| 1 | Supplying, installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4- 5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP- 66,IK-10, CRI >80 , under voltage and over voltage protection,EMIEMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 72 Watt |
| 2 | Fabrication, supply & erection of 5.0 mtr height, 3 mm thick, bottom dia of 130mm & top dia of 70mm base plate of size 225 x 225 x 12 mm thick flange mounted hot dip galvanized octagonal pole made from HT steel plate, window with flash cover with full vertical window cover at appropriate height from the base plate on existing cement concrete pedestal as required. i/c supplying and fixing of 6 mm thick laminated mounted sheet inside the window mounted on and i/c providing and welding 3 nos. GI strips 4 mm thick of suitable length and having suitable size tapped holes as reqd, terminal block suitable for 25 sq mm conductor - 4 nos. shorting links on DIN channel i/cpdg and fixing DIN channel of suitable length,, 6 Amp. SPMCB\"C\" curvecharacteristics, earth stud, cable support clamp suitable for upto 4x25 sqmm cable. Logo/Name of manufacturer shall be embossed on the pole. Galvanization as per relevant IS.code etc as required. |
| 3 | Providing and laying in position M25 grade reinforced cement concrete foundation of size 450 mm (L) ×450 mm wide and 1000 mm deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia- 960 mm long(approx)-8 nos. and reinforcement of cold twisted bars of 8 mm dia- 1400 mm (approx) -6 nos.(with 150 mm spacing) as required with supplying and positioning of 4 nos. foundation bolts 16 mm dia,600 mm long, J type i/c 2 nos. template anchor plates of size 225mm×225mm×3mm and providing DWC HDPE for cable entry and exit as required for 3 m and 5 mtr pole. |
| 4 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 5 | Providing and fixing 6 SWG dia GI Wire on surface or in recessed for loop earthing as required. |
| 6 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.(a)Upto 35 sq. mm |
| 7 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. (a)Upto 35 sq. mm |
| 8 | S & L of following size DWCHDPE pipe ISI marked along withall accessoried like socket ,bend,couplers etc. Confirming to Is 14930, Part II complete with fittings and cutting jointing etc. Diret in ground (75 Cm below ground level) including excavation and refilling the trench but excluding sandcushioning and protective covring etc. complete as reqd. (a) 63 mm dia (OD-63mm & ID-51 mm nominal.) |
| 9 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (a) 3 x 1.5 sq .mm |
| 10 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a)63 A |
| 11 | Supplying and Fixing following rating, four pole,(three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections , testing and commissioning etc. as required .(a) 25 A |
| 12 | Fabrication, supplying and fixing class B galvanised single overhang arm bracket made out of 250mm long galvanised top tube with cap and 1000mm long 40 mm dia galvanised pipe with tightening bolts complete as required. |
| 13 | Fabrication, supplying and fixing class B galvanised double overhang arm bracket made out of 250mm long galvanised top tube with cap and 1000mm long 40 mm dia galvanised pipes with tightening bolts complete as required. |
| 14 | S.I.T.C of Hot Press moulded SMC panel/Canopy Box of size(OD) 920 mm x 460 mm x 260 mm & (ID) 900 mm x 450 mm x250 mm , anti – corrosive, dust proof, rust proof, shock proof , Self-extinguishing property , resistant to heat , Vermin proof, Ultra Violet stabilized, Pilfer resistant, Suitable for mounting 1 no. 3 phase Starter, 1 no. 63 Amp 4 pole isolator and 1 no. 3 phase Energy meter, Socket for outgoing connection with pilferage proof SMC door duly welded with S/S handle having danger logo on its outer surface and with 1 no Hot Dip galvanized iron stand for a base of size 40 mm x 40 mm x 5 mm and height of the stand is 600 mm including 300 mm height below the ground with side strip of size 25 x 5 mm. |
| 15 | Providing and laying of HDPE PIPE OF 40mm outer dia with PN 4 rating by hand Moling/Mannual method Confirming to IS 4984 592 |
| 16 | Supply of XLPE insulated PVC Sheathed Al conductor armoured cable 1.1 KV grade conforming to IS-7098 of following size: (a) 2C* 6 sqmm |