| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 14-01-2026 | Corrigendum No. 01 | BOQ | 31-01-2026 |
| Sl. No. | Item Description |
| 1 | Sch A Part-I:- (Repair/ Maint of IRP, sewage installation and allied works of PH-I and PH-II area under GE Panagarh)[Quantity of same nature of works pertains to Sch A Part-I, II & III are clubbed up with relevant items of here-in-after of tender in respect of location of work. Bidders are requested to quote the rate considering the above aspect] |
| 2 | Excavation in trenches n exc 1.5 m wide & n exc1.5 mtr deep in soft/lose soil for taking out pipe & laying of pipe & getting outfor diverting of CI pipeline complete all as specified and directed.[Note : Total Qty : 27.00 (Part-I) + 164.00 (Part-II) + 133.00 (Part-III) = 324.00] |
| 3 | Returning, filling in, including spreading, leveling, watering & well ramming in layersn. exc 25 cm thick complete all as specified and directed.[Note : Total Qty : 23.00 (Part-I) + 140.00 (Part-II) + 112.00 (Part-III) = 275.00 |
| 4 | Removal of excavated soil to a distance not exc 50 m and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.[Note : Total Qty : 4.00 (Part-I) + 24.00 (Part-II) + 20.00 (Part-III) = 48.00] |
| 5 | Taking up CI/DI water main (incl all fitting) with spigot & socket ends and lead joints incl burning out & recovering lead frompipe of 100 mm bore for relaying / rerouting of serviceable pipe after cleaning complete all as specified and directed.[Note : Total Qty : 42.00 (Part-I) + 80.00 (Part-II) + 80.00 (Part-III) = 202.00] |
| 6 | Taking up CI/DI water main (incl all fitting) with spigot & socket ends and lead joints incl burning out & recovering lead frompipe of 150 mm bore for relaying / rerouting of serviceable pipe after cleaning complete all as specified and directed.[Note : Total Qty : 24.00 (Part-I) +140.00 (Part-II) + 120.00 (Part-III) = 284.00] |
| 7 | Relaying of DI/CI/GI pipe 100 mm bore in trenches/ over the masonry pillars after cleaning thoroughly including fittings complete all as specified and directed.[Note : Total Qty : 30.00 (Part-I) + 30.00 (Part-II) + 30.00 (Part-III) = 90.0] |
| 8 | Relaying of DI/CI/GI pipe 150mm bore in trenches/ over the masonry pillars after cleaning thoroughly including fittings complete all as specified and directed.[Note : Total Qty : 12.00 (Part-I) + 40.00 (Part-II) + 40.00 (Part-III) = 92.00] |
| 9 | M&L DI pipe of 100 mm bore with spigot and socket end rubber gas cate joint(titon) centrifugally cast class k-7 conforming to IS 8329-2000 laid in trenches/ on surface/ over masonry pillar and connection to old or new position complete all as specified and directed.[Note : Total Qty : 12.00 (Part-I) + 50.00 (Part-II) + 50.00 (Part-III) = 112.00] |
| 10 | M&L DI pipe of 150 mm bore with spigot and socket end rubber gas cate joint(titon) centrifugally cast class k-7 conforming to IS 8329-2000 laid in trenches/ on surface/ over masonry pillar and connection to old or new position complete all as specified and directed.[Note : Total Qty : 12.00 (Part-I) + 100.00 (Part-II) + 80.00 (Part-III) = 192.00] |
| 11 | Taking up or down 80 mm bore steel tubing and connection including cleaning for relaying or removal to store from trenches/wall surfaces complete all as specified and directed.[Note : Total Qty : 28.00 (Part-I) + 46.00 (Part-II) + 46.00 (Part-III) = 120.00] |
| 12 | Taking up or down 50 mm bore steel tubing and connection including cleaning for relaying or removal to store from trenches/wall surfaces complete all as specified and directed.[Note : Total Qty : 38.00 (Part-I) + 136.00 (Part-II) + 116.00 (Part-III) = 290.00] |
| 13 | Taking up or down 25 mm bore steel tubing and connection including cleaning for relaying or removal to store from trenches/wall surfaces complete all as specified and directed.[Note : Total Qty : 38.00 (Part-I) + 380.00 (Part-II) + 180.00 (Part-III) = 598.00] |
| 14 | Taking up or down 20 mm bore steel tubing and connection including cleaning for relaying or removal to store from trenches/wall surfaces complete all as specified and directed.[Note : Total Qty : 38.00 (Part-I) + 350.00 (Part-II) + 130.00 (Part-III) = 518.00] |
| 15 | Relaying/re-fixingold 80 mm bore GI tubing or in floor/pillar/wall in new or old position complete all as specified and directed.[Note : Total Qty : 10.00 (Part-I) + 10.00 (Part-II) + 10.00 (Part-III) = 30.00] |
| 16 | Relaying/re-fixingold 50 mm bore GI tubing or in floor/pillar/wall in new or old position complete all as specified and directed.[Note : Total Qty : 20.00 (part-I) + 36.00 (Part-II) + 36.00 (Part-III) = 92.00] |
| 17 | Relaying/re-fixingold 25 mm bore GI tubing or in floor/pillar/wall in new or old position complete all as specified and directed.[Note : Total Qty : 20.00 (Part-I) + 80.00 (Part-II) + 80.00 (Part-III) = 180.00] |
| 18 | Relaying/re-fixingold 20 mm bore GI tubing or in floor/pillar/wall in new or old position complete all as specified and directed.[Note : Total Qty : 20.00 (Part-I) + 50.00 (Part-II) + 50.00 (Part-III) = 120.00] |
| 19 | M&L 80 mm bore GI Tubing medium grade in Trenches/ Floor/Pillar andconnectionin old or news position including fittinglike socket/Union/Tee/Reducer Nipple etc complete all as specified and directed and required will be supplied by Contractor rate for the same is included in the item rate quoted.[Note : Total Qty : 18.00 (Part-I) + 36.00 (Part-II) + 36.00 (Part-III) = 90.00] |
| 20 | M&L 50 mm bore GI Tubing medium grade in Trenches/ Floor/Pillar andconnectionin old or news position including fittinglike socket/Union/Tee/Reducer Nipple etc complete all as specified and directed and required will be supplied by Contractor rate for the same is included in the item rate quoted.[Note : Total Qty : 18.00 (Part-I) + 100.00 (Part-II) + 80.00 (Part-III) = 198.00] |
| 21 | M&L 25 mm bore GI Tubing medium grade in Trenches/ Floor/Pillar andconnectionin old or news position including fittinglike socket/Union/Tee/Reducer Nipple etc complete all as specified and directed and required will be supplied by Contractor rate for the same is included in the item rate quoted.[Note : Total Qty : 18.00 (Part-I) + 300.00 (Part-II) + 100.00 (Part-III) = 418.00] |
| 22 | M&L 20 mm bore GI Tubing medium grade in Trenches/ Floor/Pillar andconnectionin old or news position including fittinglike socket/Union/Tee/Reducer Nipple etc complete all as specified and directed and required will be supplied by Contractor rate for the same is included in the item rate quoted.[Note : Total Qty : 18.00 (Part-I) + 300.00 (Part-II) + 80.00 (Part-III) = 398.00] |
| 23 | Supply and laying of UPVCpipes 20.mm outer dia, UV stabilized and having thermal stability for hot & cold water supply all fittings laid in trenches / wall including all fittings complete including taking out old unservicable pipe all as specified and directed.[Note : Total Qty : 6.00 (Part-I) + 30.00 (Part-II) + 30.00 (Part-III) = 66.00] |
| 24 | Supply and laying of UPVCpipes 25 mm outer dia, UV stabilized and having thermal stability for hot & cold water supply all fittings laid in trenches / wall including all fittings complete including taking out old unservicable pipe all as specified and directed.[Note : Total Qty : 6.00 (Part-I) + 30.00 (Part-II) + 30.00 (Part-III) = 66.00] |
| 25 | S&FUPVC fittings i.e Tee ,elbow , socket,union,reducer,tank nippleetc any size any type upto 40mm suitable for fixing with existing or new pipe line complete all as specified and directed.[Note : Total Qty : 5.00 (Part-I) + 30.00 (Part-II) + 30.00 (Part-III) = 65.00] |
| 26 | Supply ans fix PVC ball valve suitable for UPVC pipe line any type any size upto 40mm complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) + 10.00 (Part-II) + 10.00 (Part-III) = 22.00] |
| 27 | M&L DI bend any type, radius and angles, tappers and type (straight, bend, increasing, decreasing, or double socket etc. Tee pipes single branch Y junction, double branch cross (all socket, socket and Spigot or flanged ends) collors, caps and plugs for the Pipes socket and Spigot.All socket and flanged upto bore of 250 mm complete all as specified and directed.[Note : Total Qty : 40.00 (Part-I) + 60.00 (Part-II) + 60.00 (Part-III) = 160.00] |
| 28 | S & F in repairs 100 mm bore Sluice valve PN – 1.6 IS 14846-2000 with Spindle Iron (Heavy duty) Wheel head and both ends flanged and MS nut bolts and washers and pair of rubber/fiber gasket and fixed in position complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 29 | S & F in repairs 150 mm bore Sluice valve PN – 1.6 IS 14846-2000 with Spindle Iron (Heavy duty) Wheel head and both ends flanged and MS nut bolts and washers and pair of rubber/fiber gasket and fixed in position complete all as specified and directed.[Note : Total Qty : 1.0 (Part-I) + 5.00 (Part-II) + 5.00 (Part-III) = 11.00] |
| 30 | S & F in repairs 100 mm bore cast iron Non Return Sluice Valve heavy duty with flanged ends, brass spindle any pattern with Brass spindle with GM Check Nut confirming to IS including jointing and jointing material, nuts, bolts, and washer etc complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 1.00 (Part-II) + 1.00 (Part-III) = 3.00] |
| 31 | S & F in repairs 150 mm bore cast iron Non Return Sluice Valve heavy duty with flanged ends, brass spindle any pattern with Brass spindle with GM Check Nut confirming to IS including jointing and jointing material, nuts, bolts, and washer etc complete all as specified and directed.[Note : Total Qty :1.00 (Part-I) + 1.00 (Part-II) + 1.00 (Part-III) = 3.00] |
| 32 | S & F in repairs of Butter flyvalve 150mmbore confirming to IS-5312 Part-I, pressure rating PN1.6, Flange drilling as per IS-1538, CI valve body diaphragm, CI disc, Disc face ring -rubber, Aluminium hinge pin, CI hinge and bornze body ring complete including taking out existing UNSV valve complete all as specified and directed.[Note : Total Qty :14.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 18.00] |
| 33 | Refixing of Sluice valve from 150 mm to 250 bore after taking out and repair/refacing of valve spindle,re grinding if required , including taking part and replacement of unserviceable parts,glant packing and reassembling as per existing size to make it leak proofand complete descaling and proper functioning at site including replacement of new nuts, bolts, washers and gasket as required at site, reassembling, testing and re-fixing complete all as specified and directed.[Note : Total Qty :3.00 (Part-I) + 5.00 (Part-II) + 5.00 (Part-III) = 13.00] |
| 34 | Refixing of Sluice valve from 100 mm bore after taking out and repair/refacing of valve spindle,re grinding if required , including taking part and replacement of unserviceable parts,glant packing and reassembling as per existing size to make it leak proofand complete descaling and proper functioning at site including replacement of new nuts, bolts, washers and gasket as required at site, reassembling, testing and re-fixing complete all as specified and directed.[Note : Total Qty : 3.00 (Part-I) +5.00 (Part-II) + 5.00 (Part-III) = 13.00] |
