. |
| 44 | S&F in repair LT three phase digital multifunctional meter suitable for measure all electrical qualities like voltmeter, current, power, Frequency & power factor complete all as specified and directed. |
| 45 | M&L for painting of LT panel indoor/outdoor type area of front face of panel exc 1.5 sq mm but n. exc 2.5 sq m each with spray gun with two coats of synthetic enamel heat resistant grey paint including preparation of old painted surface/ removing old faded/rust/cemented material of surface of complete LT panel , complete all as specified and directed. |
| 46 | Taking out of Old ACB and Supply and fixingACB 1600 Amps 4 pole 415V, 50Hz AC with microprocessor-based release having O/L, S/C & E/F protection with indicator & draw interlocking out/fixed type with EDO operating mechanism confirming to IS 13118 duly retrofit in existing indoor panel in including all electric connection and fixing the same in existing panel including necessary modification with angle iron and plain sheet all as directed. |
| 47 | S&F sheet metal enclosure, SPN industrial type with two pin & earth plug and socket (industrial type DB) with and including one MCB SP, C Curve type of capacity 20 Amp, 10 KA complete all as specified and directed. |
| 48 | S&F triple pole and neutral enclosure with a three pin and earth plug and socket industrial type complete with one triple pole MCB of rating 32 Amps complete all as specified and directed. |
| 49 | Supply and fixing in replacement ofSPN DB 8 ways with 200 amps rated busbar 240 volt double door complete all as specified and directed. |
| 50 | Supply and fixing in replacement of SPN DB 12 ways with 200 amps rated busbar 240 volt double door complete all as specified and directed. |
| 51 | Supply and fixing in replacement ofTPN DB 4 ways with 200 amps rated busbar 415 volt double door complete all as specified and directed. |
| 52 | Supply and fixing in replacement ofTPN DB 8 ways with 200 amps rated busbar 415 volt double door complete all as specified and directed. |
| 53 | M&L for Chemical spray WD-40 having container 420mlfor precision blended multipurpose product for prevents corrosion penetrates, lubricates, displaces and seals out moisture release rusted mechanism cleanse etc. |
| 54 | S&F DLP U-PVC trunking system size 195x50 mm with all accessories for fittings including flexible cover (make as approved by GE)complete all as specified and directed. |
| 55 | S&FDLP U- PVC trunking system size 150x50 mm with all accessories for fittings including flexible cover (make as approved by GE)complete all as specified and directed. |
| 56 | S&F in replacement MNX 50 contactor with suitable auxiliary contactor (NO/NC) including taking down old burnt contactor complete all as specified and directed. |
| 57 | S&F in replacement MNX A1 contactor including taking down old burnt contactor complete all as specified and directed. |
| 58 | S&F in replacement MNX A2 contactor including taking down old burnt contactor complete all as specified and directed. |
| 59 | S&F in replacement ML-3 contactor including taking down old burnt contactor complete all as specified and directed. |
| 60 | S&F in replacementB1 metal over load relay 30-50 Amp including taking down old burnt relay complete all as specified and directed. |
| 61 | S&F in replacementB1 metal over load relay 6-10 Amp including taking down old burnt relay complete all as specified and directed. |
| 62 | S&F in replacementstar-delta timer micon series including taking down old burnt timer complete all as specified and directed. |
| 63 | S&F in repalacement Indoor unit suitable for2 TR split type AClabour cost for fixingand taking down costdeemedin quotedrate complete all as specified and directed. (Old unserivceable indoor unit will be diposited to MES Store) |
| 64 | S&F in repalacement outdoor unit suitable2 TR splittype AC, without compressor labour cost for fixingand taking down costdeemedin quotedrate complete all as specified and directed. (Old unserivceable indoor unit will be diposited to MES Store) |
| 65 | Supply & Fixing in replacement hermetically sealed compressor for split/ window type AC capacity 1.5 Ton labour cost for fixingand taking down costdeemedin quotedratecomplete all as specified and directed.Note:- Compressor shall be procured from authorised dealer and contractor shall submit purchase vouchers alongwith written guarantee/warantee as per manufacturer. |
| 66 | All as per ser item No. 65.00 above but for split/ window type AC capacity 2.0 Ton. |
| 67 | All as per ser item No. 65.00 above but for split type AC capacity 3.0 Ton three phase run. |
| 68 | Taking out window type AC complete unit from any height/ any floor up to threestorey buildingand shifting to another locationin the sameor other building in the complex including refixing & reconnection of the unit, testingcomplete all as specified and directed. |
