| 1 | Taking down carefully unserviceable copper / aluminium point wiring (light, fan, bell socket or power) including all fittings such as switches, socket, ceiling roses , regulators and fittings complete and making good the disturbed surfaces complete all as specified and directed. |
| 2 | M&L for point wiring for one light/fan/bell with single core PVC insulated and unsheathed stranded FRLS copper conductor cable 1100 volts grade size 1.5 Sqmm (nominal area) in and including PVC conduit & PVC casing capping 20/25/32/40 mm width with one single core PVC insulated unsheathed 1.5 Sqmm (nominal area) stranded FRLS copper conductor as earth continuity wire and connected to earth dolly including PVC switch board onexisting wall surface for one light/fanpoint /bell point controlled by one number one way switch & making good the disturbed surface to match with existing surface/wall complete all as specified and as directed. Note: - (i) Rate quoted shall include provision of blank plates as per site requirement (No extra payment will be made for the same) |
| 3 | All as per Item No 2 here-in-before but for one 5 pin socket outlet 5 Amps on independent board with 1.5 Sqmm complete all as specified and as directed. |
| 4 | All as per Item No 2 here-in-before but One 3 pin socket outlet, 5 Amps on the same board with other switches, with cables 1.5 sq. mm size complete all as specified and as directed. |
| 5 | All as per ItemNo. 2 here-in-before but for one 5 pin socket outlet 15 Amps on independent board with 4 Sqmm copper cable FRLS & 4 Sqmm FRLScopper cable for earth continuity wire complete all as specified and as directed. |
| 6 | S&F for switch piano flush type 6 Amp single pole one way complete all as specified and as directed. |
| 7 | S&F for socket flush type 6 Amp 5 Pin complete complete all as specified andas directed. |
| 8 | S&F for switch socket combination 5 Pin 6 Amp universal complete all as specified and as directed. |
| 9 | S&F for switch socket combination 5 Pin, 6/15 Amp universal complete all as specified and as directed. |
| 10 | S & F ceiling rose, 3 phase/PVC/Polycarbonate, isolated body complete all as specified and as directed. |
| 11 | S & F call bell, ding dongAC 230 volts, single pole complete all as specified and as directed. |
| 12 | S & F bell push, flush type, 5 amp complete all as specified and and directed. |
| 13 | S & F Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittingscomplete all as specified and and directed. |
| 14 | S&F sub main wiring with 2 run of 4.0 Sqmm (nominal cross-sectional area) PVC insulated unsheathed single core copper cable FRLS working voltage 1100 volts grade conforming to IS-694 with stranded copper conductor in and including heavy duty rigid non-metallic PVC conduit & casing/caping (20/25/32/40 mm width) including size 4.0 sqmm (nominal cross sectional area) PVC insulated un-sheathed single core multi stranded copper conductor cable as earth continuity conductor connected to main switches/DB\"S or common earth dully complete all as specified and directed after taking down old sub main wiring complete and making good the disturbed surface complete all as specified and as directed. ( NOTE :- Two runs of 4.0 Sqmm pvc wire, one run of 4.0 Sqmm pvc wire and one run of pvc casing caping/ PVC conduit will be measured as one unitcomplete all as specified and and directed. |
| 15 | S&F sub main wiring with 2 run of 6.0 Sqmm (nominal cross-sectional area) PVC insulated unsheathed single core copper cable FRLS working voltage 1100 volts grade conforming to IS-694 with stranded copper conductor in and including heavy duty rigid non-metallic PVC conduit & casing/caping (20/25/32/40 mm width) including size 6.0 sqmm (nominal cross sectional area) PVC insulated un-sheathed single core multi stranded copper conductor cable as earth continuity conductor connected to main switches/DB\"S or common earth dully complete all as specified and directed after taking down old sub main wiring complete and making good the disturbed surface complete all as specified and as directed. ( NOTE :- Two runs of 6.0 Sqmm pvc wire, one run of 6.0 Sqmm pvc wire and one run of pvc casing caping/ PVC conduit will be measured as one unitcomplete all as specified and and directed. |
| 16 | S&F sheet metal enclosures for DB’s double door suitable for mounting of MCB’s/Isolators, 240 Volt, SPN, 4 way with built in bus bar complete after taking down old unserviceable DB\"s and including making good the distrubed surface and matching with existing colour complete all as specified and as directed. |