| 35 | M&L 50 mm bore gate valve gum metal class-II screwed down high pressure with clutch handle screwed both ends for Iron pipe including taking out of old unserviceable gate valve complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 5.00 (Part-II) + 5.00 (Part-III) = 11.00] |
| 36 | M&L 25 mm bore gate valve gum metal class-II screwed down high pressure with clutch handle screwed both ends for Iron pipe including taking out of old unserviceable gate valve complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) +10.00 (Part-II) + 10.00 (Part-III) = 22.00] |
| 37 | M&L 20 mm bore gate valve gum metal class-II screwed down high pressure with clutch handle screwed both ends for Iron pipe including taking out of old unserviceable gate valve complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) +5.00 (Part-II) + 5.00 (Part-III) = 12.00] |
| 38 | M&Linrepair/rectification of leakage in existingrising/delivery/mainCI/DI Pipe Spigot/ socketed end of size upto 100 mm bore including necessary earth work (i.e. excavation, removal & refilling,of trench), Pumping out water from the ditch and rectify the defects by taking out of existing lead and rejoining the same by using necessary additional lead, Lead Wool, Spun Yarn,tyton joint ,mechanical jointetc including testing, commissioning of CI Pipeline complete all as specified and directed.[Note : (i) Total Qty : 2.00 (Part-I) + 4.00 (Part-II) + 6.00 (Part-III) = 12.00](ii) All materials required for rectification of said defects is included in the cost of item complete] |
| 39 | M&Linrepair/rectification of leakage in existingrising/delivery/mainCI/DI Pipe Spigot/ socketed end of size upto 150 mm to 250 mm bore including necessary earth work (i.e. excavation, removal & refilling,of trench), Pumping out water from the ditch and rectify the defects by taking out of existing lead and rejoining the same by using necessary additional lead, Lead Wool, Spun Yarn,tyton joint ,mechanical jointetc including testing, commissioning of CI Pipeline complete all as specified and directed.[Note : (i) Total Qty : 2.00 (Part-I) + 4.00 (Part-II) + 6.00 (Part-III) = 12.00](ii) All materials required for rectification of said defects is included in the cost of item complete] |
| 40 | M&L in repair/rectification in existing rising/ delivery CI/GI pipe line flanged end type of 100 mm bore incl necessory earth work (i.e. excavation, rubber sheet nut & bolts etc and other arrangement for rectification of said deffects is included in the cost of item completeRemoval and refilling of trenches). Pumping out water from the ditch and rectify the defects by taking out of existing rubber gasket / fibre sheet, nut & bolt etc and rejoining the same by using new one incl testing, commissioning of CI pipe line complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) +4.00 (Part-II) + 6.00 (Part-III) = 12.00] |
| 41 | M&L in repair/rectification in existing rising/ delivery CI/GI pipe line flanged end type of 150 mm to 250 mm bore incl necessory earth work (i.e. excavation, rubber sheet nut & bolts etc and other arrangement for rectification of said deffects is included in the cost of item completeRemoval and refilling of trenches). Pumping out water from the ditch and rectify the defects by taking out of existing rubber gasket / fibre sheet, nut & bolt etc and rejoining the same by using new one incl testing, commissioning of CI pipe line complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) + 4.00 (Part-II) + 6.00 (Part-III) = 12.00] |
| 42 | M&Linrepair/rectification of leakage in existingGI/PVC line any size upto 80mmincluding necessary earth work (i.e. excavation, removal & refillingof trench,) if required, Pumping out water from the ditch and rectify the defects by taking out of existing GI/PVC pipe and rejoining the same by using necessary additional fittings,etc including testing of pipeline complete all as specified and directed.[Note : (i) Total Qty : 4.00 (Part-I) + 10.00 (Part-II) + 10.00 (Part-III) = 24.00](ii) All materials required for rectification of said defects is included in the cost of item complete] |
| 43 | S&F for straight plain brass ferrules (or connecting screws) screwedbolt ends of 20 mm bore Pipe complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 44 | S&F for straight plain brass ferrules (or connecting screws) screwedbolt ends of 25 mm bore Pipe complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 45 | M&L Plain Cement Concrete (1:4:8) type D2 (using 40 mm graded stone aggregate) as in foundation of pillar, complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) +2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 46 | M&L Plain Cement Concrete (1:2:4) type B-0 (using 12.5 mm graded stone aggregate) as in coping on brick machinery on of of pillar and like complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 47 | M&L Brickworkwith fly ash bricks straight or curved on plan exc 6 m mean radius in cement mortar (1:6) as brick pillar for hoisting of CI pipe line complete all as specified and directed.[Note : Total Qty : 3.00 (Part-I) +2.00 (Part-II) + 2.00 (Part-III) = 7.00] |
| 48 | Cleaning of existing valve pit chamber from inside after cleaning around valve pit area ,dewatering, painting of existing valvepit chamber external surface , painting ofvalve, pipe in chamberof any size ,painting of angle , hinges ,locking arrangement , cover sheet of required size and existingall as specified and directed.[Note : Total Qty : 4.00 (Part-I) + 7.00 (Part-II) + 7.00 (Part-III) = 18.00] |
| 49 | Repair to valve pit chamber any sizewith bricks works, Plain Cement Concrete works,plasteing of internal and external surfaces making it leak proof wherever required including replacement of iron frame ,hinges , locking arrangement ,painting ofiron frame ,painting of external plaster surfaceas per site requirement complete all as specified and directed.[Note : Total Qty : 4.00 (Part-I) +7.00 (Part-II) + 7.00 (Part-III) = 18.00] |
| 50 | M&L brick massonary valve pit with brickin Cement Mortar (1:6) with 100mm thickPlain Cement Concrete work 1:3:6 type C2 from fundation over 75mm thick hard core, sub class B brick full brick thick wall, 15mm thick internal and external plaster at bottom of the pit of size 600x600x600 mm along with valve pit cover made out MS angle iron 50mm x 50mm x 6mm frame work, , MS platecover made out of 3.15mm thick with locking arrangment fixed over the valve pit including a coat of synthetic enamel paintcomplete including necessary frame work welding, drilling etc complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) + 4.00 (Part-II) + 4.00 (Part-III) = 10.00] |
| 51 | M&L brick massonary valve pit with brickin Cement Mortar (1:6) with 100mm thickPlain Cement Concrete work 1:3:6 type C2 from fundation over 75mm thick hard core, sub class B brick full brick thick wall, 15mm thick internal and external plaster at bottom of the pit of size 900x900x900 mm along with valve pit cover made out MS angle iron 50mm x 50mm x 6mm frame work, , MS platecover made out of 3.15mm thick with locking arrangment fixed over the valve pit including a coat of synthetic enamel paint over a coat of red oxide primer complete including necessary frame work welding, drilling etc complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) + 4.00 (Part-II) + 4.00 (Part-III) = 10.00] |
| 52 | M&L brick massonary valve pit with brickin Cement Mortar (1:6) with 100mm thickPlain Cement Concrete work 1:3:6 type C2 from fundation over 75mm thick hard core, sub class B brick full brick thick wall, 15mm thick internal and external plaster at bottom of the pit of size 1200x1200x900 mm along with valve pit cover made out MS angle iron 50mm x 50mm x 6mm frame work, , MS platecover made out of 3.15mm thick with locking arrangment fixed over the valve pit including a coat of synthetic enamel paint over a coat of red oxide primer complete including necessary frame work welding, drilling etc complete all as specified and directed.[Note : Total Qty : 5.00 (Part-I) + 6.00 (Part-II) + 4.00 (Part-III) = 15.00] |
| 53 | Painting of water supply pipe line of any size and existing colour inside pump houses/E/M Installations complete all as specified and directed.[Note : Total Qty : 20.00 (Part-I) + 50.00 (Part-II) + 50.00 (Part-III) = 120.00] |
| 54 | S&F 3.15mm thick mild steel plain black sheet for earth, covering to door shutters, and covering to valve pit frame cut size edges beaded as directed , holes punched, including rounded head serews with plain 40mm lap, joints or welded/ reveted seams including bending, turning up mitred angle, stopped ends, outlets as required complete all as specified and directed.[Note : Total Qty : 16.00 (Part-I) + 16.00 (Part-II) + 16.00 (Part-III) = 48.00] |
| 55 | M&L Cutting wild growth i.e. grass, shurbs, bushes etc.from ground level by using grass cutting Machine or manuallyin the Periphery of pump houses/STPs/OH tank /Valve area including removing grass from fences removing the cut materials to out side the Pump house area and depositing where directed, complete all as specified and directed.[Note: (i) Total Qty : 100.00 (Part-I) + 200.00 (Part-II) + 200.00 (Part-III) = 500.00](ii) T&P and cutting tool are inclusive of above quoted rate] |
| 56 | Repair to existing contactor for pump houses/STP control panel as per existing size with replacement of minor unsv parts complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00][Equipment make to be repaired: L&T, ABB, Legrand, Havells] |
| 57 | Repair toexisting pump motor starter for pump houses/STP any type and any size at proper site itself with replacement of minor unsv parts complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00][Equipment make to be repaired: L&T, ABB,Legrand,Havells] |
| 58 | M&L Submersible pump Fully Automatic Star delta Starter In sheet Enclosure Typerating AC-3,Duty 415v, 50 Hz 3 Phase upto 35 HP,Relay range of 30-40 A as per existing model after taking out old unserviceable one complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 1.00 (Part-II) + 1.00 (Part-III) = 3.00][Equipment make to be repaired: L&T, ABB,Legrand,Havells] |
| 59 | M & Lfor Fully Automatic Star delta Starter In sheet Enclosure Type MNMotor rating AC-3,Duty 415v, 50 Hz 3 Phase upto 50 HP,Relay range of 30-50 A as per existing model after taking out old unserviceable one complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 1.00 (Part-II) + 1.00 (Part-III) = 3.00][Equipment make to be repaired: L&T, ABB,Legrand,Havells] |