| 69 | Taking out split type AC complete indoor and outdoor unit from any height/ any floor up to threestorey buildingbyincluding pumping down the gas into thecompressor by controlling the suction and discharge valves , disconnecting the suction and dischagre copper piping and shifting to another locatiionin the sameor other building in the complex including refixing of the unit with electric connections and testing complete all as specified and directed. |
| 70 | Supply and charging the refrigerant gas R-22 in window type AC upto 3 ton capacity after and including testing with application of nitrogen gas pressure to find out any leakage, brazing and stopping of all leakage detected, re-application of nitorgen pressure to ensure leak proof gas circulator system flushing out the nitrogengas complete all as specified and directed. |
| 71 | All as per ser item No. 70.00 above but R- 410/32 for split type AC up to 3 TR capacity. |
| 72 | S&F in replacementdigital ampere meter 96x96 mm flust type rated 0-300 A with ampere meter selector switch ) including taking down old burnt ampere meter complete all as specified and directed. |
| 73 | S&F in replacementdigital Volt meter 96x96 mm flust type rated 0-500 V with volt meter selector switch including taking down old burnt volt meter complete all as specified and directed. |
| 74 | S&F in replacementdigital ampere meter (0-100 Amp) including taking down old burnt ampere meter complete all as specified and directed. |
| 75 | S&F in replacementdigital ampere meter (0-30 Amp) including taking down old burnt ampere meter complete all as specified and directed. |
| 76 | S&F in replacement CT 250/5 A,CL 1.0 tape wound including taking down old burnt CT complete all as specified and directed. |
| 77 | S&F in replacement CT 100/5 A, CL 1.0 including taking down old burnt CT complete all as specified and directed. |
| 78 | S&F in replacement CT 30/5 A, CL 1.0 including taking down old burnt CT complete all as specified and directed. |
| 79 | S&F in replacement single phase preventer including taking down old burnt single phase preventer complete all as specified and directed. |
| 80 | S&F in replacement push button start/stop with element including taking down old burnt push button complete all as specified and directed. |
| 81 | S&F in replacement On/Off/Trip indicating Lights LED (RYB)type 220 V AC including taking down old burnt Led light complete all as specified and directed. |
| 82 | S&F in replacement selector switch including taking down old U/s switch complete all as specified and directed. |
| 83 | M&L for servicing of AMF panel of any size/make, check all loose connections of end terminals, screws, nuts, bolts thimbles, clean all electric/electronic parts by using CRC spray, check contactors connections and its serviceability, check all relay setting of AMF panel and check all internal connections of AMF Panel and hinges and locking devices complete all as directed. |
| 84 | S&F 630 Amp vacuum interrupter for 11KV Vacuum Circuit Breaker complete all as specified and directed. |
| 85 | Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for laying of Cable or Pipe, electric pole, stay assembly etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and directed. |
| 86 | M&L for cutting hard standing/ Road cutting for taking up or laying of LT UG cable/pipe upto a depth of 15cm and after laying of cable, well ramming to the excavated soil and repair the cutting/exvcavated portion of road by providing PCC (1:2:4) type B1 (using 20mm graded stone aggregate) complete all as specified and directed. |
| 87 | Returning, filling in , including spreading, leveling, watering and well ramming in layers not exc 25 cm. in soft/loose soil complete all as specified and directed. |
| 88 | Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point in soft/loose soil complete all as specified and directed. |
| 89 | M&L for sub class \"B\" burnt brick flat across the cable, for protection of cable laid in trenches complete all as specified and directed |
| 90 | M&L for Galvanized steel tubing, light grade, with All fittings of size 40mm dia for protection of cable including taking down old, rusted & corroded unsv Galvanized steel tubing complete all as specified and directed. |
| 91 | Supply and spreading clean fine dry river sand in trenches for cushioning of under ground cable / cable duct. (Only punned thickness shall be measured for payment purpose) complete all as specified and directed. |
| 92 | M&L for PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate)in roof kerbs or mud stops, rounded or chamfered on edges etc complete all as specified and directed. |
| 93 | M&L for PCC 1:4:8 Type D2 (using 40 mm graded crushed stone aggregate) in foundations, filling and mass concrete complete all as specified and directed. |
