| 1 | All below item provided by contractor (Basic Rate with Frieght & Insurance Charges to be Quoted by bidder) |
| 2 | MS Channel 125x65, 3.2Mtr. Long 1,2,3,4 No Pieces for Top channe and Terminal & Busbar Gantry. 13.10 Kg/Mtr.+wastage. |
| 3 | MS Angles 50x50x6mm for bracing type members of T.G./B.G./Trench |
| 4 | MS Angles 75x75x8, 2.6mtr long, total 5.2 @ 8.9 Kg/Mtr. |
| 5 | MS Angles 75x75x6mm (6.8 Kg/Mtr.) for Neutral/Cable Stand |
| 6 | MS Angle 50x50x6 mm |
| 7 | MS Round of 32 mm dia for earthmat (6.1 Kg/Mtr.) |
| 8 | Rail Pcs of 90 Lbs 3.46M long 2 No. Pcs 6.92M @ 44.61 Kg./M |
| 9 | MS Channel 100x50 mm (9.6 Kg/Mtr.) for Cable Stand |
| 10 | M.S. Angle Iron 65x65x6mm, 4300 mm long 2/6/8 no. Bracing, with 4/12/16 clamps (5.8 kg./m) |
| 11 | M.S. Angle Iron 65x65x6, 3200mm long, 5.8 Kg/Mtr. for cable with clamp |
| 12 | Top channel 125X65mm, 3200 mm long (13.10 Kg./m) with clamp |
| 13 | MS Flat 50x6mm |
| 14 | MS Plate 200x150x8mm (12.6 Kg/mtr.) |
| 15 | GI Nuts & Bolts of Size with washers |
| 16 | 33 KV line/Bus type Isolator/LA/CT/PT/FS, clamps with Nuts and Bolts washers suitable for A.C.S.R. Dog/Panther conductor |
| 17 | PG Clamp for Weasel/dog/Panther |
| 18 | Transformer clamps/L-Piece |
| 19 | Copper Bond 0.5 mtr. long, 65x8mm suitable for 5/10 MVA T/F |
| 20 | Holding Clamp for cable /TPMO/Top Chennel/fuse/ST Pole-Cross arm /ST Pole-Stud Pole/ ST/PCC Pole-Guarding Angle/GI holding clamp etc. |
| 21 | Chemical Earthing GI Pipe 50 mm dia, 3 Mtr. long |
| 22 | GI Strip 50x6 mm |
| 23 | GI Barbed wire |
| 24 | Danger Board with clamps for 11 KV |
| 25 | Control cable 2x2.5 sq.mm. |
| 26 | Control cable 4x2.5 sq.mm. |
| 27 | Stone Pad 300x300x75 mm |
| 28 | Number Plates with clamp, nuts & bolts |
| 29 | Aluminium binding wire- 6 swg (0.5 kg./pole) |
| 30 | G.I. Pipe 6\" dia |
| 31 | Aluminium Paint |
| 32 | Red Oxide Paint |
| 33 | Erection, Installation, Fabrication and Commissioning of following items to be done by contractor As per RESPO drawing & Norms |
| 34 | MS Channel 125x65, 3.2Mtr. Long 1,2,3,4 No Pieces for Top channe and Terminal & Busbar Gantry. 13.10 Kg/Mtr.+wastage. |
| 35 | MS Angles 50x50x6mm for bracing type members of T.G./B.G./Trench |
| 36 | MS Angles 75x75x8, 2.6mtr long, total 5.2 @ 8.9 Kg/Mtr. |
| 37 | MS Angles 75x75x6mm (6.8 Kg/Mtr.) for Neutral/Cable Stand |
| 38 | MS Angle 50x50x6 mm |
| 39 | MS Round of 32 mm dia for earthmat (6.1 Kg/Mtr.) |
| 40 | Rail Pcs of 90 Lbs 3.46M long 2 No. Pcs 6.92M @ 44.61 Kg./M |
| 41 | MS Channel 100x50 mm (9.6 Kg/Mtr.) for Cable Stand |
| 42 | M.S. Angle Iron 65x65x6mm, 4300 mm long 2/6/8 no. Bracing, with 4/12/16 clamps (5.8 kg./m) |
| 43 | M.S. Angle Iron 65x65x6, 3200mm long, 5.8 Kg/Mtr. for cable with clamp |
| 44 | Top channel 125X65mm, 3200 mm long (13.10 Kg./m) with clamp |
| 45 | MS Flat 50x6mm |
| 46 | MS Plate 200x150x8mm (12.6 Kg/mtr.) |
| 47 | GI Nuts & Bolts of Size with washers |
| 48 | 33 KV line/Bus type Isolator/LA/CT/PT/FS, clamps with Nuts and Bolts washers suitable for A.C.S.R. Dog/Panther conductor |
| 49 | PG Clamp for Weasel/dog/Panther |
| 50 | Transformer clamps/L-Piece |
| 51 | Copper Bond 0.5 mtr. long, 65x8mm suitable for 5/10 MVA T/F |
| 52 | Holding Clamp for cable /TPMO/Top Chennel/fuse/ST Pole-Cross arm /ST Pole-Stud Pole/ ST/PCC Pole-Guarding Angle/GI holding clamp etc. |
| 53 | Chemical Earthing GI Pipe 50 mm dia, 3 Mtr. long |
| 54 | GI Strip 50x6 mm |
| 55 | GI Barbed wire |
| 56 | Danger Board with clamps for 11 KV |
| 57 | Stone Pad 300x300x75 mm |
| 58 | Number Plates with clamp, nuts & bolts |
| 59 | Aluminium binding wire- 6 swg (0.5 kg./pole) |
| 60 | G.I. Pipe 6\" dia |
| 61 | Aluminium Paint |
| 62 | Red Oxide Paint |
| 63 | Safe carriage, Shifting up JE dump store / side from any ESC Center of Jhansi Zone and Erection, Commissioning, Fabrication and installation of following items done by contractor As per RESPO drawing & Norms |
| 64 | 33 KV line Isolator |
| 65 | 33 KV Bus Isolator |
| 66 | Post Insulator |
| 67 | 33 KV Lightening Arrester |
| 68 | 33 KV VCB 800 Amp., 750 MVA |
| 69 | 33 KV CT 200/100/1 Amp. |
| 70 | 33 KV XLPE Cable 3x300 sq.mm. (Carriage only) |
| 71 | 11 KV 3x300 SQ MM XLPE Cable (Carriage only) |
| 72 | ACSR Panther Conductor |
| 73 | 33KV Polymeric Disc Insulator B&S 7000 Kg |
| 74 | 33 KV Disc fitting for Dog/Panther conductor |
| 75 | 33 KV Polymeric Pin Insulator With Nut & Washer |
| 76 | PCC Pole 8.5m long. |
| 77 | ST Pole 11 Mt Long-SP-55 |
| 78 | LT ABC conductor (3x50+1x35+1x16) |
| 79 | MS Earthing rod 20x2500 mm |
| 80 | GI Wire 6 SWG |
| 81 | 33 KV XLPE 3X300 sq.mmm C/J/Kit (Outdoor) |
| 82 | 11 KV 3x300 SQ MM XLPE Cable Jointing kit Outdoor |
| 83 | 11 KV 3x300 SQ MM XLPE Cable Jointing kit Indoor |
| 84 | Complete Stay (GI Stay rod 20x1800 mm, Stay 7/8 SWG 10 Kg.) |
| 85 | 33 KV VCB 800 Amp., 750 MVA (Old and Used ) |
| 86 | Cost of 33 KV Double T/f Control Pannel (Old and Used) |
| 87 | Cost of 33 KV Double Feeder Control Pannel (Old and Used) |
| 88 | Construction of plinth of size 3.46 x4.46 Mtr. For 5/10 MVA T/F having 0.45 Mtr. above ground level. The work also includes laying of 2 No. 3.46 mtr. long rail pieces complete with cutting, welding & proper fitting etc. The plinth will be made as per drawing and shall be plastered/ finished on top and sides of the plinth. |
| 89 | Painting of all S/S Structure as requied |
| 90 | Laying and Dressing of 11/33 kv 3x300 sqmm XLPE cable by digging method the cable shall with duly protected by brick, sand and stone slab & refiling, raiming of the left soil as per drawing. |
| 91 | 10 MVA & 8 MVA Power transformer HT/LT connection with proper jumpering, clamping, Cu L Piece and copper Net neutral connection etc. |
| 92 | Stucture instalatiion and Grounting of Neutral Stand (0.268 Cu.M.) in L shape & proper size and alignement |
| 93 | Stucture making, instalatiion and Grounting of cable support stand made of two piece chennel 100x50 mm 3.00 mtr long jointing to each other by means of MS flat and Plinthing of cable stand (1.0x0.75x0.5) |
| 94 | Earthing of power T/F & Structure by way of Boring & Lowering of 40 mm dia (1.5 inch) 2.5m thick GI B class pipe from ground up to the water level as per drawing with making of earth pit of chamber with cover (size 300x300x400mm) |
| 95 | Concreting of grouting of ST/PCC Poles (0.268 Cu.m/pole) |
| 96 | Stucture making, instalatiion and Grounting of Isolator Structure with 3.5 mtr hight as per drawing including CC 1:4:8, Grouting [(0.3x0.3x1.3)]x2 Mtr. with 0.3 Mtr. Above G.L. |
| 97 | Plastering in 1:4 12mm thick of LA, CT, PI, LI & BI Structure [(0.3x0.3)+(0.3x0.35)x2+(0.3x0.35)x2]x2 |
| 98 | Stucture making, instalatiion and Grounting of LA, CT, PT, FS, PI Structure 3.5 mtr hight as per drawing with CC grouting and all civil works |
| 99 | Construction of Control Cable trench of size 300x300mm and providing MS Strip at an interval of 0.5 Mt. and MS Angle (50x50x6mm) running on both the edges of trench. |
| 100 | Construction of welded frame type control cable trench cover 0.5 Mt. long suitable for trench including cost of MS/Tor Bar. |
| 101 | Making of cable J/kit |
| 102 | Concrte and Grouting of Stay set (0.108 Cu.m./Stay)) |
| 103 | Stucture making, instalatiion and Grounting of Terminal Gantry and 33KV main Bus Bar Structure- Gantry using rail pole and channel as per RESPO Drg. |
| 104 | Mounting & Commissioning of 120 watt. LED street light complete fitting and of standard quality ISI mark and laying of 2x6 sq. mm. aluminum cable from S.G. room to street light supports complete in all respect. |
| 105 | Plinth & Foundation of VCB as per drawing with all respect |
| 106 | Laying of LT ABC conductor (3x50+1x35+1x16) for switchyard Lightening with clamping & jointing and all respect |
| 107 | Soil filling of yard |
| 108 | Cost of Yard Leveling and Brick of Edge Bar |
| 109 | Removal of all connections safe lifting & Shiftng of 08 & 10 MVA Power T/f from exising plinth, Instalation, commissioning of Existing Power T/f include all connections jumpring etc at new plinth with removal of any leakage/sepage if required |
| 110 | Rearrangement, Laying and Dressing of Existing 11 KV 3x300 sqmm XLPE cable |
| 111 | Safe removal, shifting & dump at suitable place of existing two side 132 KV S/s switchyard fencing |
| 112 | Toe Wall Construction of Toe wall around the outdoor Switchyard of the S/s of size 0.75 Mt at Base and 0.23 Mt at top as per RESSPO Norms by lst class bricks in the ratio 1:6, Base concreting of the wall to be done in ratio 1:6:12 and plaster 12 mm thick in ratio 1:4.(All materials to be provided by Contractor). |
| 113 | Switchyard Fancing Fabrication of switchyard fencing with wire chain link fencing mesh D fence of as per drawing along with Fabrication of one number gate made of MS Angle 65x65x6mm, MS Channel 100x50mm, MS Flat 50x6mm, together with locking arrangement, its Installation including the cost of civil material, angle 50x50x6mm.(All materials to be provided by Contractor). Please Enable Macros to View BoQ information |