| 1 | Excavation in trenches notexceeding 1.5 mtr wide andnot exceeding 1.5 mtr deep for foundationof laying cable includinggetting out in soft/loose soil complete all as specifiedand directed. |
| 2 | Returning, filling in, including spreading , watering and well ramming in layers not exceeding 25cm complete all as directed. |
| 3 | Removing of surplus soil to distance not exceeding50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 4 | Material & labour for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed by Engineer-in-Charge. |
| 5 | Supplying & Laying Sub Class ”B’ bricks, old size, kiln burnt,laid with axis of brick perpendicularto the axis of the cable, for protection of cable all as specified and directed by Engineer-in-Charge. |
| 6 | Trenchless Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique (HDD) and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed by Engr-in- Charge. |
| 7 | Taking Out Old and Unserviceable XLPE Cable any size(300sqmm 3.5core /240/120/95/70/25/16/ 10/6sqmm4core/3.5 core) from trenches,pole,road,duct etc incl necessary joint Etc complet all as specified and directed. |
| 8 | S&Fcable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 sqmm3.5core XLPE Cable complete all as specified and directed. |
| 9 | Ditto as above but for size 240sqmm3.5 core XLPE Cable…ditto… |
| 10 | Ditto as above but for size120sqmm3.5 core XLPE Cable…ditto… |
| 11 | Ditto as above but for size 95Sqmm3.5 coreXLPE Cable…ditto… |
| 12 | Ditto as above but for size 70Sqmm3.5 core XLPE Cable…ditto… |
| 13 | Ditto as above but for size 35Sqmm3.5 core XLPE Cable…ditto… |
| 14 | Ditto as above but for size 25 Sqmm 4 Core XLPE Cable…ditto… |
| 15 | S&F in repair of aluminium lugs for fixing armoured cable in panel of for size from 10 to 16 sqmm 4 core cable complete all as specifie and directed. |
| 16 | Ditto as above but for sizefrom 25 to 35 sqmm 4 core cable…ditto… |
| 17 | Ditto as above but for size from 50 to 70 sqmm 3.5 core cable…ditto… |
| 18 | Ditto as above but for sizefrom 95 to 120 sqmm 3.5 core cable…ditto… |
| 19 | Ditto as above but for size from 150 to 185 sqmm 3.5 core cable…ditto… |
| 20 | Ditto as above but for size from 240 to 300 sqmm 3.5 core cable…ditto… |
| 21 | Relaying of existingserviceable undergroundcable of size16 to 300Sqmm of any core obtained from the items specified(i.e during taking out of under ground cable) complete all as specified and as directed. |
| 22 | Supply and fix cable jointing kit for 1.1KV grade cable for straight through joint complete with Jointing material (Epoxy Based) and accessories suitable for 3K/4 core XLPE armoured Al conductor cable of size from25 to 50sqmm cable complete all as specified and directed. |
| 23 | Ditto as above but for size from 70 to 95sqmm cable…ditto…… |
| 24 | Ditto as above but for size from 120 to l50sqmm cable…ditto…… |
| 25 | Ditto as above but for size from 185 to 300sqmm cable…ditto…… |
| 26 | M&L for machine spray painting of LT Panels by rubbing, scrapingof oldpaints withemery paper,cleaning and preparation ofsmooth surfacescomplete withapprovedqualitypaintallasspecifiedand directed by Engineer - in-Charge. |
| 27 | S&F in repair of Change overswitchON LoadtypeFront Handle Operated 63Amppole415Volts4 Pole confirmingtoIS13947-3insheetsteel enclosurefixingwithallasrequiredwithnutboltscomleteallas specifiedanddirected. Confrming to CatNo.ITASOO63ofindoasian oreuivalentto havells/HPL/C&G |
| 28 | S&F in repair ofChange over switchONLoad type Front Handle Operated l00Amppole 415 Volts 4 Poleconfirmingto IS 13947-3insheet steel enclosurefixingwithallasrequiredwithnutboltscomleteallas specifiedanddirected. Conforming to CatNo.lTASO100ofindoasian oreuivalentto havells/HPL/C&G |
| 29 | S&F in repair ofChange over switchON Load type FrontHandle Operated 200Amppole 415 Volts4 Poleconfirming to lS13947-3insheetsteel enclosurefixingwithallasrequiredwithnutboltscomleteallas specifiedanddirected. Conforming to CatNo.ITAS0100 ofindoasianofStandardor euivalent to havells/HPL/C&G |
| 30 | M&Lforearthingwithgalvanizedsteelearthplateelectrodeofsize600 x 600 x 6 mm buried directly in ground earth pit not less than 2.25 mtr below of normal ground levelwith top edgeof earth plate should notlessthan1.5mtrbelownormalgroundlevelandconnectedto galvanizedironstrip32x6mmbymeansofbolts,nuts,washersof galvanized iron or steel all as shown in electrical plate No.5 of MES SSR Part I connecting to earthing test point on completion with and including 15 mm bore GI light grade protection pipe (7.5 mtr long) for earth lead GI lead wire 4mm dia (7.5 mtr long), PCC pit with cover in PCC1:2:4typeB-1reinforcedwith8mmdia torbars @ 80mmC/C, 20mm dia medium grade watering pipe with funnel, wire mesh, commonsalt, charcoal, necessaryexcavationand earth work including dismantling of old existing earthing complete all as specified and directed by Engr- in- Chanrge(Note :- On testing after completion if desired earth resistence is not obtained, the earthing will be redone at no extra cost.) |
| 31 | S&F in repair ofIndicator lamp LED TypeRed,Yellow,Blueinto exting panel complete all as specified and directed. |
| 32 | S&F in repair ofdigitalVoltmeter0-600Volts, includingflxinginto exting panel complete all as specified and directed. |
| 33 | S&F in repair of digitalAmeter0-400Amps,includingfixingof into exting panel complete all as specified and directed. |
| 34 | S&F in repair ofSelector Switch (Three Phase)including fixing ofinto exting panel complete all as specified and directed. |
| 35 | S&F in repair CurrentTransformer Ratio100/5A,240VoltAC indoortape insulatedringtypeLT CurrentTransformerandincluding connecting wire and connected with panel busbar comleted as per EIC. |
| 36 | M&L for disconnecting burnt end or portion of 10 sq mm to 185 Sq mm 31/2corecableremovingthecablefromloopincludingnecessary excavation,earthwork,removingbrickprotectionandrealayingthe same,and reconnectingthecableby removingburntprotionof cable andpreparingfreshterminalsofLTcabletopole/mainswitchetc complete all as specified. |
| 37 | Repair of LT Panel /Bus bar chamber of any make and size and replace allrustedpartsincludingdoorandroofandbroken/damaged hinges with locking arrangementincludingpaining of complete panel complete all as specified and directed |