| 60 | M & L for 3/4 Pole Power Contactor type MNX, AC 3 any amps as per existing model after taking old unserviceable one complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 6.00][Equipment make to be repaired: L&T, ABB,Legrand,Havells] |
| 61 | M & L for Over Load Relay Direct Mounting Relay range of 30-50A as per existing modelafter taking old unserviceable one complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00][Equipment make to be repaired: L&T, ABB,Legrand,Havells] |
| 62 | S&F of rotational moulded polyethylene water storage tank capacity of 500 Ltrs. (Cylindrical, vertical with closed top with double layer conf to IS-12701-96 complete including provision of all inlet,outlet,overflow and drain pipe fitting complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) + 20.00 (Part-II) + 10.00 (Part-III) = 32.00] |
| 63 | S&F of rotational moulded polyethylene water storage tank capacity of 1000 Ltrs. (Cylindrical, vertical with closed top with double layer conf to IS-12701-96 complete including provision of all inlet,outlet,overflow and drain pipe fitting complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) + 6.00 (Part-II) + 6.00 (Part-III) = 14.00] |
| 64 | S&F ofhigh pressure PTMT ball float valve suitable for size of 25 mm dia with epoxycoatedaluminum rod& HD plastic ball screwed for iron pipe including GI/PVC Fitting as reqd after taking out old unserviceable one complete all as specified and directed.[Note : Total Qty : 4.00 (Part-I) + 15.00 (Part-II) + 15.00 (Part-III) = 34.00] |
| 65 | S&F ofhigh pressure PTMT ball float valve suitable for size of 20 mm dia with epoxycoatedaluminum rod& HD plastic ball screwed for iron pipe including GI/PVC Fitting as reqd after taking out old unserviceable one complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) + 8.00 (Part-II) + 8.00 (Part-III) = 18.00] |
| 66 | Cleaningoverhead building servicewater tank (capacity of upto -5000 ltrs ) by high pressure and disinfections by ultraviolet radations and disposal of sludge at safe place. Rate also includes all labour, materials, equipment, plants and mechinery etc complete in all respect. Total process of the cleaning comprises of following steps.(i)Cleaning of initial sludge and sedimentation etc and disposal of sludge insludge tank carefully.(ii)Total high pressure cleanig with machines using s high pressure cleaning for total removal of scaling, dirt and algae etc from the walls, pillars and flooring to thoroughly expose the original concrete wall/surface.(iii)Removal of sludge by labours.(iv)Sterilisation of all walls, flooring and pillar byanti bacterial agents for reductions of microbiological impurities.[Note :- (i)Total Qty : 450.00 (Parrt-I) + 700.00 (Part-II) + 700.00 (Part-III) = 1850.00](ii) Rate are deemed for writing work i.e. tank clean on(date), (month) and (year), font size should be 60 cms.(iii)Any damages of float valves and tanks due to negligence of work will be rectified by the contactor is own cost.] |
| 67 | Lifting of submersible pump set of any type and capacity alongwith column pipe and 3 core flat cable complete after disconnecting of all elect and water line connection for any make of pump & motor, complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 5.00 (Part-II) + 8.00 (Part-III) = 14.00][Equipment make to be repaired: Kirlosker,KSP,CG,WPIL] |
| 68 | Dismantling and taking out motor (20 to 40 HP) burnout motor winding from the stator of motor and rewinding with existing gauge PVC copper cable insulation material incl cleaing of slots, insulating papers etc.complete all as specified and directed.[Note: (i) Rewinding will be paid separately (ii) Total Qty : 1.00 (Part-I) + 5.00 (Part-II) + 8.00 (Part-III) = 14.00][Equipment make to be repaired: KSB, Kirlosker,CG, WPIL] |
| 69 | Lowering the submersible pump set alongwith cable,column pipe and other connected accessories incl moter and pump assemblled with cuppler and after lowering pump set elect connection with starter testing & commissioning complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 5.00 (Part-II) + 8.00 (Part-III) = 14.00][Equipment make to be repaired: KSB, Kirlosker,CG, WPIL] |
| 70 | Supply and laying in repair flexible flat PVC insulated PVC sheathed copper couductor stranded submersible cable cores 1100 volt grade 10 Sqmm 3 core including jointing material and connection work complete all as specified and directed.[Note : Total Qty : 50.00 (Part-I) + 50.00 (Part-II) + 50.00 (Part-III) = 150.00] |
| 71 | S & F in repairs round strand steel wire rope dia 12 mm and connected clamp nut bolts fixed complete all as specified and directed.[Note : Total Qty : 50.00 (Part-I) + 40.00 (Part-II) + 50.00 (Part-III) = 140.00] |
| 72 | M&L digital voltmeter 0-500V capacity as per existing after taking out old unserviceable one complete all as specified and directed. [Note : Total Qty : 2.00 (Part-I) + 4.00 (Part-II) + 4.00 (Part-III) = 10.00] |
| 73 | M&L digital Ampmeter 96x96 size digital with CT ratio of 0-200 Amp as per existing after taking old unserviceable one complete all as specified and directed. [Note : Total Qty : 2.00 (Part-I) + 4.00 (Part-II) + 4.00 (Part-III) = 10.00] |
| 74 | Rewiring of Pump Starting Panel incl all accessories to rectify panel connections using PVC insulated FRLSH (IS : 659) stranded copper wire as per required, complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 6.00] |
| 75 | Taking out chlorine Dozing machine, dismantling the dozing plant, cleaning, disconnecting electric connection of all Job parts taking out all defective parts and S&Fnew parts for replacement (New parts will be measured and paid separately )reassembling, testing and re-fixing with replacement of PVC pipeand gasket upto required at site complete all as specified and directed.[Note : (i) Total Qty : 3.00 (Part-I) + 6.00 (Part-II) + 12.00 (Part-III) = 21.00(ii) New spare parts for Decrin Dozning Pump will be measured and paid separately under item No 1.075 to 1.086(iii) New spare parts for Satya sai Make Chemical Chlorine Dozing paid separately under item No 1.087 to 1.097(iv) Make of Chlorine dozing machine/Pump:Decrin/Satya sai] |
| 76 | Supply only Rotor assembly with brackets & tolerance rings part No. PMBRPL2 spare parts of Decrin dozing Pumps to be incorporated against Item No. 1.074 as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 77 | Supply only 7 Pump Head (Ferrules 1/4\" & duckbill included) Part No. UCPH7FD spare parts of Decrin dozing Pumps to be incorporated against Item No.1.074 here in before, complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 78 | Supply only 7 Pump Tube Part No. MCCP207 (5 PK) spare parts of Decrin dozing Pumps to be incorporated against Item No.1.074 here in before, complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 79 | Supply onlyInjection check valve3/8\" Part No. MCINJ38 (5 PK) as per existing sample spare parts of Decrin dozing Pumps to be incorporated against Item No.1.074 here in before, complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 80 | Supply only Weighted suction line strainer 3/8\" Part No. ST138 as per existing sample spare parts of Decrin dozing Pumps to be incorporated against Item No.1.074 here in before, complete all as specified and directed.[Note : Total Qty :1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 81 | Supply only 3/8\" weighted suction /discharge tubing Part No. MALT002 spare parts of Decrin dozing Pumps to be incorporated against Item No.1.074 here in before, complete all as specified and directed.[Note : Total Qty : 20.00 (Part-I) + 20.00 (Part-II) + 50.00 (Part-III) = 90.00] |
| 82 | Supply only Checkvalve duckbill (PK of 5) Part No. MCCVDBO as per existing sample spare parts of Decrin dozing Pumps to be incorporated against Item No. 1.074 here in before, complete all as specified and directed.[Note : Total Qty :1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 83 | Supply only Connecting nutand Adopter 3/8\" Part No. MANUT00 as per existing sample spare parts of Decrin dozing Pumps to be incorporated against Item No.1.074 here in before, complete all as specified and directed.[Note : Total Qty :1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 84 | Supply only Rollar Assembly4 Pack, Part No. MC3ASYD as per existing sample spare parts of Decrin dozing Pumps to be incorporated against Item No.1.074 here in before, complete all as specified and directed.[Note : Total Qty :1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 85 | Supply only Coil 250 V 50 HzPart No. MP6J222 as per existing sample spare parts of Decrin dozing Pumps to be incorporated against Item No. 1.074 here in before, complete all as specified and directed.[Note : Total Qty :1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 86 | Supply only Complete 230V 50 Hz gearmotoras per existing sample spare parts of Decrin dozing Pumps to be incorporated against Item No. 1.074 here in before, complete all as specified and directed.[Note : Total Qty :1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 87 | Supply only single head feed rate control with shaftas per existing sample spare parts of Decrin dozing Pumps to be incorporated against Item No.1.074 here in before, complete all as specified and directed.[Note : Total Qty :1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 88 | Supply only PVC dosing head assembly with suction and delivery with NRV for 25 LPH spare parts of Chemical chlorine dozing to be incorporated against Item No-1.074 here in before, [Note : Total Qty :1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 89 | Supply only PVC NRV set with glass ball for suction and delivery adopter spare parts of Chemical chlorine dozing to be incorporated against Item No- 1.074 here in before, complete all as specified and directed.[Note : Total Qty :1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 90 | Supply only PVC adopter for suction and delivery without NRV spare parts of Chemical chlorine dozing to be incorporated against Item No- 1.074 here in before, complete all as specified and directed.[Note : Total Qty :1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 91 | Supply only PVC stainer washer type heavy duty or Y type stainer for suction spare parts of Chemical chlorine dozing to be incorporated against Item No- 1.074 here in before, complete all as specified and directed.[Note : Total Qty :1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 92 | Supply only Teflon gland square type 3 mm spare parts of Chemical chlorine dozing to be incorporated against Item No- 1.074 here in before, complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) + 4.00 (Part-II) + 4.00 (Part-III) = 10.00] |
| 93 | Supply only Chemical oil seal with cap spare parts of Chemical chlorine dozing to be incorporated against Item No 1.074 here in before, complete all as specified and directed.[Note : Total Qty : 10.00 (Part-I) + 10.00 (Part-II) + 10.00 (Part-III) = 30.00] |
| 94 | Supply only Dosing aligator gear box 25 LPH spare parts of Chemical chlorine dozing to be incorporated against Item No- 1.074 here in before, complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) +1.00 (Part-II) + 1.00 (Part-III) = 3.00] |
| 95 | Supply only Plunger assembly without plunger dosing head 25 LPH spare parts of Chemical chlorine dozing to be incorporated against Item No-1.074 here in before, complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 96 | Supply only Plunger assembly with PVC dosing head complte 25 LPH spare parts of Chemical chlorine dozing to be incorporated against Item No- 1.074 here in before, complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 97 | Supply only Heavy duty FRP Tank capacity 150 ltr spare parts of Chemical chlorine dozing to be incorporated against Item No- 1.074 here in before, complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 98 | Supply onlyHeavy duty PVC NRV for delivery line spare parts of Chemical chlorine dozing to be incorporated against Item No-1.074 here in before, complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 4.00 (Part-III) = 7.00] |
| 99 | S&F in replacement Heavy duty chemical dosing system plunger type suitable to inject solution upto 25 LPH working pressure 10Kg/cm2 comprising dosing pump coupled with three phase electric motor of capacity 0.5 HP,14000 rpm assembly with agitator in one motor ,agitator with SS sweep blade dult FRP coated,FRP tank 150 Ltrs capacity ,complete unit mounted on heavy duty MS fabricated frame duly anticorrosive paint complete with chemical grade PVC NRV , alongwith control panel for dosing pumpmade of power coated MS fabricated box consisting of Led indicator ,digital volt meter, amp meter ,single phase preventor,High voltage low voltage protector, complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 1.00 (Part-II) + 1.00 (Part-III) = 3.00] |
| 100 | Supply and laying in repair flexible flat PVC insulated PVC sheathed copper couductor stranded submersible cable cores 1100 volt grade 16 Sqmm 3 core including jointing material and connection work complete all as specified and directed.[Note : Total Qty : 40.00 (Part-I) +100.00 (Part-II) + 40.00 (Part-III) = 180.00] |
| 101 | S&F Polymer insulated copper winding wire of existing gauge for 20 to 50 HP submerible motor, complete all as specified and directed.[Note : Total Qty : 30.00 (Part-I) + 100.00 (Part-II) + 70.00 (Part-III) = 200.00] |
| 102 | S&F super enameled copper winding wire of existing gauge for above 40 to 50 HPvertical motor, complete all as specified and directed.[Note : Total Qty : 20.00 (Part-I) + 40.00 (Part-II) + 40.00 (Part-III) = 100.00] |
| 103 | Opening completely pressure filter & oxidation chamber of capacity upto 10000 GPH and taking out existing filter media (sand, gravells) stainers and nozzles, removing and depositing filter media to a distance not exceeding 50 m including necessary repair/welding to make the pressure filter vessels complete leak proof for improving the strength and finally reassembling the pressure filter including filling of new strainer, gravles & sand in existing position duly cleaned replacing worn out gasket and nut bolts and washers, complete all as specified and directed. [Note- Total Qty : 10.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 14.00]Strainers, gravels shall be measured and paid separately under relevant items.Equipment make to be repaired: RMCO, Peral filter, Ion exchange] |
| 104 | M&L prepration of old painted steel/iron surfaces of pressure filter chamber by scrapping and cleaning of external and internal surfaces and applying two coats of black bituminious anti corrosive paint internal surface suitable for drinking water and Navy blue paint on outer surface marking the date of cleaning on the body complete all as specified and directed.[Note : Total Qty : 10.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 14.00] |
| 105 | Refixing of existing PVC strainer of IRP plantcomplete all as specified and directed.[Note : Total Qty : 1000.00 (Part-I) + 150.00 (Part-II)= 1150.00] |
| 106 | Supply only PVC push type/threaded type strainer suitable for filteration plant ,complete all as specified and directed.[Note : Total Qty : 800.00 (Part-I) + 150.00 (Part-II)= 950.00] |
| 107 | Supply only special coarse sandpassing through 3.125x 1.56 mmmesh suitable for use in filteration plant complete all as specified and directed.[Note : Total Qty :5.00 (Part-I) + 0.50 (Part-II) + 1.50 (Part-III) = 7.00] |
| 108 | Supply only special coarse sandpassing through 1.6 x 3.2 mmmesh suitable for use in filteration plantcomplete all as specified and directed.[Note : Total Qty :5.00 (Part-I) + 0.50 (Part-II) + 1.50 (Part-III) = 7.00] |
| 109 | Supply only new washed, cleaned, dust free, gravel of grading 25 mmto 20 mm graded filter media suitable for use in filteration plant complete all as specified and directed.[Note : Total Qty :5.00 (Part-I) + 0.50 (Part-II) + 1.50 (Part-III) = 7.00] |
| 110 | Supply only new washed, cleaned, dust free, gravel of grading 20 mmto 12 mm. graded filter media suitable for use in filteration plant complete all as specified and directed.[Note : Total Qty :5.00 (Part-I) + 0.50 (Part-II) + 1.50 (Part-III) = 7.00] |
| 111 | Supply only new washed, cleaned, dust free, gravel of grading 12 mmto 06 mm. graded filter media suitable for use in filteration plant complete all as specified and directed.[Note : Total Qty :5.00 (Part-I) + 0.50 (Part-II) + 1.50 (Part-III) = 7.00] |
| 112 | Supply only new washed, cleaned, dust free, gravel of grading 06 mmto 03 mm. graded filter media suitable for use in filteration plant complete all as specified and directed.[Note : Total Qty :5.00 (Part-I) + 0.50 (Part-II) + 1.50 (Part-III) = 7.00] |
| 113 | Supply and fixing live catalyticmedia (green Sand) suitable for use in filltration plant complete all as specified and directed.[Note : Total Qty : 8.00 (Part-I) + 1.00 (Part-II) + 3.00 (Part-III) = 12.00] |
| 114 | Supply only mix of manganese dioxide (MnO2) and treated carbofil in lumps of size 20 mm to 15 mm containing 75% of manganese Dioxide and 25%carbofil suitable for use in filltration plant complete all as specified and directed.[Note : Total Qty :5.00 (Part-I) + 0.50 (Part-II)= 5.50] |
| 115 | Repair to the motor (230 Volt 50 Hz) Power 120 watt, RPM-920) of agitator belongs to chlorine dozing system by dismantling the rotor complete rewinding the stator with proper gauge of super enamelled copper wire including changing of insulating material proper heat varnish, painting replacement of bearing complete & connected with chlorine dozing system afitetor complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 6.00][Equipment make to be repaired: KIrlosker,CG] |
| 116 | S&F in repairs Direct online starter set for induction motor Pump set of rating 5 HP, 415 volts, 50 Hz having with sheet metal encloser and relay range 3 phase 9 to 15 Amps rating panel mounting complete all as specified and directed.[Note : Total Qty : 3.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 7.00] |
| 117 | S&F contactor for 5 HP 415 Volts DOL starter complete all as specified and directed.[Note : Total Qty : 2.00 (Part-I) + 1.00 (Part-II) + 1.00 (Part-III) = 4.00] |
| 118 | S&F relay range 3 phase 9 to 15 Amps rating for 5 HP 415 Volts DOL starter complete all as specified and directed. [Note : Total Qty : 2.00 (Part-I) + 1.00 (Part-II) + 1.00 (Part-III) = 4.00] |
| 119 | M&L repairing of defective compressorand dismantling spare parts of Air Compressor of any size, re-metalling machinery polishing and re-assembling including replacement of old parts and necessary painting apply spray paint with two coat of synethetic enamel paint over a coat of red oxide primer complete all as specified and directed. [Note:- (i) Spare parts required will be measured and paid separately as \"Supply only\" here in after(ii) Total Qty : 2.00 (Part-I) + 2.00 (Part-II) + 4.00 (Part-III) = 8.00][Equipment make to be repaired: KIrlosker,Macshe,ELGi,Ingersol] |
| 120 | Supply only Piston for pump set complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 1.00 (Part-II) + 1.00 (Part-III) = 3.00] |
| 121 | Supply only Piston oil ring complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 3.00 (Part-III) = 6.00] |
| 122 | Supply only Liner complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 3.00 (Part-III) = 6.00] |
| 123 | Supply only Bearing complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 5.00 (Part-III) = 8.00] |
| 124 | Supply only Gear oil complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 125 | Supply only Compressor air meter complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 2.00 (Part-III) = 5.00] |
| 126 | Supply only Nozzle (Air) complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 3.00 (Part-III) = 6.00] |
| 127 | Supply only Gate valve 1/2 inchcomplete all as specified and directed.[Note : Total Qty :1.00 (Part-I) + 2.00 (Part-II) + 3.00 (Part-III) = 6.00] |
| 128 | Supply only 15 mm GI medium grade pipe complete all as specified and directed.[Note : Total Qty : 14.00 (Part-I) +10.00 (Part-II) + 20.00 (Part-III) = 44.00] |
| 129 | Supply only Fan belt complete all as specified and directed.[Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 5.00 (Part-III) = 8.00] |
| 130 | Cleaning of 1.2 MLD Sewage treatment plant after Pumping out sewage water from the existing sumps/tanks ofwith the help of Non clogging of pump any kind capacity of pump set not less than 2100 LPM capacity along with tanking out mud/ solid sludge from the tanks complete from soild sepration chamber, aeration chamber and despose whole sludge to faraway areas from public places including cleaning of sump completely all as specified and directed.[Note : Cleaning of all chambers to be treated as one Job] |
| 131 | Cleaning of raw sewage collection sump of 1.2 MLD Sewage treatement plant ofwith the help of Non clogging of pump any kind capacity of pump set not less than 2100 LPM capacity along with tanking out mud/ solid sludge from the tanks complete from and despose whole sludge to faraway areas from public places including cleaning of sump completely all as specified and directed. |
| 132 | Lifting the non clogging pump set electrically operated by 15HP/20HP 3 phase motor including its connected accessories etc. after disconnecting of all electrical and water line connection for any make of pump & motor, complete all as specified and directed.[Equipment make to be repaired: Kirlosker,CG] |
| 133 | Dismantaling of non clogging submersible pump of capacity 15HP/20HP and taking out burn out winding from the stator of motor and rewinding with PVC copper wire as per existing gauge incl connection commissioning & testing completed all as specified and directed.[Equipment make to be repaired: Kirlosker,CG] |
| 134 | Lowering complete the non clogging pumping set electrically operated by 15HP/20HP 3 phase motor including its connected accessories etc. and refixing the motor carefully including connection and testing, complete all as specified and directed.[Equipment make to be repaired: Kirlosker,CG] |
| 135 | Pumping out sewage water from the existing sumps/tanks ofSTPs (MBBR technology) with the help of Non clogging of pump any kind capacity of pump set not less than 1500 LPM capacity 10HP/15 HP (Minimum) along with tanking out mud/ solid sludge from the tank complete and despose whole sludge to faraway areas from public places including cleaning of sump completely. [Note :- (a) Pumping shall be continued till the main pumps installed in STPs sump is cleared for carrying out repair work.(b) Delivery pipe should be connected and the sewage water shall be thrown in the manhole of out side the fencing /wall of STPs towards the main gravity dropping main hole.(c) Pumping of sewage water stillbe continued till the sumps are fully empty and to keep till the installed non clogging pump are repaired & fully operative.(d) Necessary man power to operate the pump set are deemed to be included in the rate.(e) Rate quoted is deemed to include for Diesel/Engine oil till completion of repair work including testing of sewage pump set.(f) Rate included for transportation of pump set to site/back. (g)Cleaning of MBBR MS chamber and Concrete RCC chamber all required to be cleaned.] |
| 136 | Lifting thenon clogging submersible pump set electrically operated by 3.7 HP3 Phasemotor incl its connected accessories etc after disconnecting of all electric and water line connectionfor the any make of pump & motor complete all as specified and directed.[Equipment make to be repaired: kirlosker,CG] |
| 137 | Dismantling of non clogging submersible pump of capacity 3.7 HP and taking out burnout winding from the stator of motor and rewinding with PVC copper wire as per existing gauge incl connection commissioning & testing, complete all as specified and directed.[Note: PVC insulated copper winding wire of existing gauge paid and measured seprately][Equipment make to be repaired: Kirlosker,CG] |
| 138 | Lowering complete the non clogging pumping set electrically operated by 3.7 HP3 Phasemotor incl its connected accessories etc and refixing the motor carefully including connection and testing, complete all as specified and directed.[Equipment make to be repaired: Kirlosker,CG] |
| 139 | Dismantling of electric sewage induction motor 3.0 HP, AC, 3 phase, 415 volts from site after disconnecting from pump & electric connection for rewinding, taking out to work shop, opening of motor, taking out old worn-out / burnt-out winding complete, cleaning the slots properly and rewinding with supper enamelled copper wire as per existing gauge and varnishing complete, and reassembling after repairs and replacement of parts as required, refixing the same at site and connecting the electric connection with existing cable etc and including painting of external portion of pump withsynthetic enamel paint (1 st quality) of two coat after one coat priming of red oxide primer and testing for satisfatory working of pump, complete all as specified and directed.[Note: (a) Super enameled copper winding wire of existing gauge paid and measured seprately.(b) spare parts included in quoted rate.][Equipment make to be repaired: Kirlosker,CG] |
| 140 | Repair/Maint/overhauling of electric sewage induction motor upto 5.0 HP, AC, 3 phase, 415 volts from site after disconnecting from pump & electric connection, taking out old worn-out / burnt-out winding complete and reassembling after repairs and replacement of parts as required such as bearing, terminal plate etc., refixing the same at site and connecting the electric connection with existing cable etc and including painting of external portion of pump withsynthetic enamel paint (1 st quality) of two coat after one coat priming of red oxide primer and testing for satisfatory working of pump, complete all as specified and directed.[Note: (a) Super enameled copper winding wire of existing gauge paid and measured seprately.][Equipment make to be repaired: Kirlosker,CG] |
| 141 | Dismantling, Repair/Maint/overhauling of electric induction blower motor 30.00 HP, AC, 3 phase, 415 volts from site after disconnecting from blower & electric connection and assembly after repairs and replacement of parts as required, refixing the same at site and connecting the electric connection with existing cable etc and including painting of external portion of pump withsynthetic enamel paint (1 st quality) of two coat after one coat priming of red oxide primer and testing for satisfatory working of pump, complete all as specified and directed.[Note: (a) Super enameled copper winding wire of existing gauge paid and measured seprately.][Equipment make to be repaired: Kirlosker,CG] |
| 142 | M&L servicing and taking out & comprehensive maintenance of existing unserviceable Air Blower(of any Make ) of capacity 08 CFM to 20CFM with taking out of electric cable complete and reconnecting the electric and mechanical connection at existing location after carrying out following repairs complete all as specified and directed.[Note- (i) Some spare parts required for replacement shall be measured and paid under item no 1.142 to 1.146 as supply only. (ii) Replacement of Oil seal, locking arrangement of pully, gland packing with oil and greasing shall be deemed to be including in the quoted rate of this item.(iii) Painting of external surface with enamel paint.][Equipment make to be repaired: kirlosker,CG] |
| 143 | Supply only Gear oil EP 90, complete all as specified and directed. |
| 144 | Supply only Air filter suitable for existing one, complete all as specified and directed. |
| 145 | Supply only V belt as per existing model, complete all as specified and directed. |
| 146 | Supply only bearing as per existing, complete all as specified and directed. |
| 147 | Supply only set of rotor with hub as per existing model, complete all as specified and directed. |
| 148 | Supply only in repair\"s flexible flat PVC insulated PVC sheathed copper couductor stranded submersible cable cores 1100 volt grade 4 Sqmm 3 core including jointing material and connection work, complete all as specified and directed. |
| 149 | Supply only Pressure gauge for blower as per existing after taking out old unserviceable one, complete all as specified and directed. |
| 150 | Supply only in repair\"s Butterfly valve PN-1.0, 80 mm dia use in STPsincluding replacement of old rusted Nut, Bolts washers etc complete all as specified and directed. |
| 151 | Supply only Plastic MBBR Filter Bio media for sewage water treatment of size 25x12 mm black in colour, complete all as specified and directed. |
| 152 | S&F smart water level controller with sensor integration via screw terminals with the on-field configuration for providing the option for underground sump and overhead tank each,indication for 5 sensor reading per tank each.Indication for 5 sensor reading per tank (0%,25%,50%,75%,100%). Display interaface with4.3\"TFT LCD screen with 32 Bt microcontroller unit,fixed resolution 480X 720 Pixels.Operating Temperature foara device -20 to 70 DegreeC. The controller must support I/O based controls over 8 Bit 8051 base microcontroller unit with support for buzzer/Alarm at 25% and 100 % capacity to operate On/Off operations.Manual Override option to override the cintrols from Auto mode. The enclosure is made of ABS material for IP Protection.[Note : Horizontal magnetic float switch with SS pipe for sensor mountiing ,7 core copper alloy signal cable with weather proof rubber coating including in quoted rate.Any plumbing and electric work required at site for water or electric connections at siteis included in quoted rate.][Note : Total Qty : 1.00 (Part-I) + 2.00 (Part-II) + 1.00 (Part-III) = 4.00] |
| 153 | Sch A Part-II:- (Repair/ Maint of external water supply CI/DI, GI pipe line cleaning of OHT, UG sumps, maint of VT/ submersible pump, and allied works in Power House-I area under GE Panagarh)[Quantity of same nature of works pertains to Sch A Part- IIare clubbed up with relevant items of here-in-before in Part-I in respect of location of work. Bidders are requested to quote the rate considering the above aspect] |
| 154 | Taking up CI/DI water main (incl all fitting) with spigot & socket ends and lead joints incl burning out & recovering lead frompipe of 80 mm bore for relaying / rerouting of serviceable pipe after cleaning complete all as specified and directed.[Note : Total Qty :48.00 (Part-II) + 48.00 (Part-III) = 96.00] |
| 155 | Taking up CI/DI water main (incl all fitting) with spigot & socket ends and lead joints incl burning out & recovering lead frompipe of 200 mm bore for relaying / rerouting of serviceable pipe after cleaning complete all as specified and directed.[Note : Total Qty : 60.00 (Part-II) + 60.00 (Part-III) = 120.00] |
| 156 | Taking up CI/DI water main (incl all fitting) with spigot & socket ends and lead joints incl burning out & recovering lead frompipe of 250 mm bore for relaying / rerouting of serviceable pipe after cleaning complete all as specified and directed.[Note : Total Qty : 50.00 (Part-II) + 50.00 (Part-III) = 100.00] |
| 157 | Relaying of DI/CI/GI pipe 80 mm bore in trenches/ over the masonry pillars after cleaning thoroughly including fittings complete all as specified and directed.[Note : Total Qty : 12.00 (Part-II) + 12.00 (Part-III) = 24.00] |
| 158 | Relaying of DI/CI/GI pipe 200 mm bore in trenches/ over the masonry pillars after cleaning thoroughly including fittings complete all as specified and directed.[Note : Total Qty : 30.00 (Part-II) + 30.00 (Part-III) = 60.00] |
| 159 | Relaying of DI/CI/GI pipe 250 mm bore in trenches/ over the masonry pillars after cleaning thoroughly including fittings complete all as specified and directed.[Note : Total Qty : 30.00 (Part-II) + 30.00 (Part-III) = 60.00] |
| 160 | M&L DI pipe of 80 mm bore with spigot and socket end rubber gas cate joint(titon) centrifugally cast class k-7 conforming to IS 8329-2000 laid in trenches/ on surface/ over masonry pillar and connection to old or new position complete all as specified and directed.[Note : (i) Total Qty : 36.00 (Part-II) + 36.00 (Part-III) = 72.00(ii) Cost of joint included in the qoted rate] |
