| Sl. No. | Item Description |
| 1 | Dismantling and taking down security light, street light, hanger light, flood light and high mast lights of any type at any height fittings such asHPSV/MH /LED light of 48 Watt/ 60 watt / 70/72 watt/ 90 watt/ 120 watt/ 150 watt/ 200 watt and 300 watt of any make etc. AC 230 volts any wattage from pole/ wall roof top/hanger roof including washing/cleaning of perpex cover, inspection for location of faultand replacing of defective spare/parts required for smooth functioning, tightening of electric connection complete assembling and reconnecting all as per site requirment complete all as specified and directed.Note: Defective spare/ part of relevant light fitting shall be measured and paid separately under relevant item as supply only. |
| 2 | Supply only LED electronic driver/adaptor/SPDfor40-60 watt LEDsecurity light fitting existingmake complete all as specified and directed. |
| 3 | Supply only LED electronic driver/adaptor/SPDfor70/72 watt LEDsecurity light fitting existing make complete all as specified and directed. |
| 4 | Supply only LED electronic driver/adaptor/SPDfor90 watt LEDsecurity light fitting existing make complete all as specified and directed. |
| 5 | Supply only LED electronic driver/adaptor/SPDfor60-150 watt LEDflood light fitting existing make complete all as specified and directed. |
| 6 | Supply only LED electronic driver/adaptor/SPDfor200-300 watt LEDflood light fitting existing make complete all as specified and directed. |
| 7 | Supply and fix in replacement of 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathedone twin core cable flat or circular of size 10 sqmm 2 core complete all as specified and directed. |
| 8 | Supply and fix in replacement or passing through PVC conduit pipe of 1100 volts grade heavy duty, PVC insulated round 3 core 2.5 sqmm copper cable including electrical connection suitable size of lugs,nuts and bolts complete all as specified and directed. |
| 9 | Supply and fix in replacement or passing through PVC conduit pipe ofthree run of single core PVC unsheathed multi stranded copper cable (FRLS) 1.5 Sqmm nominal cross sectional area 1100 volts conforming to IS 694 including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed. |
| 10 | Supply and fix in replacement or passing through PVC conduit pipe of three run of single core PVC unsheathed multi stranded copper cable (FRLS) 2.5 Sqmm nominal cross sectional area 1100 volts conforming to IS 694 including electrical connection suitable size of lugs, nuts and boltscomplete all as specified and directed. |
| 11 | Supply and fix in replacement of rigid non-metallic PVC conduit of dia 20 mm exclusive of boxes (Junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and directed.Note: PVC pipe will be clamped at three position on pole and cost of clamp, nut, bolts etc are incl in quoted rates. |
| 12 | Supply & fix 36 W recesse/surface mounted CRCA housing LED panel light with high quality diffuser for uniform light with IP20 (10 Lm/W), complete with fixing clamps, spring etc. complete all as specified and directed. |
| 13 | Supply & fixin replacement of Integral LED Flood light Luminaries 100 Watts consisting of suitable number of LEDs andmounted on MCPCB high pressure die cast aluminium housing with sealed toughened glass cover with secondary optics lens,IP 66 protection suitable for mast light mounting, 5700K,LED efficiency >130 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV ,Confirm the tests from auth labs :LM79 & LM 80, incl proper fixing and testing of flood lights on 9/11 mtr long steel tubular pole and provide facility of power supply shall be provide as suitable for maint work of light fittings incl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed. |
| 14 | All as per Srl Item No 13.00 here in before but for 150 Watts |
| 15 | All as per Srl Item No 13.00 here in before but for 200 Watts |
| 16 | All as per Srl Item No 13.00 here in before but for 300 Watts |
| 17 | Material and labour for Detecting of fault in any type of UG cable HT/LT with fault locator equipment to supplying of HT/LT electric supply (11 KV/430 Volts) to make the HT/LT cableserviceablewith Straight throughjoint of size 95-400 Sqmm complete all as specified and directed.Note:- (a) The HT/LT fault which is detected through cable fault locator will only be paid under this item including transportation charges deemed to be included in the quoted rate. (b)Transportation charges of cable fault locator and DG set deemed to be included in the quoted rate. (c) Fault locator will be provided by the contractor for even single HT fault and no delay on this account will be acceptable otherwise penalty will levied Rs 500.00 per hour. |
