| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. (a) Group C |
| 2 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 15/16 amp switch |
| 3 | b) 3 pin 5/6 amp socket outlet |
| 4 | c) 6 pin 15/16 amp socket outlet |
| 5 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 6 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. (a) 3 Module (100mmX75mm) |
| 7 | b) 6 Module (200mmX75mm) |
| 8 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessedPVC conduit as required. |
| 9 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 10 | 4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire |
| 11 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door |
| 12 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole |
| 13 | Supply of 15\"(380 mm)sweep 1400 rpm heavy duty Exaust Fan complete with ring, blade etc as required. ISI marked. |
| 14 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.Upto 450 mm sweep |
| 15 | SITC of wall mounted fan 400mm sweep rated voltage 220-230 AC rated frequency 50HZ speed 1280-1350 RPM with desired color |
| 16 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing &Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin),SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) 18-22 watt |
| 17 | SITC of metal clad, powder coated, compartmentalized cubical panel board as per CPWD electrical specifications including insulated aluminum bus bars, supports, interconnection, erection of switchgears with depth 30 cm to 60 cm and making provisions for termination of incoming/ outgoing cables/ bus ducting and making foundation etc as required. (Suitable for 400 Amp TP & N) |
| 18 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubical panel board including drilling holes in cubical panel, making connections etc. as required 125 A, 16kA, TPMCCB |
| 19 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 400 Amp, 50 kA, FPMCCB |
| 20 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 200 Amp, 25 kA, TPMCCB |
| 21 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm width x 50 mm depth x 1.6 mm thickness |
| 22 | Brush Less Direct Current (BLDC) Motor Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9,Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 23 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-4C*16 sqmm |
| 24 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-4C*35 sqmm |
| 25 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required(a) upto 35 sq. mm (clamped with 1 mm thick saddle) |
| 26 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surfaceas required(a) upto 35 sq. mm (clamped with 1 mm thick saddle) |
| 27 | LED Flood Light, powder coated pressure die cast aluminum(System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of Flood Light,powder coated pressure die cast aluminum body with built in or separatedriver as per the requirement with Driver efficiency >85%, Input voltage:Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 degto 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P.F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltageprotection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement deg., suitable tiltable fitting, life time (LED,Driver & electrical circuitry) of minimum 50000Burning Hours with 70% of initial Lumen maintained till life ends as perLM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K/6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation ColorMatching) <5, Maximum power consumption should not more than thespecified rating and Fixture shall be of relevant BIS standard complete inall respect i/c connections with 1.5 sq mm FRLS, PVC insulatedcopper conductor single core cable and earthing etc. as required withMinimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing requiredfor LED fixtures as per BIS shall be submitted. Shape size and CCT shall beas approved by Engineer-in-Charge as per requirement. (Thermalmanagement: heat sink of aluminum housing such that LED junctiontemperature shall not rise above 90°C).150 watts |