| 161 | M&L DI pipe of 200 mm bore with spigot and socket end rubber gas cate joint(titon) centrifugally cast class k-7 conforming to IS 8329-2000 laid in trenches/ on surface/ over masonry pillar and connection to old or new position complete all as specified and directed.[Note : Total Qty : 30.00 (Part-II) + 30.00 (Part-III) = 60.00] |
| 162 | M&L DI pipe of 250 mm bore with spigot and socket end rubber gas cate joint(titon) centrifugally cast class k-7 conforming to IS 8329-2000 laid in trenches/ on surface/ over masonry pillar and connection to old or new position complete all as specified and directed.[Note : Total Qty : 20.00 (Part-II) + 20.00 (Part-III) = 40.00] |
| 163 | Taking up or down 40 mm bore steel tubing and connection including cleaning for relaying or removal to store from trenches/wall surfaces complete all as specified and directed.[Note : Total Qty : 180.00 (Part-II) + 110.00 (Part-III) = 290.00] |
| 164 | Relaying/re-fixingold 40 mm bore GI tubing or in floor/pillar/wall in new or old position complete all as specified and directed.[Note : Total Qty : 30.00 (Part-II) + 30.00 (Part-III) = 60.00] |
| 165 | M&L 40 mm bore GI Tubing medium grade in Trenches/ Floor/Pillar andconnectionin old or news position including fittinglike socket/Union/Tee/Reducer Nipple etc complete all as specified and directed and required will be supplied by Contractor rate for the same is included in the item rate quoted.[Note : Total Qty : 150.00 (Part-II) + 80.00 (Part-III) = 230.00] |
| 166 | Supply and laying of UPVCpipes 15 mm outer dia, UV stabilized and having thermal stability for hot & cold water supply all fittings laid in trenches / wall including all fittings complete including taking out old unservicable pipe complete all as specified and directed.[Note : Total Qty : 30.00 (Part-II) + 30.00 (Part-III) = 60.00] |
| 167 | M&L rubber gasket jointin repair for 80 mm boreCI/DI Pipe with Spigot & Socket ends after connection of old and new position complete all as specified and directed.[Note : Total Qty : 2.00 (Part-II) + 2.00 (Part-III) = 4.00] |
| 168 | M&L rubber gasket jointin repair for 100 mm boreCI/DI Pipe with Spigot & Socket ends after connection of old and new position complete all as specified and directed.[Note : Total Qty : 2.00 (Part-II) + 2.00 (Part-III) = 4.00] |
| 169 | M&L rubber gasket jointin repair for 150 mm boreCI/DI Pipe with Spigot & Socket ends after connection of old and new position complete all as specified and directed.[Note : Total Qty : 2.00 (Part-II) + 2.00 (Part-III) = 4.00] |
| 170 | S & F in repairs 80 mm bore Sluice valve PN – 1.6 IS 14846-2000 with Spindle Iron (Heavy duty) Wheel head and both ends flanged and MS nut bolts and washers and pair of rubber/fiber gasket and fixed in position complete all as specified and directed.[Note : Total Qty : 1.00 (Part-II) + 1.00 (Part-III) = 2.00] |
| 171 | S & F in repairs200 mm bore Sluice valve PN – 1.6 IS 14846-2000 with Spindle Iron (Heavy duty) Wheel head and both ends flanged and MS nut bolts and washers and pair of rubber/fiber gasket and fixed in position complete all as specified and directed.[Note : Total Qty : 1.00 (Part-II) + 1.00 (Part-III) = 2.00] |
| 172 | M&L 40 mm bore gate valve gum metal class-II screwed down high pressure with clutch handle screwed both ends for Iron pipe including taking out of old unserviceable gate valve complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 5.00 (Part-III) = 10.00] |
| 173 | M&L Rendering 10mm thick on fair faces of brick work or concrete surface in cement mortar (1:6) on brick surface fair and even complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 5.00 (Part-III) = 10.00] |
| 174 | S & F PVC Tank Cover (Best Quality) Suitable for Cylindrical Vertical Storage Tank of sizes 300 Ltrs to 2000 Ltrs capacity.incl tank holes hinges fitted any type complete all as specified and directed.[Note : Total Qty : 10.00 (Part-II) + 10.00 (Part-III) = 20.00] |
| 175 | Testing of Water Samples for Chemical ,biological ,bacteriological analysis as mentioned below from Pump Housescomplete all as specified and directed.Following tests perimeters are:- Ph Level, Specific Conductivity, Chloride (CL), Total Harness as Ca CO₃, Iron as (Fe),Arsenic (AS), Total dissolved solids , Bacteria, Colour,Odour, Taste, Turbidity NTU, Max,Floride,Copper,Nitrate,Alkalinity,E- Coliform, Total Coliform Bactria,Manganese, Sulfide, Calcium, Magnesium, Cyanide, Lead, cromium, Zinc, Alumium, TSS, Oil and grease, Ca hardness, Mg hardness, P Alkalinity, M Alkalinity, Sodium, Potsium, free Chloride Sulphate[Note : (a) Total Qty : 20.00 (Part-II) + 24.00 (Part-III) = 44.00](b)Sample of Water for the above media test are to collected in transparent container/Jar/bottle separately for each test against each pump houses. (Hygienically clean bottles). (c) Sample of water to becollectedshall be forwarded to Govt Lab / any NABL certified authorized Lab.(d) Testing of Raw water and Treated water in Each PH considered as One Job.(e) TestingofWaterfor Raw Water & Filtererd Water for total Pump Houses in three month Basis.] |
| 176 | Taking out vertical hollow shaft motor, 3 Phase 50HP/45 HP/40HP, 1440 RPM , 50 Cycle and dismantling the rotor complete and rewinding the stator with proper gauge of super enamelled copper wire including changing of insulating material, varnishing, baking heating properly and reassembling the moter to its original position with replacement of connection plate and also taking out U/S ratchet plate assembly from VT motor of any size / capacity and S&F ratchet plate assembly complete with ratchet, balls hexagonal bolts etc complete all as specified and directed including testing and commisioning. [Note :- (i) Total Qty : 1.00 (Part-II) + 2.00 (Part-III) = 3.00](ii) Super enameled copper winding wire of existing gauge, weight and turns paid seprately under items no. 2.183.(iii) Rate quoted is deemed to inclusive transportation charges.][Make: WPIL,Kirlosker] |
| 177 | Lifting and lowering of vertical turbine Pump set : By disconnecting of allelectrical connections to motor and pump , Lifting of VT pump assembly from bore of any depth alongwith column pipe, shaft and connected items are kept inside pump house to check the unserviceability, complete all as specified and directed. [Note :-(a)Total Qty : 2.00 (Part-II) + 2.00 (Part-III) = 4.00](b) Rate quoted against items deemed to be included for liftingand lowering. (c)Chain pulley block will be used according to the load of pump alongwith column pipe and connected items.(d)Any damages to equipment due to negligence of contract during lifting and lowering to be born by contractor at this own risk & cost.][Equipment make to be repaired: WPIL,Kirlosker] |
| 178 | Dismantling of vertical turbine pump bowl asembly of any make and capacity and size completecarefully without damaging any parts of the pump and setting aside in pump house for ascertaining the serviceability of existing dismantling parts,with the following works :-(a)Through removing sludging and cleaning of complete bowl assembly items, such as bowl, discharge case , suction case , Impeller , lock collect, bearing /bushes, pump shaft complete etc.after assamblingthe pump. Checking of all rotary and statutory parts of pump bowl assembly and making free by balancing for their satisfactory run.[Note : (i) Total Qty : 2.00 (Part-II) + 2.00 (Part-III) = 4.00](ii) All new spare parts will be paid under relevent items here-in-after alongwith with their fixing charge(iii) Make of spare paerts shall be Garden reach Ship Builders & Engineers/WPIL/Kirlosker][Equipment make to be repaired: WPIL,Kirlosker] |
| 179 | S&F Packing box bearingsuitable for upto 40 mm shaft as required at site spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 2.00 (Part-II) + 6.00 (Part-III) = 8.00] |
| 180 | S&F Packing box bearingsuitable for upto 25mmshaft as required at site spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 2.00 (Part-II) + 3.00 (Part-III) = 5.00] |
| 181 | S&F Packing box gasket suitable for 25mm/40mm shaft., complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 9.00 (Part-III) = 13.00] |
| 182 | S&F Line shaft 10 feet long both end threaded upto 40 mm (SS) spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 8.00 (Part-III) = 12.00][Equipment make to be repaired: WPIL,Kirlosker] |
| 183 | S&F Line shaft 10 feet long both end threaded upto 25 mm (SS)spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 8.00 (Part-III) = 12.00][Equipment make to be repaired: WPIL,Kirlosker] |
| 184 | S&F Line shaft 05 feet long both end threaded upto 40 mm (SS) spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 4.00 (Part-III) = 8.00][Equipment make to be repaired: WPIL,Kirlosker] |
| 185 | S&F Line shaft 05 feet long both end threaded upto 25 mm (SS)spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 4.00 (Part-III) = 8.00] |
| 186 | S&F Line shaft coupling suitable for 40mm dia shaft spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 10.00 (Part-III) = 14.00] |
| 187 | S&F Line shaft coupling suitable for 25 mm dia shaft spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 5.00 (Part-III) = 9.00] |
| 188 | S&F Head shaft (Top shaft, SS not exceeding 40 mm dia and 9 feet long as requiredat site) spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 3.00 (Part-II) + 3.00 (Part-III) = 6.00] |
| 189 | S&F Head shaft (Top shaft, SS not exceeding 25 mm dia and 9 feet long as requiredat site) spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 3.00 (Part-III) = 7.00] |
| 190 | S&F Rubber bush for line shaft bearing retainer suitable for upto 40 mm dia line shafts and suitable for 6 inch dia column pipe as required at site spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 10.00 (Part-III) = 14.00] |
| 191 | S&F Rubber bush for line shaft bearing retainer suitable for upto 25 mm dia line shafts and suitable for 6 inch dia column pipe as required at site spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 8.00 (Part-III) = 12.00] |
| 192 | S&F Bearing retainersuitable for 6\" dia column pipe and upto 40 mm dia line shaft as required at site spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 10.00 (Part-III) = 14.00] |
| 193 | S&F Bearing retainersuitable for 6\" dia column pipe and upto 25mm dia line shaft as required at site spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 10.00 (Part-III) = 14.00] |
| 194 | S&F Shaft sleeve as suitable for line shaft upto 40mm dia (SS) for spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 10.00 (Part-III) = 14.00] |
| 195 | S&F Shaft sleeve as suitable for line shaft upto 25mm dia (SS) for spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 10.00 (Part-III) = 14.00] |
| 196 | S&F Intermediate bowl Cl 10 cc/1607 as per existing sample spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 12.00 (Part-III) = 16.00] |
