| 1 | Supplying and laying in replacement of GI tubing medium grade for cable protection in trenches/duct/fixing to pole/wall or in such similar position of following size all as specified and directed by Engr-in-Charge:- |
| 2 | 100 mm bore |
| 3 | 80 mm bore |
| 4 | 50 mm bore |
| 5 | Taking up old unserviceable LT UG cables from trench/poles/wall etc of following size all as specified and directed by Engr-in-Charge:- |
| 6 | 95 Sqmm 3.5 core |
| 7 | 120Sqmm 3.5 core |
| 8 | 185Sqmm 3.5 core |
| 9 | 240Sqmm 3.5 core |
| 10 | 300Sqmm 3.5 core |
| 11 | 400Sqmm 3.5 core |
| 12 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of following sizes all as specified and directed by Engr-in-Charge:- |
| 13 | 95 Sqmm 3.5 core |
| 14 | 120Sqmm 3.5 core |
| 15 | 185Sqmm 3.5 core |
| 16 | 240Sqmm 3.5 core |
| 17 | 300Sqmm 3.5 core |
| 18 | 400Sqmm 3.5 core |
| 19 | Supply & laying in replacement Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 90 mm and inner dia 76 mm polethylene including couplers, bends, cap etc.,with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed by Engr-in-Charge:- |
| 20 | Description all as per ser item No 4.00 here-in-before but outer dia of 110 mm and inner dia 95 mm. |
| 21 | Description all as per ser item No 4.00 here-in-before but outer dia of 120 mm and inner dia 103.5 mm. |
| 22 | Description all as per ser item No 4.00 here-in-before but outer dia of 160mm and inner dia 126 mm. |
| 23 | M/L for providing earthing complete with Copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick buried directly in ground earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to copper earth strip 20 x 3 mmby means of bolts, nuts, check nuts & washers of copper and connecting to earth dolly all as shown in electrical plate No. 3 of SSR Part I of 2009 & & as specified or indicated and testing on completion including exaction/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete ( 1: 2 : 4 ) type B 1 ( reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm),funnel with wire mesh, watering pipe of 20 mm bore medium grade and lugs,including copper earth strip 20 x 3 mmwith GI protection pipe of 25 mm medium grade 7.5 meter long, etc complete all as specified. |
| 24 | Material and labour for earthing complete with Galvanized iron plate 60x60 cm x 6 mm thick electrode buried directly in ground (earth pit no less than 2.25 Mtrs deep below ground level) with top edge of the plate not less than 1.5 Mtrs below normal ground level connected to glavnasied earth lead 32X6 mmby means of bolts, nuts, check nuts and washers all as shown in electrical plate no. 5 connected to earth test point and provn of GI pipe 20 mm dia medium grade for watering, GI pipe 40 mm dia light grade for earth strip protectionall as specified and including excavation, earth workprovn ofearth pit, pit cover, CI funnel, wire mesh etccomplete and testing on completion. |
| 25 | S & F GI earth continuity conductor or main earthing lead of size 32X6 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as directed. |
| 26 | S & F copper earth continuity conductor or main earthing lead of size 25x3 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as directed. |
| 27 | Supplying and laying in replacement of GI tubing light grade 40mm bore forprotection of strip fixing to pole/wall or in such similar position complete all as directed. |
| 28 | M&L for providing cement concrete Type B1 1:2:4 (using 20mm graded stone aggregate ) as in hard standing after laying cable under road etc all as specified and directed. |
| 29 | M&L for cutting of road for passing Cables under road along with GI pipescomplete all as specified and directed. |
| 30 | Design, Supply, installing testing and commissioning factory fabricated In door type totally enclosed LT cubical panel board suitable size with busbar, conforming to relevant IS and protection class IP-65 ,dust,vermin and weather proof fabricated out of 3.15mm thick CRCA sheet duly powder coated ,mounted on 40x40x5mm MS angle iron frame,duly welded in shape and coated with two coats of synthetic enamel paint of approved colour over a coat of red oxide primer including necessary grouting of legs 300mm deep in ground in PCC 1:4:8 type D2 using 40mm graded stone aggregate ,panel base to be 500mm above ground level with suitable compartments for controls and Monitors including cable glands for incoming and outgoing cables,locking arrangement, including accomodating, supply and fixing the following accessories/items including necessary internal panel wiring with suitable size of Copper wire PVC insulated & sheathed multi stranded complete all as specified and as directed by Engr-in-charge. Including Supply and fixing the following :- |
| 31 | (a) ACB 800 Amps 4 Pole -01 No (Incoming)(b) MCCB 630 AMPs 4 Pole 50KA-01(c) Euroload , On load Change over switch 4 pole 630 AMPs-02 Nos(d) Voltmeter 0-500V with selector switch (Digital type)-01 No (e) Ammeter 0-50 Amps with CTs (50/5Amps) and selector switch(Digital type)-01 No(f) Indicating lamps (RYB) -01 Set(g) PCC Foundation (Civil works) for grouting of panel(h) Bus bar 1200 Amps |
| 32 | Design, Supply, installing testing and commissioning factory fabricated In door type totally enclosed LT cubical panel board suitable size with busbar, conforming to relevant IS and protection class IP-65 ,dust,vermin and weather proof fabricated out of 3.15mm thick CRCA sheet duly powder coated ,mounted on 40x40x5mm MS angle iron frame,duly welded in shape and coated with two coats of synthetic enamel paint of approved colour over a coat of red oxide primer including necessary grouting of legs 300mm deep in ground in PCC 1:4:8 type D2 using 40mm graded stone aggregate ,panel base to be 500mm above ground level with suitable compartments for controls and Monitors including cable glands for incoming and outgoing cables,locking arrangement, including accomodating, supply and fixing the following accessories/items including necessary internal panel wiring with suitable size of Copper wire PVC insulated & sheathed multi stranded complete all as specified and as directed by Engr-in-charge. Including Supply and fixing the following :- |
| 33 | (a) MCCB 630Amps 4 pole 415 V with rupturing capacity 50 KA-1 No (incoming)(b) MCCB 4 Pole 400 Amps 4 pole 36 KA-01 Nos -03 Nos (Outgoing)(c) MCCB TPN 100 Amps 50 Hz, 415 V with rupturing capacity 25 KA - 01 Nos (Outgoing)(d) Voltmeter 0-500V with selector switch (Digital type)-01 No(e) Ammeter 0-50 Amps with CTs (50/5Amps) and selector switch(Digital type)-01 No(f) Indicating lamps (RYB) -01 Set(g) PCC Foundation (Civil works) for grouting of panel(h) Bus bar 600 Amps |
| 34 | Design, Supply, installing testing and commissioning factory fabricated In door type totally enclosed LT cubical panel board suitable size with busbar, conforming to relevant IS and protection class IP-65 ,dust,vermin and weather proof fabricated out of 3.15mm thick CRCA sheet duly powder coated ,mounted on 40x40x5mm MS angle iron frame,duly welded in shape and coated with two coats of synthetic enamel paint of approved colour over a coat of red oxide primer including necessary grouting of legs 300mm deep in ground in PCC 1:4:8 type D2 using 40mm graded stone aggregate ,panel base to be 500mm above ground level with suitable compartments for controls and Monitors including cable glands for incoming and outgoing cables,locking arrangement, including accomodating, supply and fixing the following accessories/items including necessary internal panel wiring with suitable size of Copper wire PVC insulated & sheathed multi stranded complete all as specified and as directed by Engr-in-charge. Including Supply and fixing the following :- |
| 35 | (a) MCCB 400 Amps Amps 4 Pole 36 KA -03 No (one Incoming for DG and one for Main)(b) Euroload , On load Change over switch 4 pole 400 AMPs-02 ( One for two DG and one for DG and Main(c) MCCB 4P 320 Amps 36 KA 50 Hz, 415 V with rupturing capacity 36 KA-2 No (Outgoing)(d) MCCB 4P 250 Amps 25 KA 50 Hz, 415 V with rupturing capacity 35 KA-01 Nos (Outgoing)(e) Voltmeter 0-500V with selector switch (Digital type)-01 No (f) Ammeter 0-50 Amps with CTs (50/5Amps) and selector switch(Digital type)-01 No(g) Indicating lamps (RYB) -01 Set(h) PCC Foundation (Civil works) for grouting of panel(j) Bus bar 1200 Amps |
| 36 | Design, Supply, installing testing and commissioning factory fabricated In door type totally enclosed LT cubical panel board suitable size with busbar, conforming to relevant IS and protection class IP-65 ,dust,vermin and weather proof fabricated out of 3.15mm thick CRCA sheet duly powder coated ,mounted on 40x40x5mm MS angle iron frame,duly welded in shape and coated with two coats of synthetic enamel paint of approved colour over a coat of red oxide primer including necessary grouting of legs 300mm deep in ground in PCC 1:4:8 type D2 using 40mm graded stone aggregate ,panel base to be 500mm above ground level with suitable compartments for controls and Monitors including cable glands for incoming and outgoing cables,locking arrangement, including accomodating, supply and fixing the following accessories/items including necessary internal panel wiring with suitable size of Copper wire PVC insulated & sheathed multi stranded complete all as specified and as directed by Engr-in-charge. Including Supply and fixing the following :- |
| 37 | (a) MCCB TPN 400 Amps 36 KA 50 Hz, 415 V -1 No (Incoming) (b) Change over switch Euroload type 400 Amps 4 pole-02 Nos (c) MCCB 4 pole 250 Amps 50 Hz, 415 V with rupturing capacity 35 KA-03 Nos (Outgoing)(d) MCCB 4 Pole 160 Amps 25 KA - 02 Nos (e) MCCB 100 Amps 4 pole 16 KA- 02 Nos (f) Voltmeter 0-500V with selector switch (Digital type)-01 No (g) Ammeter 0-50 Amps with CTs (50/5Amps) and selector switch(Digital type)-01 No (h) Indicating lamps (RYB) -01 Set (j) PCC Foundation (Civil works) for grouting of panel (k) Bus bar 1200 Amps |
| 38 | Design, Supply, installing testing and commissioning factory fabricated In door type totally enclosed LT cubical panel board suitable size with busbar, conforming to relevant IS and protection class IP-65 ,dust,vermin and weather proof fabricated out of 3.15mm thick CRCA sheet duly powder coated ,mounted on 40x40x5mm MS angle iron frame,duly welded in shape and coated with two coats of synthetic enamel paint of approved colour over a coat of red oxide primer including necessary grouting of legs 300mm deep in ground in PCC 1:4:8 type D2 using 40mm graded stone aggregate ,panel base to be 500mm above ground level with suitable compartments for controls and Monitors including cable glands for incoming and outgoing cables,locking arrangement, including accomodating, supply and fixing the following accessories/items including necessary internal panel wiring with suitable size of Copper wire PVC insulated & sheathed multi stranded complete all as specified and as directed by Engr-in-charge( For OMG gate supply) . Including Supply and fixing the following :- |
| 39 | (a) MCCB 630 Amps 4 Pole 50 KA -01 Nos ( Incomming) (b) Voltmeter 0-500V with selector switch (Digital type)-01 No(c) Ammeter 0-50 Amps with CTs (50/5Amps) and selector switch(Digital type)-01 No(d) Indicating lamps (RYB) -01 Set(e) PCC Foundation (Civil works) for grouting of panel(f) BUs bar 1000 Amps Busbar for out going. |