| 94 | Supply and fixing in replacement old unserviceable PVC insulated multistranded copper conductor wire of size 16 Sqmm, single core, 1100 volts complete all as specified and as directed. |
| 95 | All as per item No 94.00 but size 25 Sqmm |
| 96 | S&F in replacement of3 Pole MCCB,160 Amp, 50 Hz, 415 V with rupturing capacity 36 KA thermal magnetic release base with Icu= 100% ICSincl rotating handle & taking down the existing MCCBcomplete all as specified & directed |
| 97 | S&F in replacement of3 Pole MCCB,250 Amp, 50 Hz, 415 V with rupturing capacity 36 KA microprocessor base release with Icu= 100% ICSincl rotating handle & taking down the existing MCCBcomplete all as specified & directed |
| 98 | S&F in replacement of 3 Pole MCCB,400 Amp, 50 Hz, 415 V with rupturing capacity 36 KA microprocessor base release with Icu= 100% ICSincl rotating handle & taking down the existing MCCBcomplete all as specified & directed |
| 99 | Material and Labour for earthing complete with GI earth plate electrode 600mmx600mmx6mm thick burried in ground vertically to a depth not less than 2.5meters below ground level with top edge of the earth plate at a depth not less than 1.5 meter below the ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same.GI plate connected with galvanised iron strip of 25mmx4mm by means of Copper nuts, bolts and washers.Strip laid in 40mm dia light grade GI pipe as protection from top of the plate up to test point (cost of protection pipe up to 7.5 meters from earth electrode will be included in the rates quoted by the contractor) with following complete all as specified and shown in electrical plate No 5 of SSR Part-I & testing on completion :-(a)GI strip of size 25mm x 4mm. (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit.(GI Funnel shall be properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitable for watering of earth pits)(c)Excavation & earthwork in any type of soil PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 plaster including RCC pit cover 50mm thick 1:2:4 type B1 reinforced with 8mm dia mild steel bar 75mm centre to centre with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover. |
| 100 | M&L GI strip 25mmx4mm buried in ground including necessary excavation & earth work in soft/loose soil and removal of excavated material to a distance n.exc 50 mtrs and deposited where directed including taking out old unserviceablecomplette all as specified & directed. |
| 101 | S&F in replacement Digital ammeter of existing size 100mm (Square type) with selector switch & copper thimble and connecting up incl taking down the existing complete all as specified and directed. |
| 102 | S&F in replacementDigital multimeter of existing size 100mm (Square type)with selector switch & copper thimble and connecting up incl taking down the existing complete all as specified and directed. |
| 103 | S&F in replacementElectronic timer type ET-100, 9 to 30 sec, 415V suitable for star-delta/DOL starter upto 30 HP capacity complete all as specified & directed. |
| 104 | S&F in replacement 3 phase sequence relay suitable for 30 HP motor with supply voltage range of 200-480 VAC, frequency 50 Hz & response time less than 1 sec complete all as specified and directed. |
| 105 | M&L for B check general servicing by authorised rep of manufacturer of DG set of capacity upto 75 KVA, replacement of oil filter, fuel filter, air filter, by pass filter cleaning of radiator with chemical afterdraining out engine/ lubrication oil, coolant flushing and cleaning of oil chamberafter opening of tappet cover/ top cover tappet clearence setting with injector timing adjustment reaffixing of tappet/ top cover including replacement of tappet cover packing set, bonding and leak proof sollution, oil pan/ chamber gasketat the servicing and other work comes under B Check service as mentioned in B Check by the manufacturer all as speciied and as directed.Note-Engine oil & Coolant will be included under respective item. |
| 106 | All as per item No 105.00 but DG set of capacity 250KVA |
| 107 | M&L for repair of self starter 12 V including rewinding of armature with super enamaled copper conductor wire of superier quality as per existing gauge, turn and pattern and replacement of bendex drive, carbon brush including services suitable for DG set of capacity upto 75 KVA complete all as specified and directed. |
| 108 | All as per item No 107.00 but 24 V for DG set of capacity 250KVA |
| 109 | Supply & Fixing in replacement of automatic battery charger with auto cut OFF suitable for charging of 2X12V 180AH batteries complete with all required necessary wiring complete all as specified and directed. |
| 110 | Supply & Fixing in replacement of automatic battery charger with auto cut OFF suitable for charging of 12V 180AH batteries complete with all required necessary wiring complete all as specified and directed. |
| 111 | M&L for replacement of wiring complete to AMF panel for any capacity of DG set includinginterlock system of AMF panel with existing size of copper wiring including proper connection and testing complete all as specified and directed. |
| 112 | Supply and Fix in replacement of battery brass terminals heavy duty suitable for 12V 180 AH battery with minimum 2 RM Battery Lead of copper Cable single core all as directed by engr-in-charge. |
| 113 | Supply and Fixin replacement ofrelay 24 V 8 pin type as per matching to existing and properly connection and testing after completion complete all as specified and directed. |
| 114 | Taking down the old U/S fan belt and Supply andFix Fan belt of existing size for DG Set of capacity 250 KVA complete all as specified and directed. |
| 115 | Supply and Cladding with glass/rock wool and aluminium sheets of exhaust manifoldforfor DG sets 250 KVA includung removing of existing asbestos rope or any other type of insulation complete all as specified and directed. |
| 116 | Supply and fixingin replacement 3 pole power contactor MNX400, 400 Amps, 415 Volts, 50 HZ complete all as specified and as directed. |
| 117 | Supply and fixingin replacement 3 pole power contactor MNX250, 250 Amps, 415 Volts, 50 HZ complete all as specified and as directed. |
| 118 | S&F in replacement fly wheel ring of DG Set of capacity 250 KVA as per existing make & model complete all as specified and directed. |
| 119 | S&F in replacement fly wheel ring of DG Set of capacity upto 75 KVA as per existing make & model complete all as specified and directed. |
| 120 | M&L for draining out the diesel tank, cleaning/washing out the sludge and re-filling with diesel for the DG Set of capacity upto 250KVA complete all as specified and directed. |
| 121 | M&L for repair toradiator of 250 KVA DG set,arresting leakage if any by welding/brazing and refixing the same for(Necessary coolant and distrilled water required will be measured and paid seperately) complete all as specified and directed. |
| 122 | M&L for repair toradiator ofDG of capacity upto 75KVA set,arresting leakage if any by welding/brazing and refixing the same for(Necessary coolant and distrilled water required will be measured and paid seperately) complete all as specified and directed. |
| 123 | Removing old U/Sinsulating material asbestos rope and fixing of newof existing size and shape complete all as directed |
| 124 | M&L for repair to alternator of DG Set of capacity 250 KVA complete including rewinding & replacement of connected items such as bearing, sleeves Nut bolts, coupling etc complete all as specified and as directed |
| 125 | Removing and replacing the old unserviceable lead acid battery of size 12 Volt, 180 AH of reputed make including charging all as specified as directed. |
| 126 | S&F ACP retro sign board of size 1.8 x 0.4 Meter using retro reflective high intensity prismatic reflective sheeting. The back ground of board is Blue Colour with white border and writing letter, numbers white colour mentioning the Pump House details and MES Logo. Retro sign board shall be pasted on 3 mm thick ACP sheet. The board shall be fixed on Wall including fixing of fastners, nuts, bolts, washer etc complete all as directed by Engineer-in-Charge at site. |
| 127 | S&F ACP retro sign board of size 1.8 x1.2 Meter using retro reflective high intensity prismatic reflective sheeting. The back ground of board is Blue Colour with white border and writing letter, numbers white colour mentioning the Single line Schematic diagram of Pump House. Retro sign board shall be pasted on existing board complete all as directed by Engineer-in-Charge at site. |
| 128 | Supply and fixing in replacement DOL starter upto 5 HP complete all as specified & directed |
| 129 | Supply only sodium hypochloride (liquid bleach) 10 % (20 ltr each pack) complete all as specified and directed. |
| 130 | M&L for LED energy saving and environmental friendly long life versatile pressure diw cast aluminium IP 66 roadway luminaire with high power LEDs and electronic diver complete set of 60 wattage 6000K, with PF-=>0.95, THD-<=10%, driver should be same make as of LED fitting, with operating range of 140 V to 280 V, isolation of driver facility as directed complete all as specified and directed by Engineer-in Charge. |
| 131 | M & Lfor replacement of cable PVC insulated unarmored for connection 1.5 sqmm x 3 core Copper conductor duly drawn fromjunction box to street light fittings on poles including PVC flexible pipes complete all as specified and directedby Engineer-In - Charge. |
| 132 | M&L in Replacement of GI bracket made of 40 mm medium grade GI pipe bend to shape approx 1.8 mtr length incl Clamp etc complete for fixing of street light complete all as specified and directed. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail