| 1 | Supplying, Installation, Testing and Commissioning of 12 Mtrs high raising lowering type mast shaft shall be in two Sections, hot dip galvanized inside & outside in single dip, suitable for wind velocity as per IS 875 part 3. It shall also include accessories for high mast including head frame , 3 point suspension system with steel wire rope 6 mm dia, double drum winch, Galvanized Lantern carriage arrangement suitable for up to 6 Luminaries symmetrically & its control gear boxes and lighting Finial. Supply of Foundation bolts manufactured from steel along with nuts, washers, anchor plates & templates. With internal Power tools.(Bottom Dia. 310 mm Top Dia. 125mm) |
| 2 | Earth work in excavation by mechanical means ( Hydraulic excav-ator) / manual means over areas ( exceeding 30 cm in depth. 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5 m, disposed earth to be leveled and neatly dressed. All Kinds of soil. |
| 3 | Providing & laying in position cement concrete of 1:4:8 grade ( 1 Cement :4 coarse sand : 8 graded stone aggregate 40 mm nominal size) excluding the cost of centering and shuttering - All work up to plinth level. |
| 4 | Providing and laying in position 1:1.5:3 grade ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level. |
| 5 | Steel reinforcement for R.C.C work i/c straightening, cutting, bending, placing in position and binding all complete upto plinth level.(Thermo-Mechanically Treated bars.) |
| 6 | Cantering & shuttering i/c strutting, propping etc. and removal of form work for : Foundations & footings. |
| 7 | S.I.T.C of feeder pillar (for High Masts), outdoor type, dust and vermin proof made out of 2 mm thick CRCA sheet of nominal size 900 mm x 750 mm X350/400 mm deep, front and back openable- hinged type door, duly eposy based pwder coated (from inside and outside), 4 strip 100 Amp capacity PVC Insulated aluminium Bus bar, provision of 4 pole terminal block for incoming and outgoing cablesand fixed on M S angle iron frame work of size 50 mmx 50 mmx 6 mm length with 4 nos. 800 mm long legs duly welded to the frame structure and out of which 400 mm will be grouted in 1:2: 4 cement concrete foundationi/c supply and fixing of following accessores, connection and interconnection, inter locking wiring, thimbling, numbering-ferrules up & lowering system, earthing stud etc. complete as reqd.(I)Main incomer 415 V, 63 Amp 4 Pole, 26 KA MCCB : 1 No. (II) 32 AmpDP , MCB C-Series: 02 Nos , (II)32 AmpTP & N , MCB C-Series: 03 Nos (vi) Indicating lights-03 Nos (3 Nos for Incoming power supply) |
| 8 | Supply, installation, testing and commissioning of 01 luminaries having wattage of 200 W each (Variation of more than +/- 5% would not be allowed) having minimum system efficacy of 110 lumen/watt outdoor type LED Flood Light Luminaire of IP 66, Accuracy Class-I, is 10122 and above having suitable pressure die cast housing/heat sink, driver, optics for operation in 230 Volts A.C, PF not less than 0.90, CRI≥70, internal $ external surge protection, colour temperature 6500 K, suitable with beam angle to meet desired aluminium level as per required technical specification & suitable for mounting on the exiting pole bracket including drilling of holes,i/c providing and fixingsuitable size of GI flexible pipe with accessories form top slot of pole to fittingconnections, interconnections etc as per specification complete as required. |
| 9 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories,and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required |
| 10 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required |
| 11 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 12 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required (a) 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 13 | Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE armoured power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required (a) 3.5 x35 sq. mm |
| 14 | Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE armoured power cable of 1.1 KV grade of following size in the existing masonry open duct as required (a) 3.5 x35 sq. mm |
| 15 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required (a) 3½ X 35 sq. mm (35mm) |