| 40 | Design, Supply, installing testing and commissioning factory fabricated In door type totally enclosed LT cubical panel board suitable size with busbar, conforming to relevant IS and protection class IP-65 ,dust,vermin and weather proof fabricated out of 3.15mm thick CRCA sheet duly powder coated ,mounted on 40x40x5mm MS angle iron frame,duly welded in shape and coated with two coats of synthetic enamel paint of approved colour over a coat of red oxide primer including necessary grouting of legs 300mm deep in ground in PCC 1:4:8 type D2 using 40mm graded stone aggregate ,panel base to be 500mm above ground level with suitable compartments for controls and Monitors including cable glands for incoming and outgoing cables,locking arrangement, including accomodating, supply and fixing the following accessories/items including necessary internal panel wiring with suitable size of Copper wire PVC insulated & sheathed multi stranded complete all as specified and as directed by Engr-in-charge. Including Supply and fixing the following :- |
| 41 | (a) MCCB 4P 250 Amps 50 Hz, 415 V with rupturing capacity 35 KA-01 Nos (Incomming)(b) MCCB 4P 160 Amps 50 Hz, 415 V with rupturing capacity 35 KA - 03 Nos (Outgoing)(c) MCCB TPN 63 Amps 50 Hz, 415V with rupturing capacity 16 KA - 02 Nos(d) Voltmeter 0-500V with selector switch (Digital type) - 01 No(e) Ammeter 0-50 Amps with CTs (50/5Amps) and selector switch(Digital type)-01 No(f) Indicating lamps (RYB) -01 Set(g) PCC Foundation (Civil works) for grouting of panel(h) BUs bar 600 Amps |
| 42 | Supply , install , testing and commissioning of wire mesh cable tray hot dip galvanised type of size of 105 mm height X 600 mm width, 3 meter length each as per EN 12329 and IEC 61537 with wire diameter of 3.9 to 5.9 mm and having SST of 550 Hrs tested , having E30/E90 certification, with following specification, complete all as specfied and directed by Egnr-in-Charge.i) C41S/RCSN/R35 (wall/celling/ground mounting supports) every after 1 meter distance.ii) Kitaster coupler (Jointimg tray ) 5 sets per joint.iii) Down rod of 1 meter length each.iv) Nuts 3 nos for each rod.v) COUPFIL(Cutter) 01 No.vi) L supports for wall with all accessories such as nut ,bolt ,washers etc.Note :- a) Shifting of all existing HT and LT cables,Removing connections of these cables and refixing at its original position through cable trays in a proper manner all as directed by engr in charge is included in the quoted rates.b) All major and minor spares are required in laying of cables and fixing of cable trays which are not mention above are included in the quoted rates.c) All meterial such as cement ,concerete,tiles etc to make wall/roof /ground in its original shape after fixing of cable trays are included in the quoted rates. |
| 43 | Excavation in trenches n. exc. 1.5 mtr in wide and n. exc. 1.5 mtr in depth for laying of underground cable and getting out in soft/loose soil, complete all as specified and directed by Engr-in-Charge |
| 44 | Returning, filling in excavated soil in trenches including spreading, leveling, watering and well rammingin layers n. exc. 25 cm thick, complete all as specified and directed by Engr-in-Charge |
| 45 | Removing of excavted soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point, complete all as specified and directed by Engr-in-Charge |
| 46 | Dismantling iron sections as in chequred plate and frame work to plates in any size and position, complete all as specified and directed by Engr-in-Charge |
| 47 | S&F plates (plain or chequred) plate channels square cut or notched forming holes , without any attachement incl necessary welding , complete all as specified and directed by Engr-in-Charge |
| 48 | S&F Rolled sections as in main and cross beam, frame work to ducts for laying chequred plates and similar work including necessary welding, grouting using PCC 1:3:6 and making good to surface, complete all as specified and directed by Engr-in-Charge |
| 49 | M&L for applying two coats of synthetic enamel paint over a coat of red oxide, Zinc chrome primer on steel surfaces of any descrption , over 10cm width or girth, including preparing on new steel surfaces, complete all as specified and directed by Engr-in-Charge |