| 1 | BATTERIES |
| 2 | Supply, Transportation, Unloading , installation, testing & Commissioning of 12 Volt, 120AhSealed Maintenance Free (SMF) – Valve Regulated Lead Acid (VRLA) battery cells, suitable for online UPS, conforming to relevant international standards including, • JIS C 8702 Certified • UL(UL-1989) & CE Certified, • Complies to IEC61056 & EUROBAT,• Complied IS 16220. • Manufactured in ISO 9001, ISO 14001, ISO45001:2018 certified facilities.Each module shall have a rated capacity of 120Ah at C20 to 1.75 ECV at 27°C, with AGM-based VRLA construction, non-spillable and maintenance-free, suitable for Industrial and UPS applicationsInstallation shall include placement, interconnection, torque tightening, polarity verification, labeling, and ensuring adequate ventilation. Submission of all certificates, test reports, and warranty documents along with Invoices.Battery Type : Maintenance Free Valve Regulated Lead Acid (MF-VRLA)Nominal Voltage : 12VBattery Rating / Capacity : 12V-120 AH to 1.75 ECV @ C20 at 27°C.Float charging voltage : ≥13.5 volts per module @ 27°C.Boost charging voltage : ≥13.8 volts per module @ 27°CCurrent limit : 12 Amps Minimum to 6.5 Amps Maximum.Voltage ripple allowable : < 2% of the RMS. ValueAH efficiency : Above 95%WH efficiency : Above 85%Operating Temperature Range of Battery : -20°C to +60°CSelf-Discharge/Week : < 1% of rated capacity. |
| 3 | Storage. Stored in a Covered area at 27°C Material of container & Cover : Polypropylene co-polymer.Type of separator : Highly absorbent Micro porous spun glass matrix.(AGM), Type of +Ve & -Ve plates : Flat pasted.Life of battery at 27°C : Life of battery at 27 deg c1150 to 1300 cycles at 30 % DOD (OR) 550 to 650 cycles at 50 % DOD (OR) 370 to 450 cycles at 80 % DOD.Batteries generally conform to : JIS 8702C international standard.Internal Resistance (IR) : Approx. 9.8 mΩ for a fully charged battery (27°C). Short Circuit Current (As per IEC) : 1278A,Operating Temp. range : -20°C to +60°C (50 to 60°C for shorter duration),Nominal Operating Temp. range : 27°C ±3°C, Standby use (27°C) : Charging Voltage≥13.5 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±18mV/battery/°C, Cyclic use (27°C): Charging Voltage≥13.8 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±30mV/battery/°C. Design Float life of upto 10 years. The entire battery unit should have minimum of 2 year Warranty.Schedule of Batteries: 1. VVF Block(88 nos), 2. Admin Block(88 nos)Buyback of old used 12V 120 AH UPS batteries (Tubular/SMF type), to be collected by supplier post-installation of new batteries. |
| 4 | 12 V 120 AH |
| 5 | Supply, Transportation, Unloading , installation, testing & Commissioning of 12 Volt, 100AhSealed Maintenance Free (SMF) – Valve Regulated Lead Acid (VRLA) battery cells, suitable for online UPS, conforming to relevant international standards including, • JIS C 8702 Certified • UL(UL-1989) & CE Certified, • Complies to IEC61056 & EUROBAT,• Complied IS 16220. • Manufactured in ISO 9001, ISO 14001, ISO45001:2018 certified facilities.Each module shall have a rated capacity of 100Ah at C20 to 1.75 ECV at 27°C, with AGM-based VRLA construction, non-spillable and maintenance-free, suitable for Industrial and UPS applicationsInstallation shall include placement, interconnection, torque tightening, polarity verification, labeling, and ensuring adequate ventilation. Submission of all certificates, test reports, and warranty documents along with Invoices.Battery Type : Maintenance Free Valve Regulated Lead Acid (MF-VRLA)Nominal Voltage : 12VBattery Rating / Capacity : 12V-100 AH to 1.75 ECV @ C20 at 27°C.Float charging voltage : ≥13.5 volts per module @ 27°C.Boost charging voltage : ≥13.8 volts per module @ 27°CCurrent limit : 12 Amps Minimum to 6.5 Amps Maximum.Voltage ripple allowable : < 2% of the RMS. ValueAH efficiency : Above 95%WH efficiency : Above 85%Operating Temperature Range of Battery : -20°C to +60°CSelf-Discharge/Week : < 1% of rated capacity. |