| 17 | S&Fsheet metal enclosures for DB’s double door suitable for mounting of MCB’s/Isolators, 240 Volt, SPN, 8 way with built in bus bar complete after taking down old unserviceable DB\"s and including making good the distrubed surface and matching with existing colour complete all as specified and asdirected. |
| 18 | S&Fsheet metal enclosures for DB’s double door suitable for mounting of MCB’s/Isolators, 240 Volt, SPN, 12 way with built in bus bar complete after taking down old unserviceable DB\"s and including making good the distrubed surface and matching with existing colour complete all as specified and asdirected. |
| 19 | S&F VTPN distribution board with provision of MCCB as incommer,double door suitable for mounting MCB\"s/Isolators, 415 Volt,4 way with built in 160A rated bus bar and with out MCCBcomplete after taking down old unserviceable DB\"s and including making good the distrubed surface and matching with existing colour complete all as specified and as directed. |
| 20 | M&L forMCCB, 4P, 415V, overload adjustable 0.63 - 0.8-1 x in short circuit fixed 63 Amps breaking capacity 16KA complete all as specified and as directed. |
| 21 | M & L for MCB, SP, 240V, 40 Amps and \" B \" series breaking capacity 10 KA ISI markedcomplete, all as specified and asdirected. |
| 22 | M & L for MCB, SP, 240V, 6 to 32 Amps and \" C \" series breaking capacity 10 KA ISI markedcomplete, all as specified and as directed. |
| 23 | M & L for MCB, SPN, 240 V, 40 to 63A Amps, and ‘C’ series breaking capacity 10 KA complete ISI marked , all as specified and as directed. |
| 24 | Supply and fix ceiling fan regulator electronic Step type, solid state, 120W, 2 module, 240 volts,complete all as specified and as directed. |
| 25 | S&F metal clad box enclosure with socket plugtop and MCB SP 20 Amp flush of 240v mounting enclosure with 2 pin earth plug socketcomplete all as specified and directed . |
| 26 | S&F in repair for wall mounted LED 4 feet 20 Wattfittingswith high diffuser ,driver holder extruded aluminium heat sink provided for energy efficient heat dissipation &integrated electronicinclall accessories and lamp ,internally prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and and directed. |
| 27 | S&F in repair for wall mounted LED 2 feet 10 Wattfittingswith high diffuser ,driver holder extruded aluminium heat sink provided for energy efficient heat dissipation &integrated electronicinclall accessories and lamp ,internally prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable sizecomplete all as specified and and directed. |
| 28 | S & F conical/globe shaped post top lantern LED type 40 Watt 230 V AC outdoor type with decorative top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete incl. fittings viz. tube bends, tubes, etc to mountcomplete all as specified and and directed. |
| 29 | Supply and fixing LED luminaire 600 mm x 600 mm, 40 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable sizecomplete all as specified and and directed. |
| 30 | Supply and fixing round shape 12 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable sizecomplete all as specified and and directed. |
| 31 | S & F LED light fitting 1x9W/1X10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and and directed. |
| 32 | M&L for earthing complete with galvanised steel earth plate electrode 600x600x 6mm thick burried in ground (earth pit not less than 2.25 m deep below ground level0with top edge of the plate not less than 1.5 m below normal ground level, connected to GI strip 25x4 mm as earthing lead by means of bolts, nuts, check nuts, and washers of GI or steel, GI strip protected by 40 mm bore medium grade GI pipe and other end connected to earth test point as directed including funnel with watering pipe 20 mm bore light grade GI, wire mesh charcoal or coke common salt laid in altrnative layer of 15 cm (complete thickness) all round the earth electrode, concrete earth pit in PCC(1:3:6) type C-1, 50 mm thick pre-cast RCC(1:2:4) type B-1 normally mix cover slab reinforced with in 8 mm dia TMT bar 10 cm C/C both ways and single handle of 10 mm dia round bar including necessary excavation, earth work etc. in soft/loose/hard soil and disposal of soil to a distance n.exc 50 m and necessry testing on completion all as shown in electrical plate No 3 MES schedule part-I complete all as specified and as directed. |
| 33 | M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 8 mm galvanised iron or steel wire,complete all as specified and and directed. |