| 18 | Supply & fix in replacementof Automatic Street Light Control Switch with Infrared Sensor based NATURE SWITCH & Voltage Monitoring System (VMS). Three phase, 25 Amps per phase, MCB rating 32 Amp, max load 8-12 kw incl circuit copper wire 10 sq.mm.Nature Switch operation should be based on Natural Light Lux level. Required Illuminance Level for Switching ON is ≤ 60 Lux and for switching OFF ≥ 10 Lux. The Sensor should also have part night operation facility of min. 4 to max. 12 hrs. VMS should have Adjustable Over & Under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The Sensor & VMS along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operation (i.e. By-Pass Option for both Sensor (NS-02) and VMS). Model :Swadeep-02EC-8kW3P-VMS or equivalent as approved by GE complete all as specified and directed.Note:-(i) S S Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii)The sensor must have the warranty of min of 2 years. (iii)The test certificate and warranty cirtificate must be provided by supplier. (iv)Cost of marking description on the box is incl quoted rate. |
| 19 | All as per Srl Item No 18.00 here in before but for single phase, 25 Amps per phase, MCB rating 40 Amp, max load 5-8 kw,complete all as specified and directed. Model : Swadeep-02EC-5kW1P-VMS or equivalent as approved by GE. |
| 20 | Supply and fix inreplacementof Lithium based Energy Efficient Integrated Solar Street Light of 24 Watt” in Single FRP body with duly Polyurethane coating (Camouflage color) , encases with Monocrystalline Solar PV Panel of 53/55Wp , Lithium Battery 11.1/12.8V, 28.6AH with inbuilt BMS, IP 66, IK 08, High brightness W-LED(160-180 lm/watt) lamp with Aluminum reflector for better light distribution , CRI >70, Color Temperature 5700K - 6500K, Microcontroller based charge controller cum driver, automatic dimming function ( first four hours at full brightness & rest of the time at lower light level with Microwave Sensor), Dusk to Dawn Operation, suitable to working temperature: (-) 10C to (+)55C, weight not more than 12-14kg with adjustable MS clamp suitable for pole/wall mounting etc complete as required. Protections: Short Circuit, overload, Reverse polarity and battery protections. Firm should provide Vital Parameters Test report from NABL accredited lab and should be of made in India with CE & ROHS compliant including tubular pole 6 mtr height with bottom base plate 200x200x12 mm , outdoor dia not less than 65 mm with heavy duty GI pipe or steel thickness 3mm and suitable arrangement to mount solar light as directed on pole including foundation PCC 1:3:6 type C-1using 20mm graded crushed stone aggregate and erection as per manufacturer drawing, providing synthetic enamel aluminium paint over one coat of red oxide complete all as specified and directed. |
| 21 | Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heatshrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size50 sqmm to 95 sqmm incl taking down old unsv HT joint complete all as specified and directed. |
| 22 | Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heatshrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm incl taking down old unsv HT joint complete all as specified and directed. |
| 23 | Material and labour for cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPEcable 50-95 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as specified and directed. |
| 24 | Material and labour for cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPEcable 120-185 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as specified and directed. |
| 25 | Supply and fix in replacement straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 35-95 Sqmm complete all as specified & directed. Note: The quoted rate shall include the earth work, RF and removal of soil etc. |
| 26 | Supply and fixin replacement straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 120-150 Sqmmcomplete all as specified & directed. Note: The quoted rate shall include the earth work, RF and removal of soil etc. |
| 27 | Supply and fixin replacement indoor/outdoor end terminationjoint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 35-95 Sqmmcomplete all as specified & directed |
| 28 | Supply and fixin replacement indoor/outdoor end terminationjoint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 120-150 Sqmmcomplete all as specified & directed |
| 29 | Material & Labour for XLPE cable insulated screened, PVC bedded galvanized steel strip of wire armoured , electric power cable (Heavy duty ) with aluminum conductor 11000 volts grade cross sectional area 95 sqmm 3 core suitable for 11 KV earthed system incl taking down old unsv HT cable complete all as specified and directed. |
| 30 | All as per Srl Item No 29.00 here in before but for 120 sqmm 3 core complete all as specified and directed. |
| 31 | All as per Srl Item No 29.00 here in before but for 185 sqmm 3 core complete all as specified and directed. |
| 32 | All as per Srl Item No 29.00 here in before but for 400 sqmm 3 core complete all as specified and directed. |
| 33 | Supply & fix in replacement of contactor 3 pole 18 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed. |
| 34 | Supply & fix in replacement of contactor two pole 25/40 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed. |
| 35 | Supply & fix in replacement ofcontactor coil (230V)for MU series 25/40 Amps 2 pole contactors complete all as specified and directed. Make- L&T/ BCH/ Siemens. |
| 36 | Supply & fix in replacement ofcontactor coil (240V)for freedom series 18 Amps 3 pole contactors complete all as specified and directed. Make- L&T/ BCH/ Siemens. |
| 37 | Supply & fix in replacement ofVMS (voltage monitoring series) 240 Un,in street light timer box, including all salient features such as selectabe under/over voltage trip levels, protection against phase loss & natural loss, protecotion against phase reversal and phase to phase unbalance (10%), voltage sensing principle and LED indications for power and fault conditions complate all as specified and directed. Make- L&T, Cat No SM500/ Siemens or equivalent as approved by GE. |
| 38 | All as per item No 37.00 here-in -before but 415 Un. |
| 39 | Supply & fixin replacement of bracket made out of GI tubing single piece not welded, bended at proper angle of size 40mm dia, light grade 1.5 mtr long including painting with aluminium paint over one coat of red oxide primer to the bracket complete all as specified and directed. |
| 40 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation, shafts, man holes ,for under ground cable / erection of poles, stays, locatingfault of LT cable and stay assembly etc not exceeding 10 square metre on plan and getting out in any type of soil including dressing/trimming of sides and leveling, grading and ramming of bottom of excavation complete all as specified and directed. |
| 41 | All as per Ser item No 40.00 here in before but depth exceeding 1.5 metre and not exceeding 3.0 metre. |
| 42 | Returning, filling in, in soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick each layer complete all as specified and directed. |
| 43 | Removing excavated material/soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. |
| 44 | Material and labour for sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cmsdeep after laying the cable (punned down to 18 cms depth after laying and stretching of cable) complete all as specified and directed. |
| 45 | Supply and lay bricks, common burnt clay, sub class \"B\", old size, laid in perpendicular direction to cable as cable protection complete all as specified and directed. |
| 46 | All as per Ser Item No 45.00 here in before but laying only old servicable bricks, complete all as specified and directed.Note:- Old bricks retrieved from Ser Item No 51.00 to 59.00 here in after shall be re-used. |
| 47 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique or manual boring and necessary machine including HDPE pipe of 50 mm to 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed. |
| 48 | Supplying and fixing in replacement oflight gradegalvanised mild steel pipe 80 mm bore with all fittings, laid under roads, drain, paths, fixed to poles/walls with suitablemild steel clamps, bolts, nuts and washers complete all as specified and directed.Note:- Excavation & earth work shall be measured and paidfor separately under appropriate item of this schedule. |
| 49 | All as per Item No 48.00 here-in-before but of size 50 mm bore. |
| 50 | Disconnecting & taking out defective underground cable from trenches, pole, pipe, floor, wall etc and locate the fault, rectify the defect and relaying the XLPE cable underground PVC insulated and overall sheathed aluminum conductor heavy duty 1100/11000 volts including connecting and testing for any size complete all as specified and directed. Note:- Excavation/earth work, sand cushioning, bricks andjoint shall be measured & paid for separately. |
| 51 | Supply, laying, connecting & testing in replacement of XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 10 sqmm 4.0 core laid in trenches/ on pole/road crossing or passing through existing/new pipe under road crossing clamping on wall incl aluminium thimbles/lugs etc complete all as specified and directed.Note: (i) Earth work, sand, bricks removing, returning fillingwill be paid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii)All equipments, machinery or tool if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost. |
| 52 | All as per Srl Item No 51.00 here in before but for 16 Sqmm 4 core complete all as specified and directed |
| 53 | All as per Srl Item No 51.00 here in before but for 25 Sqmm 3.5 core complete all as specified and directed |
| 54 | All as per Srl Item No 51.00 here in before but for 35 Sqmm 3.5 core complete all as specified and directed |