| 197 | S&F MS column coupling suitable for 6 inch dia , column pipe (8TPI) 7.1 mm minimum thickness ( internally threaded ) heavy duty spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 10.00 (Part-III) = 14.00][Equipment make to be repaired: Declibac decrin, Satya Sai] |
| 198 | S&F Intermediate bowl bush rubber upto 25 mm forany type and size of bowl for spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 8.00 (Part-III) = 12.00] |
| 199 | S&F Intermediate bowl bush rubber upto 40 mm forany type and size of bowl for spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 10.00 (Part-III) = 14.00][Equipment make to be repaired: Satya sai] |
| 200 | S&F Impellor lock collect carbon steel suitable for upto 40mm dia pump shaft as per existing sample forspare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 10.00 (Part-III) = 14.00] |
| 201 | S&F Suction/discharge case CI suitable for upto 10CC/1607 or any type of bowl as per existing for sample spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 10.00 (Part-III) = 14.00] |
| 202 | S&F Suction / discharge case bearing bronze suitable forabove items upto 40mm dia pump shaft or as per existing sample spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 8.00 (Part-III) = 12.00] |
| 203 | S&F NewImpeller close type bronze suitable 10CC/1607 upto 40mm dia pump shaft or as per existing sample for spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 4.00 (Part-III) = 8.00] |
| 204 | S&F Bowl stud suitbale for 1607 or any type and size of bowl or as per sample for spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 10.00 (Part-II) + 16.00 (Part-III) = 26.00] |
| 205 | S&F pump shaft SS upto 40mm dia 9 feet long suitable for 10 stage bowl assembly having 1607 bowl or any type of bowl or as per existing sample for spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 4.00 (Part-III) = 8.00] |
| 206 | S&F Split packing gland suitable for 40 mm dia head shaft with packing gland stud and nut spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 3.00 (Part-II) + 3.00 (Part-III) = 6.00] |
| 207 | S&F Split packing gland suitable for 25mm dia head shaft with packing gland stud and nut spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 2.00 (Part-II) + 2.00 (Part-III) = 4.00] |
| 208 | S&F Packing box suitable for upto 20000 GPH pump set for spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 5.00 (Part-III) = 9.00] |
| 209 | S&F Adjusting nut alongwith lock screw for upto 40 mm dia top shaft for spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 6.00 (Part-III) = 10.00] |
| 210 | S&F Adjusting nut alongwith lock screw for upto 25 mm dia top shaft for spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 2.00 (Part-II) + 2.00 (Part-III) = 4.00] |
| 211 | S&F Pump shaft and hallow shaft motor coupling complete suitable for 20000 GPH pump set spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 4.00 (Part-III) = 8.00] |
| 212 | S&F Thrust bearing any size and type spare parts of vertical turbine pump of any capacity, complete all as specified and directed.[Note : Total Qty : 2.00 (Part-II) + 2.00 (Part-III) = 4.00] |
| 213 | Cutting , facing and threading of column pipe upto 150mm dia of length n.exc 10 feet each complete all as specified and directed as required at site [Note : (i) Total Qty : 6.00 (Part-II) + 10.00 (Part-III) = 16.00](ii) Rate are inclusive of transportation , loading /uploading etc of the item from installation to civil workshop & back.] |
| 214 | After repairing of pump & motor, complete pump shaft, line shaft, head shaft ( top shaft) etc of any VT pump asembly and complete impeller assembly Old/New from pump house to civil workshop for carrying out the under mentiioned work and back to installation for refixing including Decoupling of VT hollow shaft motor 45 HP , 3 Phase, from pump andfixing newthrust bearing incl greasing after taking out the old U/S thrustbearing form motorand lowering of pump assembly in bore of any depth alongwith column pipe, shaft and connected items after repair against respective item here-in- afterand installation of pump motor in its original foundation, connections the same with top shaft as well as delivery main including electrical connectiion of both end i.e. with starter and motor terminals. etc with testing, commissioning, complete all as specified and directed :-(a)Proper alingment of pump shaft, line shaft and top shaft.(b)Proper balancing of the impellers[Note : Total Qty : 1.00 (Part-II) + 2.00 (Part-III) = 3.00][Equipment make to be repaired: Kirlosker,WPIL] |
| 215 | Dismantling of submersible pump bowl assembly of any make and capacity and size complete( to be measured only after lifting against Srl item No 1.066 here-in above) carefully without damaging any parts of the pump and setting aside in Pump house of ascertaining the serviceability of existing dismantled parts including reassembling complete pump with the following works, complete all as specified and directed :-(a) Cleaning of completepump assembly items dischagre case,impellor , Shaft suction casing bowls disc & bearing etc.(b) Checking of all rotary and statutory parts of pump bowl & stage casing assembly and making free for their satisfactory run[Note : (i) Total Qty : 5.00 (Part-II) + 8.00 (Part-III) = 13.00](ii) Cost of minor spares is rubber \"O\" ring , oil seal etc. is deemed to be included in the item](iii) S&F of other spare parts will be measured & paid separately under revelent item][Equipment make to be repaired: Kirlosker,KSP,CG,WPIL] |
| 216 | S&F Suction Cover (Heavy) spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 6.00 (Part-III) = 11.00] |
| 217 | S&F Half coupling pump spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 6.00 (Part-III) = 11.00] |
| 218 | S&FS.S Shaft (V Stg) spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 6.00 (Part-III) = 11.00] |
| 219 | S&F Neck Ring spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 8.00 (Part-III) = 13.00] |
| 220 | S&F S.S Sleeve spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 8.00 (Part-III) = 13.00] |
| 221 | S&F Top Washer spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 6.00 (Part-III) = 11.00] |
| 222 | S&F Allen Screw spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 6.00 (Part-III) = 11.00] |
| 223 | S&F Coupling Key for shaft spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 10.00 (Part-II) + 10.00 (Part-III) = 20.00] |
| 224 | S&F Bowl bush spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 6.00 (Part-III) = 11.00] |
| 225 | S&F Coupling bush spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 6.00 (Part-III) = 11.00] |
| 226 | S&F Bowl threaded spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 10.00 (Part-II) + 10.00 (Part-III) = 20.00] |
| 227 | S&F Discharge Outlet spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 6.00 (Part-III) = 11.00] |
| 228 | S&F Non return Valve spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 6.00 (Part-III) = 11.00] |
| 229 | S&FImpeller spare parts of submersible pump of any capacity, complete all as specified and directed.[Note : Total Qty : 5.00 (Part-II) + 8.00 (Part-III) = 13.00] |
| 230 | Supply and laying in repair flexible flat PVC insulated PVC sheathed copper couductor stranded submersible cable cores 1100 volt grade 25 Sqmm 3 core including jointing material and connection work complete all as specified and directed.[Note : Total Qty : 50.00 (Part-II) + 50.00 (Part-III) = 100.00] |
| 231 | M & L Timer Star Delta time of 3 sec-30 sec Voltage range 240-415VAC.Contact arrangement 1 C/O (Star)+1 C/O (Delta)as per existing after taking out old unserviceable one complete all as specified and directed. [Note : Total Qty : 1.00 (Part-II) + 1.00 (Part-III) = 2.00] |
| 232 | M & L Start Push Button as per existing after taking out old unserviceable one complete all as specified and directed. [Note : Total Qty : 4.00 (Part-II) + 4.00 (Part-III) = 8.00] |
| 233 | M & L for Stop Push Button as per existing after taking out old unserviceable one complete all as specified and directed. [Note : Total Qty : 4.00 (Part-II) + 4.00 (Part-III) = 8.00] |
| 234 | M&L nylon tube ¼ “dia for chlorine dozing system complete all as specified and directed.[Note : Total Qty : 10.00 (Part-II) + 30.00 (Part-III) = 40.00] |
| 235 | S&F of MS column pipe 150 mm dia (3 mtr long) both side flanged (using MS flange ) heavy grade MS pipe including nuts, bolts, gasket and washers all complete as specified and as directed including taking down old unserviceable pipe, complete all as specified and directed.[Note : Total Qty : 10.00 (Part-II) + 5.00 (Part-III) = 15.00] |
| 236 | S&F of MS column pipe 100 mm dia (3 mtr long) both side flanged (using MS flange ) heavy grade MS pipe including nuts, bolts, gasket and washers, complete all as specified and directed including taking down old unserviceable pipe.[Note : Total Qty : 10.00 (Part-II) + 5.00 (Part-III) = 15.00] |
| 237 | Developing of tube well by means of air compressor(min 40 Bar), for number of hours, until sand free clear potable water is obtained including testingto get maximum yield and discharge complete all as specified and directed.[Note : (i)Total Qty : 72.00 (Part-II) + 36.00 (Part-III) = 108.00(ii) Test report to be submitted to the Engr-in-Charge] |
| 238 | Cleaning of RCC/PS/GRP Over head tank /UG tanks upto 4,50,000 litres capacity (i.e 1,00,000 gallons) tanks (tank height 21 mtr)/sumps 110m depth by Hi-Tech system using High Pressure jet Pump having putting minimum pressure of 150 Bar to clean all sludge on walls, floors, treating with Hydrogen peroxide and applying ultra violet rays to make the tank bacteria free (by using tanclean chemical), complete all as specified and directed.[Note: (i) Total Qty : 8.00 (Part-II) + 2.00 (Part-III) = 10.00(ii) Rate are deemed for writing work i.e. tank clean on(date), (month) and (year), font size should be 30 cms.(iii) Item rate including of any damage during cleanig of OHTs(iv) Location: (a)Pump House No 2 at \"D\"Camp (b)Pump House No 4 at Lal Qtr (c) Power House-I ] |
| 239 | Dismantling pump set of centrifugal type (12.5 HP induction motor), AC, 3 phase, 415 volts from site after disconnecting of suction and delivery line, taking out to work shop if required , dismantling pump set for overhauling, replacing u/s shaft sleeve, gland packing, bearing, water seal,rubber coupling ,connection plate, pump motor coupling shaft, applying grease etc reassembling the pump set and fixing on the foundation and connecting with existing pipe line with nuts, bolts andnew gasket, connecting the electric connection with existing cable etc and including painting of external portion of pump withsynthetic enamel paint (1 st quality) of two coat after one coat priming of red oxide primer and testing for satisfactory working of pump complete all as specified and directed.[Note : Total Qty : 4.00 (Part-II) + 4.00 (Part-III) = 8.00][Equipment make to be repaired: KIrlosker,CG] |
