| 1 | PART-A ELECTRICAL WORKS |
| 2 | Supply, installlation, commissionig & testing ofSilent Diesel Generating set, AC, 3 Phase, 50 Hz, capacity 320 KVA/256 KW with CPCB IV+ approved accoustic enclosure, radiator cooled , diesel engine devloping 395 BHP at 1500 RPM, complete with standard accessaries, coupled to alternator rated at 320 KVA/256 KW, 415 volts, mounted on channel iron base frame, complete with fuel tank of capacity 615 ltrscapacity & DEF tank of 60 ltr capacity with AMF Control Panelincluding 2 Nos 12 Volts rechargeable lead acid battery of suitable AH as directed by Engineer-in-Charge including disconnectingserviceable LT UG cables from existing LT panel board & old DG Set etc and reconnecting to new DG Set & AMF panel as required and directed at site complete.Generator Set Specifications: Prime, Power Rating -320 KVA/ 256 KW, 3 phases , Out put voltage & frequency (V & Hz)- 415 V, 50 Hz, power factor - 0.8(Lagging), Current (A) -445 Amps.Engine Specifications:Required certified power for rated KVA (hp) - 395, Cooling- liquid cooled (EG compleat 50-50), DEF- AUS 32 (Premix) as per ISO22241, Aspiration, turbocharged, charge air cooled, nos of cylinders- 6, In-line, Bore(MM) x stroke(MM) - 114x145, Compression ratio - 16.7 : 1, displacement Ltr - 8.9, Fuel - High speed Diesel, Performance class of DG Set, ISO 8528-5 G2, starting system- 24 volts DC electrical, Lub oil specification- CK4, Lub oil sump capacity , High- Low level(in Ltr) - 30- 19.7 ltr, Total lub oil system capacity - 31.7 ltr, Exhaust pipe size (in inch)- 6 , Total weight(engine + radiator) -918.2 Kg, Length x widthx height ( in MM) - 1128 x791x 1277, Mean piston speed (m/s) - 7.2 , Combution air intake @100 % load (+-5%) - 689 CFM, Exhaust temperature (*C) - 539 *C. All as approved by Project Manager / Engineer-in-Charge. |
| 3 | Alternator Specifications: Alternator suitable for continuous operation generating 320 KVA at 1500 RPM, 415 Volts, 0.8 power factor (lag) suitable for 50 Hz, 3 phase, 4 wire system, confirming to BS 5000 / IS 4722. The alternation is brushless type, screen protected, revolving field, self-excited, self-regulated through an AVR. The alternator has the following features: - - + 1.0% voltage regulation (max.) in static conditions. - IP: 23 protection with insulation class H. - Permissible overload of 10% for one hour in 12 hours of operation. |
| 4 | Note:-(i) The old unserviceable DG Set 275 KVA capacity shall be removed from the site and shall be property of the contractor, for which credit shall be deducted separately as per Schedule of credit separately. (ii)DG set will be tested on load for rated KW rating. DG Set shall be operated for a period of 12 Hrs on rated KW of DG Set\"s KW rating including one hour on 10% over load, after continuous run of 12 Hrs.(iii) The following work shall be done by the contractor and therefore, the cost shall be deemed to be included in the schedule of work:-(a)Minor civil work i.e. makingopeniing on wall for fixing exhaust pipes, fuel pipes lines, LT UG cables etc.(b) Making necessary electrical cable connectionsof incoming / outgoing LT UG cables between DGset AMF panel & Main distribution Electrical Panel outgoing LT UG cables, all as required at site and as directed. (c)Making good the all disturbed/ damaged surfaceand matching to its original finish. |
| 5 | Supplly and fixing LT UG cable with aluminium conductor, 1100 volt grade , PVC insulated, armoured, heavy duty, size of cable 300sq mm 3.5core X 2 runs, Make: Havells/L&T/ legrand. |
| 6 | Supply & fixing MCCB, 400 amps 4 pole. 415 volts, 50 Hz, Breaking capacity 45 KA, frame- HIM400 make: Havells/L&T/ Phillips. |
| 7 | PART-BSchedule of Credit |
| 8 | Unserviceable / condemned Diesel Generating set , AC, 3 Phase, 50 Hz, capacity - 275 KVA with AMF Panel. |
| 9 | Quoted Percentage (+) / (-) and Total Amount in Figures (inclusive of CP / OH and levied Taxes) |