| 1 | M&L in replacement for feeder pillersbox factory made -out door type made out of MS sheet (CRCA) of thickness not less that 3 mm of size 75 x 75 x 45 cm with aluminium bus bar strip 4 Nos of250 Amps rated suitable for 1100 volt (LT) mounted on LT porcelain insulator front opening door two leafbraced with hinged, mounted on 4 Nos ofangle iron 50x50x6 mm duly welded with box and grouted in PCC block of size 30cmx30cmx 15cm in concrete 1:3:6 (Type C-1) using 20 mm graded stone aggregate. Top of box MS sheet duly bent in/slope, tapper with projection of 30 mm on all side, weather/vermin proof with high quality of rubber beeding on panel door, cable entry arrangements at bottom includes earthing terminals 2 Nos at both side and painted with two coats of smoke grey synthetic enameled paint over a primer coat including providing MCCB, 4 pole,fixed type 200 Amps, 36 KA rating-01 No, complete all as specified and directed. |
| 2 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet (CPRI Aprroved), outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glands, thimbles etc.The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixedin ground in and including PCC block of size 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15 mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed.(a)04 strips ofAluminium bus bars with insulation colour sleeves of capacity 1000 Amp fixed on PVC heat shrinkable insulator heavy duty.(b)Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c)Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d)Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e)MCCB 3 phase, 415 volts, 4 pole 36 KA, 630Amp -01No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 36 KA, 200Amp -02Nos (outgoing)(g)MCCB 3 phase, 415 volts, 4 pole 25 KA, 160Amp -01 No (outgoing)(h)MCCB 3 phase, 415 volts, 4 pole 25 KA, 125Amp -01 No (outgoing)(j)MCCB 3 phase, 415 volts, 4 pole 25 KA, 100 Amp -02 Nos (outgoing) |
| 3 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet (CPRI Approved), outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glands, thimbles etc.The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixedin ground in and including PCC block of size 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15 mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed.(a)04 strips ofAluminium bus bars with insulation colour sleeves of capacity 600 Amp fixed on PVC heat shrinkable insulator heavy duty.(b)Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c)Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d)Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e)MCCB 3 phase, 415 volts, 4 pole 25 KA, 315 Amp -01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 25 KA, 100 Amp -02 Nos (outgoing)(g)MCCB 3 phase, 415 volts, 4 pole 25 KA, 160Amp -01 No (outgoing)(h)MCCB 3 phase, 415 volts, 4 pole 25 KA, 63 Amp -02 Nos (outgoing)(j) On load Change over switch 4 pole, 25 KA, 100 Amp -01 No |
| 4 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet (CPRI approved), outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glants, thimbles etc.The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixedin ground in and including PCC block of size 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed.(a)04 strips ofAluminium bus bars with insulation colour sleeves of capacity 600 Amp fixed on PVC heat shrinkable insulator heavy duty.(b)Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c)Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d)Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e)MCCB 3 phase, 415 volts, 4 pole 36 KA, 400 Amp -01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 25 KA, 100 Amp -06 No (outgoing) |
| 5 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet (CPRI approved), outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glants, thimbles etc.The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixedin ground in and including PCC block of size 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed.(a)04 strips ofAluminium bus bars with insulation colour sleeves of capacity 600 Amp fixed on PVC heat shrinkable insulator heavy duty.(b)Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c)Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d)Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) MCCB 3 phase, 415 volts, 4 pole 36 KA, 315 Amp -01 No (incoming)(f)MCCB 3 phase, 415 volts, 4 pole 25 KA, 100Amp -05 Nos(outgoing) |
| 6 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet (CPRI approved), outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glants, thimbles etc.The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixedin ground in and including PCC block of size of 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15 mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed.(a)04 strips ofAluminium bus bars with insulation colour sleeves of capacity 600 Amp fixed on PVC heat shrinkable insulator heavy duty.(b)Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c)Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d)Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e)MCCB 3 phase, 415 volts, 4 pole 36 KA, 250 Amp -01 No (incoming)(f)MCCB 3 phase, 415 volts, 4 pole 36 KA, 100Amp -03 Nos(outgoing)(g) MCCB 3 phase, 415 volts, 4 pole 25 KA, 160 Amp -01 Nos(outgoing) |
| 7 | Note for Sl Item No : 2 to 6 :(i)Layout diagram of panel shall be produced by contractor for approval of Accepting Officer before placing order to manufacturer and panel shall be brought at site as per approved drawing.(ii) Contractor is required to submit purchase vouchers, e-way bill and test certificates while claiming payment of LT panels. |
| 8 | S&F in replacement MCB 63 Amp TPN, complete all as specified and directed. |
| 9 | S&F in repairs MCCB 63 Amp, 4 pole, 25 KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu, complete all as specified and as directed. |
| 10 | S&F in repairs MCCB 100 Amp, 4 pole, 25 KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu, complete all as specified and as directed. |
| 11 | S&F in repairs MCCB 160 Amp, 4 pole, 25KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu, complete all as specified and as directed. |
| 12 | S&F in repairs MCCB 200 Amp, 4 pole, 25KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu, complete all as specified and as directed. |
| 13 | S&F in repairs MCCB 250 Amp, 4 pole, 36 KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu, complete all as specified and as directed. |
| 14 | S&F in repairs MCCB 315 Amp / 320 Amp, 4 pole, 36KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu, complete all as specified and as directed. |
| 15 | S&F in repairs MCCB 400 Amp, 4 pole, 36 KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu, complete all as specified and as directed. |
| 16 | S&F in repairs MCCB 630 Amp, 4 pole, 36 KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu, complete all as specified and as directed. |
| 17 | Material and Labour for inspecting and servicing of Oil cooled / air cooled servo controlled voltage stabilizer of 16 KVA to 30 KVA, 415V, 50 Hz, three phase capacities installed at various locations within Air Force Station Halwara by cleaning the complete unit with suitable cleaning agent and checking the serviceability state ofall the switchgears/ components such as variacs, ECC box, stepper motors, RC networks, control PCB, Carbon Brushes, sensing transformers, synchronising motor, drive gears etc complete and replacing the defective spare parts and testing for proper fuctioning, complete all as specified and as directed. Note : Components/ spare parts will be measured and paid separately under relevant items of Schedule \"A\", as \"Supply only\" however the the cost of suitable wires, lugs, nuts, bolts and washers required for control wiring shall deemed to be included in quoted rate. |
| 18 | All as per Sl Item No 16 above but 50 to 60 KVA, 415V, 50 Hz, three phase. |
| 19 | All as per Sl Item No 16 above but 100 to 160 KVA, 415V, 50 Hz, three phase. |
| 20 | All as per Sl Item No 16 above but 200 to 300 KVA, 415V, 50 Hz, three phase. |
| 21 | All as per Sl Item No 16 above but 500 KVA, 415V, 50 Hz, three phase. |
| 22 | All as per Sl Item No 16 above but 630 KVA, 415V, 50 Hz, three phase. |
| 23 | All as per Sl Item No 16 above but 750 KVA, 415V, 50 Hz, three phase. |
| 24 | Supply only AC stepper motor of capacity 3Kg/CMsuitable for Servo controlled voltage stabilizer, complete all as specified and as directed. |
| 25 | Supply only AC stepper motor of capacity 10Kg/CMsuitable for servo controlled voltage stabilizer, complete all as specified and as directed. |
| 26 | Supply only motor gear and variac shaft gear set suitable for servo controlled voltage stabilizer, complete all as specified and as directed. |
| 27 | Supply onlyRC Network 3Kg/CM to 10 Kg/CM suitable for servo controlled voltage stabilizer, complete all as specified and as directed. |
| 28 | Supply only sensing transformer with triac board, complete all as specified and as directed. |
| 29 | Supply only voltmeter 0 to 500 V of existing type suitable for existing servo controlled voltage stabilizer, complete all as specified and as directed. |
| 30 | Supply only limit switches suitable for existing servo controlled voltage stabilizer, complete all as specified and as directed. |
| 31 | Supply only POT meters suitable for existing servo controlled voltage stabilizer, complete all as specified and as directed. |
| 32 | Supply only carbon brushes of various capacity suitable for existing servo controlled voltage stabilizer, complete all as specified and as directed. |
| 33 | Supply only VARIAC of rating upto 15A suitable for existing servo controlled voltage stabilizer, complete all as specified and as directed. |
| 34 | Supply only VARIAC of rating above 35A and upto 200A suitable for existing servo controlled voltage stabilizer, complete all as specified and as directed. |
| 35 | Supply only VARIAC of rating above 100A and upto 200A suitable for existing servo controlled voltage stabilizer, complete all as specified and as directed. |
| 36 | Supply only digital servo controller for servo voltage stabilizer of all capacity, complete all as specified and as directed. |
| 37 | Material and labour for Filtration / dehydration of transformer oil of oil cooled servo voltage stabilizer of various capacities installed at various locations within Air Force Station with mobile type filtration plant to achieve di-electric strength of 30 KV for 1 minute at 2.5mm gap as per relevant IS including testing and recording the values of dielectric strength of oil before and after filtration at site with transformer oil testing machine, complete all as specified and as directed. |
| 38 | Supply and Topping up of transformer oil into the body of servo controlled voltage stabilizer to the desired level, complete all as specified and as directed. |
| 39 | Taking out of burnt winding from the unserviceable voltage stabilizer of any capacity,cleaning all the limbs, rewinding with supper enamelled wire of same weight, gauge etc of winding with suitable gauge by calculating number of turns as per voltage of voltage stablizer, varnishing and drying by vaccum impregnating, replacing insulating material, nuts,bolt etc including testing as per latest IS/BS specification to make it functional compete all as specified and as directed. |
| 40 | M&L for opening of all electrical connections from existing LT panel & unserviceable LT panel door from existing position/location, of any make & specifications any of capacity & transporting (To and Fro) to the authorised / approved workshop for repairs with opening of all mechanical parts from the LT panel,inspecting the same to assess the repairs required, cleaning , greasing and overhauling of complete panel, re-assembling after repainting the entire panel connecting all electrical/mechanical connections, commissioning and testing the same, complete all as specified & as directed. Note :- (1) Any welding work reqd at site or at work shop, Rates for the same deemed to be included in quoated prices. (2) Transportation charges are included the cost of loading / unloading, Toll taxes, insurance etc and quoted rate shall deemed to be included fo this provision.(3)A Board of Officers shall be appointed by the accepting officer for ascertaining the repair work required in LT Panels and all inventory shall be prepared in presence of Engr-in-Charge and contractor. |