| 6 | Storage. Stored in a Covered area at 27°C Material of container & Cover : Polypropylene co-polymer.Type of separator : Highly absorbent Micro porous spun glass matrix.(AGM), Type of +Ve & -Ve plates : Flat pasted.Life of battery at 27°C : Life of battery at 27 deg c: 1150 to 1300 cycles at 30 % DOD (OR) 550 to 650 cycles at 50 % DOD (OR) 370 to 450 cycles at 80 % DOD.Batteries generally conform to : JIS 8702C international standard.Internal Resistance (IR) : Approx. 9.8 mΩ for a fully charged battery (27°C). Short Circuit Current (As per IEC) : 1278A,Operating Temp. range : -20°C to +60°C (50 to 60°C for shorter duration),Nominal Operating Temp. range : 27°C ±3°C, Standby use (27°C) : Charging Voltage≥13.5 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±18mV/battery/°C, Cyclic use (27°C): Charging Voltage≥13.8 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±30mV/battery/°C. Design Float life of upto 10 years.The entire battery unit should have minimum of 2 year Warranty.Schedule of Batteries: 1. RABIES Block(44 nos)2. ANIMAL HOUSE (32 nos)3. BCG BLOCK (44 nos)Buyback of old used 12V 100 AH UPS batteries (Tubular/SMF type), to be collected by supplier post-installation of new batteries. |
| 7 | 12 V 100 AH |
| 8 | Supply, Transportation, Unloading , installation, testing & Commissioning of 12 Volt, 26AhSealed Maintenance Free (SMF) – Valve Regulated Lead Acid (VRLA) battery cells, suitable for online UPS, conforming to relevant international standards including, • JIS C 8702 Certified • UL(UL-1989) & CE Certified, • Complies to IEC61056 & EUROBAT,• Complied IS 16220. • Manufactured in ISO 9001, ISO 14001, ISO45001:2018 certified facilities.Each module shall have a rated capacity of 26Ah at C20 to 1.75 ECV at 27°C, with AGM-based VRLA construction, non-spillable and maintenance-free, suitable for Industrial and UPS applicationsInstallation shall include placement, interconnection, torque tightening, polarity verification, labeling, and ensuring adequate ventilation. Submission of all certificates, test reports, and warranty documents along with Invoices.Battery Type : Maintenance Free Valve Regulated Lead Acid (MF-VRLA)Nominal Voltage : 12VBattery Rating / Capacity : 12V-26 AH to 1.75 ECV @ C20 at 27°C.Float charging voltage : ≥13.5 volts per module @ 27°C.Boost charging voltage : ≥13.8 volts per module @ 27°CCurrent limit : 2.6 Amps Minimum to 6.5 Amps Maximum.Voltage ripple allowable : < 2% of the RMS. ValueAH efficiency : Above 95%WH efficiency : Above 85%Operating Temperature Range of Battery : -20°C to +60°CSelf-Discharge/Week : < 1% of rated capacity. |
| 9 | Storage. Stored in a Covered area at 27°C Material of container & Cover : Polypropylene co-polymer.Type of separator : Highly absorbent Micro porous spun glass matrix.(AGM), Type of +Ve & -Ve plates : Flat pasted.Life of battery at 27°C .Cycle Life of battery at 27°C : 4000 cycles at 20% Depth of Discharge(DOD) (or)2000 cycles at 50% DOD (or)1200 cycles at 80% DOD. Design Float life of upto 20 yearsThe entire battery unit should have minimum of 2 year Warranty.Schedule of Batteries: 1. UTILITY Block(34 nos)2. MRS SUBSTATION (34 nos)3. CENTRAL LAUNDRY(34 nos) ;4 Secondary packing(34 nos) Buyback of old used 12V 26 AH UPS batteries (Tubular/SMF type), to be collected by supplier post-installation of new batteries. |
| 10 | 12 V, 26 AH |
