| 1 | Supply, installing, commissioning and testing complete of Manufacturer or OEM (Original Eqpt Manufacturer) manufactured and tested silent Diesel Engine driven generating set capable of delivering 160 KVA (128 KW), or nearest higher rating, 415 volts (AC 3 Phase, 4 wire system of supply), 50 Hz to operate at a powers factor of 0.8. The DG set shall consist of a diesel engine coupled through flexible coupling to a matching alternator and mounted on AVM pads (As per respective Mnufacturer Design ) on a common base frame all as specified complete with control panel standardised by manufacturer, fuel tank with mounting arrangement and inlet, outlet, return oil arrangement, flexible exhaust pipe as per IS 10001/10002 and alternator as per IS 13364 complete with relay panel and switch gears for automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB IV+ norms and including foundation and control cabling & power cabling with end terminal connections. The DG set shall comprise of the following: - |
| 2 | (a) Engine (Prime Mover) :Diesel engine 6 cylinders, inline, 4 stroke cycle, water cooled, gross engine power minimum of 200HP at 1500 RPM under NTP conditions of ISO 3046, or having suitable HP as recommended by manufacturer, Turbocharged, the engine shall be provided with electrical starging arrangement and give the electrical output of 160 KVA/128 KW at 0.8 power factor, 415 volts at the alternator terminal. 2 x 12 V DC 180 AH batteries,confirming to BS 5514,BS 649 and IS 10000 complete with fly wheel and all standard fittings/ fixtures as per manufacturing practice including suitable engine control panel with tachometer, lube oil temp & pressure gauges, water temp gauge, and frequency meter(digital type) (including safety shutdown contents) and also including self starter,dynamo,fuel tank etc. |
| 3 | (b)Alternator : AC alternator, self excited, self regulated, self ventilated, brushless design, conforming to BS 2613 / 5000, 3 phase , 415 volts, 4 wire rated line current 223 amps for outputPF 0.8, 1500 RPM, insulation class ‘H’ Temprature Reise H @ 125 Deg C; Enclosure IP 23confirming to IS-4722 / BS-2613 complete with AVR with + 1 % voltage regulation,directly coupled to and match the above engine with unbalancing load capacity of 25% of rated Amps. |
| 4 | (c) Anti-vibration pads for mounting engine – alternator assembly on the base frame/ plate. |
| 5 | (d) Base Frame : One no. MS Fabricated adequately machine Channel Common Base Frame with lifting facility, pre-drilled foundation holes suitable for permanent installation on concrete foundation for direct grouting or on anti-vibration mountings which will be suitable to receive the offered engine and alternator duly coupled through a flexible coupling. A suitable coupling guard shall also be provided. |
| 6 | (e) Silencer: Critical Gradeand exhaust gas piping system of suitable dia MS pipe of \"B\" class of required legth as per CPCB IV+ norms with necessary bends, supports and clamps anti vibration mounting inulated with rockwool 50 mm thick with wire mesh and aluminium clading complete all as specified. |
| 7 | (f) Fuel tank of capacity min 250L or as specified by the manufacturer, made of 14 SWG CRCA MS sheet, duly powder coated and provided with float, gauge and fuel float switch. |
| 8 | (g) Emission limit & smoke limit for DG set shall be as per CPCB IV norms applicable at the time of bidding. |
| 9 | NOTE:- 1) Anything missed out in the technical specifications but technically required for efficient working of DG Set is deemed to be included in the quoted rates.2) The quoted rate shall be deemed to be inclusive of first fill of engine oil & final successful acceptance test.3) The quoted rate shall be deemed to be inclusive of 12 Hrs test run at site as specified in the PS in presence of rep of Accepting Officer; all testing arrangements / equipment’s, resistive load including POL shall be made available by the contractor.are to be included.4) The quoted rate shall be deemed to be inclusive of the PCC foundation required for placing the DG set and it should be as per the manufacturers recommendation.DG Set should comply CPCB IV+ or Latest CPCB norms applicable at the time of bidding.5) The Location of Installation is situated in highly secured area and there is space constraint also for loading/unloading of the DG set, requiring crane or other heavy machinery during installation. So contractor are advised to visit the site before quating the rate. No additional Charges will be paid for the loading/unloading. |
| 10 | AMF PanelFabricating, Installing, Testing & Commissioning of automatic mains failure control including auto by-pass panel, suitable for 160 kVA silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyzer to indicate currents, phase and line voltages, frequency, power factor, KWH, KVARHprovision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF panel to diesel engine and elsewhere if required all connection at site to make it fully functional, complete and inter locking including for following:AMF panel should have provision for cable upto 3.5C x 240 sqmm size for main incoming supply & outgoing supply. AMF panel will be outside the DG set fabricated & installed separately as directed by Engineer-in-Charge. directedOutgoing supply MCCB 400 Amps. 4 PoleAuto/ Manual/ Test/ Off selector switch |
| 11 | (a) 2 Nos over voltage relay, 2 Nos reverse power relay and 2 Nos under voltage relay. |
| 12 | (b) 3 Sets of current transformers 15P 10 accuracy for protection and 15 VA class-I for metering |
| 13 | (c) Energy analyzer unit to indicate current voltage frequency power factor and KWH |
| 14 | (d) Indicating lamps for load on mains and load on set |
| 15 | (e) Fuse for instruments |
| 16 | (f) Battery charger, complete with transformer/ rectifier, D.C voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment |
| 17 | (g) Main supply failure monitor |
| 18 | (h) Supply failure timer |
| 19 | (i) Restoration timer |
| 20 | (j) Control unit with three impulse automatic engine start/ stop and failure to starty lockout |