| 34 | Dismantling complete ceiling fan of size 1200/1400/1500 mm sweep down rod with its canopies, shackle, condenser housing with its rubber bushes, split pins, unscrewing the body parts of ceiling fan, taking out stator, motor winding, ball bearing, gun metal bush etc.complete all as specified and and directed to carry out the following repairs :- (a) Removing of burnt out fan winding and re-winding of motorwith suitable size of copper enamelled wire, varnishing, heating as per manufractures design and directed and re-assembling (b)New spare parts (i.e) rubber bush of shackle and condenser housing, gun metal bushes, ball bearing, shaft, twin twisted copper cableshall be measured and paid separately under relevant item. |
| 35 | Supply and fixing rubber bush for shackle with bolt, nut and lock pin suitable for ceiling fan 1200/1400 mm sweepcomplete all as specified and and directed. |
| 36 | Supply and fixingbearing number of 6201/6202/6203/6204 as required, complete all as specified and and directed .Make : SKF/NBC or Equivalent make as specified. |
| 37 | Supply and fixing condenser 2/2.5/3.15 Mfdcomplete all as specified and and directed. |
| 38 | Supply and fixing PVC holder for condenser housingcomplete all as specified and and directed. |
| 39 | Supply and fixingtwin core twistedcopper flexible wire/cable of size 0.5 sqmm, single corecomplete all as specified and and directed |
| 40 | Supply and fixingonlygun metal bushcomplete all as specified and and directed . . |
| 41 | Supply and Fix Ceiling fan shaft suitable for 1200/1400/1500 mm sweep fans, size 9 inches to 18 inches complete all as specified. |
| 42 | Taking down ceiling fan and Complete painting of ceiling fan by scraping with brush / removing old spray paint with the help of paint remover chemical and spray painting with two coat of synthetic enamelled paint with super glossy finish (grey/brown/white) with the help of spray painting machine and writing Ceiling fan Nos with paint and refixing the same complete all as specified and and directed. |
| 43 | Dismantling complete exhaust fan of size 350/400/450 mm sweep with condenser housing unscrewing the body parts of ehaust fan, taking out stator, motor winding, ball bearing, gun metal bush etc complete all as specified and and directedto carry out the following repairs :- (a) Removing of burnt out fan winding and re-winding of motorwith suitable size of copper enamelled wire, varnishing, heating as per manufractures design and directed and re-assembling (b)New spare parts (i.e) condenser housing, gun metal bushes, ball bearing, shaft twin twisted copper cableshall be measured and paid separately under relevant item. |
| 44 | Supply and Fix exhaust fan shaft suitable for 350/400/450 mm sweep fans, complete all as specified and directed. |
| 45 | Supply and fixing Switch modular type, single pole, one way, 5/6 Amp, one module, completes all as specified and directed. |
| 46 | Supply and fixingsocket outlet multipurpose having provision for 6 A-2/3 pin combined, two modulecomplete all as specified and and directed. |
| 47 | Supply and fixing Switch modular type, single pole, one way, and 15/16 Amps, one modulecomplete all as specified and and directed. |
| 48 | Supply and fixing socket outlet multipurpose having provision for 6/16 Amp-2/3 pin, combined 2 module completes all as specified and directed. |
| 49 | Supply and fixing Gong Bells, single phase, 230 V AC, 22 cms (9\"), Aluminium Cast Body, Dust and weather proof, wall mounted complete all as specified and directed.(Make: Kheraj GB-22or Equivalent make as specified.) |
| 50 | S&F White cover plate with frame,1 modulecomplete all as specified and and directed. |
| 51 | S&F White cover plate with frame,2 modulecomplete all as specified and and directed. . |
| 52 | S&F White cover plate with frame,3 module complete all as specified and and directed. |
| 53 | S&F White cover plate with frame,6 module complete all as specified and and directed. |
| 54 | S&F White cover plate with frame,8 module complete all as specified and and directed. |
| 55 | S&F White cover plate with frame,4 module complete all as specified and and directed. |
| 56 | S&F Metal flush box 1 modulecomplete all as specified and and directed. |
| 57 | S&F Metal flush box 2 module complete all as specified and and directed. |
| 58 | S&F Metal flush box 3 modulecomplete all as specified and and directed. |
| 59 | S&F Metal flush box 6 modulecomplete all as specified and and directed. |
| 60 | S&F Metal flush box 8 modulecomplete all as specified and and directed. |
| 61 | S&F Metal flush box 4 modulecomplete all as specified and and directed. |