| 11 | Supply, Transportation, Unloading , installation, testing & Commissioning of 2 Volt, 100AhSealed Maintenance Free (SMF) – Valve Regulated Lead Acid (VRLA) battery cells, suitable for 110 V DC Battery Charger, conforming to relevant international standards including rack and Connectors.. • IS15549:2005 • IEEE1188 & 1189 • BS-6290, Part-IV• IEC 60896 -21 & 22 :2004, Part – II. • Manufactured in ISO 9001, ISO 14001, ISO45001:2018 certified facilities.Each module shall have a rated capacity of 100Ah to 1.75 ECV @ C10 at 27°C, with AGM-based VRLA construction, non-spillable and maintenance-free, suitable for Industrial and UPS applications.Installation shall include placement, interconnection, torque tightening, polarity verification, labeling, and ensuring adequate ventilation. Submission of all certificates, test reports, and warranty documents along with Invoices.Battery Type : Maintenance Free Valve Regulated Lead Acid (MF-VRLA)Nominal Voltage : 2VBattery Rating / Capacity : 110V / 100 AH to 1.75 ECV @ C10 at 27°C.Float charging voltage : ≥2.23 - 2.25 Volts per Cell @ 27°C.Boost charging voltage : ≥2.30 - 2.32 Volts per Cell @ 27°CCurrent limit : 10 Amps Minimum to 20 Amps Maximum.AH efficiency : Above 95%WH efficiency : Above 85%Operating Temperature Range of Battery : -20°C to +60°CSelf-Discharge/Week : < 1% of rated capacity. |
| 12 | Storage. Stored in a Covered area at 27°C Material of container & Cover : Polypropylene co-polymer.Type of separator : Highly absorbent Micro porous spun glass matrix.(AGM), Type of +Ve & -Ve plates : Flat pasted.Voltage ripple allowable : <2% of the RMS. Value. Life of battery at 27°C :Life of battery at 27 deg c Cycle Life of battery at 27°C : 4000 cycles at 20% Depth of Discharge(DOD) 80% DOD(OR) 370 to 450 cycles at 80 % DOD.Batteries generally conform to : JIS 8702C international standard.Internal Resistance (IR) : Approx. 9.8 mΩ for a fully charged battery (27°C). Short Circuit Current (As per IEC) : 1278A,Operating Temp. range : -20°C to +60°C (50 to 60°C for shorter duration),Nominal Operating Temp. range : 27°C ±3°C, Standby use (27°C) : Charging Voltage≥13.5 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±18mV/battery/°C, Cyclic use (27°C): Charging Voltage ≥ 13.8 V/battery, Charging Current Max. 25% of rated capacity, Temp. Compensation ±30mV/battery/°C. Design Float life of upto 10 years. The entire battery unit should have minimum of 2 year Warranty.Schedule of Batteries: 1. Utility Substation (55 nos) with rack2. Rabies Substation (55 nos) with rack3. VVF Substation (55 nos) with rack4. BCG Substation (55 nos) with rackBuyback of old used 2V 100 AH UPS batteries (Tubular/SMF type), to be collected by supplier post-installation of new batteries. |
| 13 | 2V 100 AH |
| 14 | Comphrensive, Service, Repair and Maintenance of 10 KVA Emerson make UPS system including required parts, not limited to (DC TO DC PCB, SCR DRIVE PCB-3NOS, IGBT-3NOS, SCR-3NOS, MICRON PCB-1NO, DC CAPACITOR-2NOS, COMMUNICATION PCB-1NO & CONTROL, COMMUNICATION PCB-1NO & CONTROL BOARD-1NO ETC. REPLACEMENT CHARGES for complete functioning of the unit as per manufacturer\"s specifications and site requirements.The supplied Parts should have minimum one year warranty.Block:MAin Receiving station |
| 15 | Comphrensive, Service, Repair and Maintenance of 160 KVA Emerson make UPS system including required parts, not limited to, (IGBT -12NOS, FUSE-6NOS, DC CAPACITOR-10NOS, IGBT DRIVE PCB-6 nos, COMMUNICATION PCB-1NO, CONTROL BOARD-1NO & SCR-6NOS ETC. REPLACEMENT CHARGES for complete functioning of the unit as per manufacturer\"s specifications and site requirements.The supplied Parts should have minimum one year warranty.Block : QC Block |