| 21 | (l) Impulse counter with locking and reset facility |
| 22 | (i) Audio/ Video annunciation for |
| 23 | (ii) High water temperature |
| 24 | (iii) Low lubricating oil pressure |
| 25 | (iv) Engine over speed |
| 26 | (v) Engine fails to start |
| 27 | (vi) Full load/ maximum load warming |
| 28 | M&L for earthing complete with galvanised steel earth plate electrodesize 600 x 600 x 6 mm thick, burried directly in ground, (Earth pit not less than 3.0 m deep below ground level) with top edge of the plate not less than 2.25 m below ground level connected to galvanised iron strip 32 x 6 mm as earthing lead wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including testing on completion, surrounded from all sides by mixture of charcoal and common salt, Providing 40 mm bore protection pipe for GI strip,GI pipe light grade 20mm dia bore for watering includingfunnel with wire mesh on top, CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 3 connected to earthing test point all as specified. |
| 29 | Notes for earthing :1. The unit rate includes for protection pipe and GI strip dia from top of earth plate upto 7.5 meter above ground level. 2. The unit rate includes for protection GI pipe of 40 mm and watering pipeof 20 mm bore including excavation for earth pit in any type of soil/ disintegrate rock.3.The cost ofGI strip of size 32 x 6 mm from top of earth plate upto 7.5 meter above ground level is deemed to be included in the unit rate of item and earth strip beyond 7.5 RM will be measured and paid seperately under relevant item 4. All the joints in GI strip and connection with Earth Plate to be weldedand in addition by providing double brass nut bolt and washer.5. Cost ofwelding and nut bolts are deemed to be included in the unit rate.6.Before leaving the site all excavated soil etc to disposed off and to make the site clean bythe contractor without any extra cost. |
| 30 | M&L in replacment earth continuity conductor or main earthing lead fixed to wall on batten or reccess or chases or burid in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing as required 32x6 mm galvanised iron strip all as specified. |
| 31 | Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade,XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cables, heavy duty with aluminium conductor of cross sectional area 185 sqmm 3.5 core with all fixing & connecting accessories complete as specified and as directed. |
| 32 | S & F Cable jointing kit for 1100 voltcomplete with jointing material andaccessories suitable for 3.5/4 core XLPE armoured aluminium conductor cable of size upto 185 sqmm complete all as specified and as directed by Engineer-in-Charge. |
| 33 | Excavation in trenches n.exc 1.5m wide andn.exc1.5 mtr in depth and getting out in soft/loose soil all as specified and directed by Engineer-in-charge. |
| 34 | Returning and filling including spreading, leveling, watering and well ramming in layer n.exc 25 cm thick in soft/loose soil all as specified and directed by Engineer-in-charge. |
| 35 | Removing excavated material to a distance not exc. 50 mtrs and deposting where directed at a level not exceeding 1.50mm above the starting point all as specified and directed by Engineer-in-charge. |
| 36 | S & F GI tubing light grade 100 mm bore for protection of LT UG cable laid in trenches/walls/ceiling etc and for protection of connection wire from junction box to light fittings, ( Note : Necessary clamps, nuts, bolts etc deemed to be included) |
| 37 | Supply and laying natural river sand as cushioning of cables, including spreading and punning down all as per clause No 3.21 of SSR part -I complete all as specified and directed by Engineer-in-charge and directed by Engineer in chargeNote : punned thickness will only be measured for payment purpose. |
| 38 | M&L for sub class \"B\" brick for protection of UG cable in tranches of old size brick all as specified and directed by Engineer-in-charge. |
| 39 | Supply and fixwire meshed(Cablofil) Hot Dip Galvanized tray 54mm(h)x100mm(w) complete with nuts bolts washers (GI) and all accessories for mounting and supporting the cable tray system, along with vertical bends,bends. Including taking down and re fixing any type of electric cable, LAN /signal cable ,if require through and including wall cutting and making to good surface in disturbed area complete all as specified and as directed by Engineer-in-Charge. Make :- Legrand(000073),Panduit,Commscope |
| 40 | Supply & fix Hot Dip Galvanized Cover for covering cables on cable tray width100 mm along with clips and other fixing arrangement complete all as specified and as directed by Engineer-in-Charge. Make -Legrand(CM646020),Panduit,Commscope |
| 41 | Making/boring hole under road/pavement/hard standing with help of Bookies suitable for passing pipe (any type) up to 150 mm Dia not less than one mtr below ground level including required earth work |
| 42 | M&L complete removal of existing treatment and applying three coats of white wash on old wall surface or undecorated plastered surfaces complete all as specified and directed.(3.6+9.4+7.5+6.7*2) |
| 43 | M&L complete removal of existing treatment and appplying two coats of weather coat(Exterior emulsion)) over a coat of damp shealth primer by smart painting method toold plastered walls as per manufacturer instrcution including properly fillings the crackscomplete all as specified and directed. |
| 44 | Dismantling of Stone slabs and tiles of any description or thickness in floors, aprons etc laid, bedded and pointed in any mortar complete all as specified and directed. |
| 45 | M & L Machine cut pre polished kota stone slab/tiles flooring 20-25mm thick in any size over cement screed base laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing over and incl 15mm thick screed bed in cement mortar 1:4 complete in all respect as specified.(1027.4+223.47) |
| 46 | M & L Machine cut pre polished kota stone slab/tlies 20-25mm thick in riser of steps, skirting, dado and pillar laid over cement screed and jointed over and incl 10mm thick screed bed in cement mortar 1:4 complete in all respect as specified.(1064.3+204.8) |