| 55 | All as per Srl Item No 51.00 here in before but for 50 Sqmm 3.5 core complete all as specified and directed |
| 56 | All as per Srl Item No 51.00 here in before but for 70 Sqmm 3.5 core complete all as specified and directed |
| 57 | All as per Srl Item No 51.00 here in before but for 95 Sqmm 3.5 core complete all as specified and directed |
| 58 | All as per Srl Item No 51.00 here in before but for 120 Sqmm 3.5 core complete all as specified and directed |
| 59 | All as per Srl Item No 51.00 here in before but for 150 Sqmm 3.5 core complete all as specified and directed |
| 60 | Taking down old unsv Prestressed Concrete LT pole and supply and erection of Prestressed Concrete LT pole 9.0 mtr long in true vertical position 102x172 mm at top and 102 x 279 mm at bottom class-10 incl providing cement base paint over one coat of red oxide primer and also providing black and white strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black stripcomplete all as specified & directed. Note:- (i) Earth work and PCC shall be measured and paid seperately.(ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost. |
| 61 | Taking down old unsv Steel tubular LT pole and supply and erection of steel tubular swaged poles 9.0 mtr long complete with cast iron base plate, finial taper plug, bolts,nuts and screws as specified type 410 SP-31, providing synthetic enamel aluminium paint over one coat of red oxide primer and black and white strips with synthetic enamel paint 30 cm each alternatively upto 1.5 mtr above the coping of pole starting with black stripcomplete all as specified & directed.Note:- (i) Earth work and PCC shall be measured and paid seperately.(ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost. |
| 62 | Supply & fix in replacement ofstay assembly complete with all accessories, such as stay plate 230x230x6 mm, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc all as per electrical plate No 1 or SSR part 1 and as directed incl taking down old unsv stay assycomplete all as specified & directed.Note:- The quoted rate shall include the cost of loop type insulator, stay clamps, excavation, PCC, stay wire, stay bow, turn buckle, nuts etc. complete. |
| 63 | Material and labour for Plain cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate in foundation complete all as specified and directed. |
| 64 | Material and labour for PCC 1:3:6 type C1 using 20 mm graded stone aggregate for stay poles etc including necessary form work to exposed surfaces finished smooth and even complete all as specified and directed. |
| 65 | Material and labour for PCC 1:2:4 Type B-1 using 20 mm graded stone aggregate for coping of poles including necessary form work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed. |
| 66 | Material & Labour for surface cleaning of LTsteel tubular poles9 mtrs long including removing rusted particles painting withtwo coats of synthetic enamelaluminium paint over a coat of red oxide primer including stand cross arms, bracing, supports,clamps eye hooks, security light bracket clamps etc providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl repairing and painting on coping with cement base white paintcomplete all as specified & directed. Note: (i)The quoted rate shall includes marking of numbers on each LT pole as per direction of Engr-in-Charge.(ii)The quoted rates shall including the repairing of coping with cement / PCC |
| 67 | Material & Labour for surface cleaning of LT Prestressed Concrete pole 9 mtr long including painting with two coat of cement base paint also marking black & white strips alternatively 30 cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint and repairing and painting on coping with cement base white paintcomplete all as specified & directed. Note: (i)The quoted rate shall includes making of numbers on each LT pole as per direction of Engr-in-Charge.(ii)The quoted rates shall including the repairing of coping with cement / PCC |
| 68 | Material and labour in replacement of Loop insulator Porcelain, vitreous white/brown/green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, large size with overall dimensions 90mmx 140mm, clearance of hole 25.5 mm,complete all as specified & directed |
| 69 | Material and labourin replacement for shackle type porcelain vitreous white or brown insulator including GI straps washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm hight, 90 mm dia, section of strip 30mmx3mm & dia of bolt 12 mmcomplete all as specified & directed. |
| 70 | Taking down old unserviceable ACSR conductor and material and labourforaluminium conductor steel reinforced (ACSR) conductor of size 6/1 x 2.59(Weasel) and6/1 x 2.11 (Squirrel) or other existing type conductor ISI marked for LT over head lines on poles including stretching, tightining of poles insulator with winding wire of suitable size with insulator/strechingof ACSR conductor complete all as specified and directed. |