| 240 | Dismantling of electric induction motor 12.5 HP, AC, 3 phase, 415 volts from site after disconnecting from pump & electric connection for rewinding, taking out to work shop, opening of motor, taking out old worn-out / burnt-out winding complete, cleaning the slots properly and rewinding with supper enamelled copper wire(including proper insulating paper/ film) as per existing gauge/ size with varnishing, baking as required, and reassembling after repairs and replacement of parts as required, refixing the same on the base at site and connecting the electric connection with existing cable to starter and including painting of external portion of pump withsynthetic enamel paint (1 st quality) of two coat after one coat priming of red oxide primer and testing for satisfactory working of Motor complete all as specified and directed.[Note : Total Qty : 2.00 (Part-II) + 2.00 (Part-III) = 4.00][Equipment make to be repaired: KIrlosker,CG] |
| 241 | Rewinding to aircompressor motor of size upto 5Hp at various Pump houses with proper gauge winding wire complete all as specified and directed. |
| 242 | Sch A Part-III:- (Repair/ Maint of external water supply CI/DI, GI pipe line cleaning of OHT, UG sumps, maint of VT/ submersible pump, and allied works in Power House-II area under GE Panagarh)[Quantity of same nature of works pertains to Sch A Part-III are clubbed up with relevant items of Sch A Part-I & Part-II here-in-before. Bidders shall note the above aspects while quoting of tender in respect of location of work] |
| 243 | Testing of Sewage Water Samples for BOD annd COD testing analysis as mentioned below from STPs viz 1.2 MLD STP, STP ILP-II - 03 Nos, STPs 59 DOU- 01, sadhunagar STP Nos complete all as specified and directed.(a) BOD(b) COD(c) PH Level (d) Total Suspended Soild(TSS)(e) Outlet Coliform[Note: TestingofSewage Water Treated sewage Waterin three month Basis.(i.e Treated Sewage water in Each STPs consider as one Job)(a)Sample of Sewage Water for the above media test are to collected in transparent container/Jar/bottle separately for each test against each STPs. (Hygienically clean bottles). (b) Sample of water to becollectedshall be forwarded to Govt Lab / any NABL certified authorized Lab.] |
| 244 | M&L cleaning of Over head tank ofMasonary Tank/ GRP tank atPump House No 6 (1 x20000Gln )(Tank height 12 mtrs) by Hi-Tech system using High Pressure jet Pump having putting minimum pressure of 150 Bar to clean all sludge on walls, floors, treating with Hydrogen peroxide and applying ultra violet rays to make the tank bacteria free (by using tanclean chemical), complete all as specified and directed.[Note: (i) Rates are deemed for writing work i.e. tank clean on(date), (month) and (year), font size should be 30 cms.(ii) Item rate including of any damage during cleanig of OHTs] |
| 245 | All as per item No. 3.002 above but for PS/GRP Tank (2 x 12000 Gln) at PH No-15, complete all as specified and directed. |
| 246 | All as per item No. 3.002 above but for PS/GRP Tank at PH No-06 PS Tank (1 x 12000 Gln), complete all as specified and directed. |
| 247 | M&L cleaning of RCC/PS/GRP Over head tank of 2,25,000 litres capacity (i.e 50,000 gallons) tanks (Tank height 18 mtrs) by Hi-Tech system using High Pressure jet Pump having putting minimum pressure of 150 Bar to clean all sludge on walls, floors, treating with Hydrogen peroxide and applying ultra violet rays to make the tank bacteria free (by using tanclean chemical) , complete all as specified and as directed.[Note: (i) Rate are deemed for writing work i.e. tank clean on(date), (month) and (year), font size should be 30 cms.(ii) Item rate including of any damage during cleanig of OHTs](iii) Total Qty : 1.00 (atPump House No-3 at ME Line) + 1.00 (PH 104 at KLP) + 1.00 (ILP-2 PH 1) +1.00 (ILP-2 PH 2) + 1.00 (ILP-2 PH 3)= 5.00] |
| 248 | M&L cleaning of UGReservoir/Sump by Hi-Tech system using High Pressure jet Pump having putting minimum pressure of 150 Bar to clean all sludge on walls, floors, treating with Hydrogen peroxide and applying ultra violet rays to make the tank bacteria freeof20000 Gln capacity tanks complete all as specified and directed.[Note: Total Qty : 1.00 ( of Pump House No 16) + 1.00 (of Pump House No 19)= 2.00] |
| 249 | M&L Pumping out water from Swimming Pool with the help of External Pump &cleaning of Swimming Pool complete by usingmechanical cleaning equipments complete all as specified and directed.(The cost of mtrl, labour and necessary tools & plants are deemed to be included in the quoted rate)[Note : Any leakage in pipe of any size if found inside swimming pool is to be repaired at siteis deemed to be included in quoted rate. Dismantling of tiles and refixing at proper location for repair of pipe line is deemed to be included in quoted rate.] |
| 250 | M&L cleaning of UGReservoir of swimming pool (Water) by Hi-Tech system using High Pressure jet Pump having putting minimum pressure of 150 Bar to clean all sludge on walls, floors, treating with Hydrogen peroxide and applying ultra violet rays to make the tank bacteria free (by using tanclean chemical) of20000 Gln capacity tanks complete all as specified and directed. |
| 251 | Comprehensive maintenance of suction sweeper 3.0 HP, AC, 3 phase, 415 volts50hz including greasing, oiling etc and other accessories including bearing, sleeves, couplings,connection plate etcas required after maintance pump set painting of external portion with enamaled paint of pump complete all as specified and directed. |
| 252 | Dismantling of electric induction motor of suction sweeper 3.0 HP, AC, 3 phase, 415 volts from site after disconnecting from electric connection for rewinding, taking out to work shop, opening of motor, taking out old worn-out / burnt-out winding complete, cleaning the slots properly and rewinding with supper enamelled copper wire as per existing gauge and varnishing complete, and reassembling after repairs and replacement of parts including repair of pump set as required, refixing the same at site and connecting the electric connection with existing cable etc and including painting of external portion of pump withsynthetic enamel paint (1 st quality) of two coat after one coat priming of red oxide primer and testing for satisfatory working of pump complete all as specified and directed. |
| 253 | Dismantling of electric centrifugal monoblock pump of 1.0 HP, AC, single phase from site after disconnecting from electric connection for rewinding, trasportingto work shop, opening of motor, taking out old worn-out / burnt-out winding complete, cleaning the slots properly and rewinding with supper enamelled copper wire as per existing gauge and varnishing complete,bakingand reassembling after repairs and replacement of parts all parts including pump as required, refixing the same at site and connecting the electric connection with existing cable etc and testing for satisfatory working of pump complete all as specified and directed. |
| 254 | Dismantling of electric centrifugal monoblock pump of 0.5 HP, AC, single phase from site after disconnecting from pump & electric connection for rewinding,opening of motor, taking out old worn-out / burnt-out winding complete, cleaning the slots properly and rewinding with supper enamelled copper wire as per existing gauge and varnishing complete, baking incl isnulation material and reassembling after repairs and replacement of parts as required, refixing the same at site and connecting the electric connection with existing cable etc and testing for satisfatory working of pump complete all as specified and directed. |
| 255 | S&F PVC flexible hose pipe upto 50 mm dia with flat iron clamp complete as per existing sample complete all as specified and directed. |
| 256 | S&F Nylon brush 4 feet long for suction sweeper complete complete all as specified and directed. |
| 257 | S&F PVC tyres for suction sweeper as per existing complete all as specified and directed. |
| 258 | Repair to hair stainer by replacement of brass hair strainer welding/ leath work , of strainer Body,locking clump, including the replacement of rubber/ fibre washer belongs to the cover of hair strainer including the repair of strainer base by welding & necessary PCC work so as to operate the contrifugal pumps smoothly to avoid air lock complete all as specified and directed. |
| 259 | M&L opening of sluice valves 125 mm dia bore after de-scaling and grinding on Lathe Machine and replacement ofSpindle, Gutka, valve sheet, brass rings as per existing and complete scaling and proper functioning at site refixing at existing postion inclcluding nut, bolt, washer, gasket, wheelcomplete all as specified and directed. |
| 260 | Opening completely pressure filter chamber of capacity 32,000 GPH and taking out existing filter media (sand, gravells) stainers pipe and nozzles, removing and depositing filter media to a distance not exceeding 50 m and strainer and nozzles to MES stores yard including necessary repair/welding to make the pressure filter vessels complete leak proof for improving the strength and finally reassembling the pressure filter including filling of gravles & sand, replacing of unsv strainer , in existing position duly cleaned replacing New gasket and nut bolts and washers complete all as specified and directed.[Note- Gravels shall be measured and paid seperatly under relevant items] |
| 261 | Testing of Water Samples for Physical, Chemical and biological analysis as mentioned below from viz swimming pool Pump house ).(i) Ph Level (ii) Specific Conductivity (iii) Chloride (CL) (iv) Total Harndess as Ca CO₃ (v) Iron as (Fe) (vi) Arsenic (AS) (vii) Total dissolved solids (viii) Bacteria (ix) Colour (x) Odour (xi) Taste (xii) Turbidity NTU, Max (xiii) Floride (xiv) Copper (xv) Nitrate (xvi) Alkalinity (xvii) E- Coliform (xviii) Total Coliform Bactria (xix) Manganese[Note :-(a) TestingofWaterfor Raw Water & Filtererd Waterfor Swimming pool plant in three month Basis.(Raw water and filtered water sample consider as one job.(b) Sample of Water for the above media test are to collected in transparent container/Jar/bottle separately for each test against each pump houses (Hygienically clean bottles). (c) Sample of water to be collectedshall be forwarded to Govt Lab or any NABL approved Lab.(d) Testing of Water shall be carried out any authorized Central/State Govt Lab. (e) Water samples shall be collected every three month Test Results alongwith remarks shall be submitted in this office. (W.e.f the commencement of contract agreement to the completion of the contract ) |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail