| 1 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. ( Pump House No:6)Incoming:-(a) ACB 630 amps, 4 pole, 50 KA, microprocessor release drawout type - 01 No (b) Bus bar electrolytic grade copper 1000 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing:-(a) MCCB 250 amps, 4 pole,35/36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos.b) MCCB 160 amps, 4 pole, 25KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 03 Nos. (c) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 03 Nos. |
| 2 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. ( 61 Sub area conference room)Incoming:- (a) MCCB 250 amps, 4 pole,35/36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade copper 400 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing:-(a) MCCB 200 amps, 4 pole,25 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) MCCB 160 amps, 4 pole, 25KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (c) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (d) MCCB 63 amps, 4 pole, 16 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos. (e) ON load change over switch 200 Amp-02 Nos. |
| 3 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. ( Pump house No: 9)Incoming(a) MCCB 250 amps, 4 pole,35/36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 400 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing(a) MCCB 160 amps, 4 pole, 25KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (b) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (c) MCCB 63 amps, 4 pole, 16 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. |
| 4 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. (Near P-21 Khatipura and Near P-164 Lane-V)Incoming(a) MCCB 160 amps, 4 pole,35/36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 250 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing(a) MCCB 100 amps, 4 pole, 25KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (b) MCCB 63 amps, 4 pole, 16 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. |
| 5 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. (GE Jaipur Khatipura)Incoming(a) MCCB 315 amps, 4 pole,35/36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 500 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing(a) MCCB 250 amps, 4 pole, 25KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 03 Nos. (b) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (c) Digital timer with suitable contactor-01 No |
| 6 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. (Haldighati switchyard)Incoming(a) MCCB 250 amps, 4 pole,35/36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 400 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing(a) MCCB 160 amps, 4 pole, 25KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (b) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (c) MCCB 63 amps, 4 pole, 16 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos. (d) Digital timer with suitable contactor-01 No |
| 7 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. (61 SAPU near JCO block)Incoming(a) MCCB 100 amps, 4 pole,25 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 150 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing(a) MCCB 63 amps, 4 pole, 16 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 03 Nos. (b) Digital timer with suitable contactor-01 No |
| 8 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. (HRDC and SSA AC Plant)Incoming(a) MCCB 160 amps, 4 pole, 36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 250 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing(a) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (b) MCCB 63 amps, 4 pole, 16 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. |
| 9 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. (VIP Road and Near P-460)Incoming(a) MCCB 160 amps, 4 pole, 36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 250 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing(a) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos. |
| 10 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. (Near Block P-158, 199 Med Regiment JCO mess,61 SAPU and 199 Med Regiment Officer mess )Incoming(a) MCCB 160 amps, 4 pole,35/36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 250 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing(a) MCCB 100 amps, 4 pole, 25KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos. (b) MCCB 63 amps, 4 pole, 16 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos. |
| 11 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. (Signal Quarter Guard & Nirman vihar and behind Command mess)Incoming(a) MCCB 400 amps, 4 pole, 36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 600 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panel including, selector switch Outgoing(a) MCCB 250 amps, 4 pole,25 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos.(b) MCCB 160 amps, 4 pole, 25KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos. (c) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (d) MCCB 63 amps, 4 pole, 16 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos. (e) Digital timer with suitable contactor-01 No |
| 12 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. (Near P-161)Incoming(a) MCCB 400 amps, 4 pole, 36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 600 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panel including, selector switch Outgoing(a) MCCB 250 amps, 4 pole,25 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 03 Nos.(b) MCCB 160 amps, 4 pole, 25KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (c) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 Nos. (d) MCCB 63 amps, 4 pole, 16 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos. (e) Digital timer with suitable contactor-01 No |
| 13 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. (Transformer near Gas Agency Main Panel and near P-292)Incoming(a) MCCB 250 amps, 4 pole, 36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 400 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing(a) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 05 Nos. |
| 14 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. (SSA)Incoming(a) MCCB 200 amps, 4 pole,36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 300 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing(a) MCCB 160 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 03 Nos. (b) Digital timer with suitable contactor-01 No |
| 15 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT Panelout door type IP-54, floor mounted,compartmantalised and suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete withfollowingaccessories complete. (Golf ground near PH No:6 OH tank)Incoming(a) MCCB 200 amps, 4 pole,36 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No.(b) Bus bar electrolytic grade copper 300 Amp, 4 pole , not less than 100cm long mounted on insulators- 01 No.(c)LED indicating lamps (R, Y & B) -01 Set.(d)Digital voltmeterAmmeter with CT PTaccording to Capacity of Load of main panelincluding, selector switch Outgoing(a) MCCB 160 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (b) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. |
| 16 | M&L earthing complete as per electrical plate No. 3 of MES SSR Part-I with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, buried directly vertically in ground in a pitdepth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less then 1.5 metre below normal ground level connected to and including galvanised iron or steel earth strip 25mm x 4mm by means of bolts, nuts check nuts and washers of galvanised iron or steel.Earthing strip shall be protected by galvanised iron or steel pipe 40mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GImedium grade.The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete.(for panel) |
| 17 | Schedule of Credit |