| 71 | Taking down old unserviceable cross-arms and material and labour for cross arms,bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape of size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed. |
| 72 | Material and labourfor spraying chemical (Round up) on area to remove unwanted vegitation/grass at various locationscomplete all as specified & directed. |
| 73 | Supply & filling for loose filling in substations, under poles, under transformers of hard core broken to gauge not exc 63 mm broken stone/boulders incl leveling and spreading lime stone powder under stones complete all as specified and directed. |
| 74 | Material & Labour in replacement of steel nuts, bolts, washers of any size required at site complete all as specified and directed. |
| 75 | Material & Labour forpreperingold painted steel suraces of any description not otherwise described over 10 cm width orgirthand applying one coat of synthetic enamel paint complete all as speciied and directed. |
| 76 | Dismantling andtaking down old u/s earthing of any type and description but provision of earthing complete with galvanisedearth plate electrode 600mm x 600mm, 6.00mm thick surrounded by charcoal and salt, burried directly in ground vertically in a pit of depth not less than 2.25m belowground level with top edge of the earthplate not less than 1.5m belownormal groundlevel, connected to 25x4 mm GI strip earth lead by means of bolts, nuts, checks nuts and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 40mm bore medium grade and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work. The rate also include charcoal & salt in alternate layers, 20mm bore GI pipe medium grade for watering and 40mm bore GIprotection pipe (light grade), funnel, wire mesh,cast iron cover andframe etc including testing on completion complete all as specified and directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with standgrouted in PCC. (iii) On testing after completion if the desired earth resistanceis more than 2Ώthe earthing will be redone at no extra cost. |
| 77 | All as per Srl Item No 76.00 here in before but for connected to galvanised earth lead wire of 4.0 mm dia by means of GI nuts bolts, check nuts and washers and connected to earthing test point drawn through 15 mm bore GI pipe medium grade for protection of GI earth lead wire including 20mm bore GI pipe medium grade for watering GI funnel. |
| 78 | Supply & fix in replacement of LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 5 line as per IS complete all as specified & directed |
| 79 | All as per Srl Item No 78.00 here in before but 4 line complete all as specified & directed |
| 80 | Material & Labour for aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 240-400 sqmm complete all as specified & directed. |
| 81 | Material & Labour for aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 70-120 sqmm complete all as specified and directed. |
| 82 | Material & Labour for aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 25-50 sqmm complete all as specified and directed. |
| 83 | Material & Labour for aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 10-16 sqmm complete all as specified and directed. |
| 84 | Re-stretching existing/retrievedACSR conductor on LT /HTpoleand binding conductor on insulator properly using new binding wire/jumper wire complete all as specified and directed.Note : Each Run of line conductor shall be measured in Running Metre from pole to pole. |
| 85 | Material and labour in repairs of stay by tightening of stay wire after untying the conductor spans from the poles to make correct tensions and maintain verticality of poles, including re-jointing the conductors in position with new binding wire complete all as specified and directed. |
| 86 | Material and labour for Repairing broken Door, Locking Arrangements, Hinges, etc. of LT Panel/ Feeder Pillar/ Pole Box, Indoor/ Outdoor type of any size, necessary welding, drilling as reqiured, Replacing Door, Locking Arrangements, Hinges, etc. if ordered, complete all as specified and directed. |
| 87 | Material and labour for Cleaning, Scraping of Exposed Surfaces of LT Panel/ Feeder Pillar /Pole Box, Indoor/ Outdoor Type and applying One coat of Synthetic Enamel Paint (Paint & Shade as approved) with Spray Painting Machine including Writing MES No. and Machine No. with Black Paint, Letters 50mm High and 15mm wide, complete all as specified and directed. |
| 88 | Material and labour for shifting ofheavy items upto 5 Ton / excavation / cleaning areas / cleaning site by providing crane/hydra / excavators /tractors/ trolley etc as required at site complete all as specified and directed. |
| 89 | Repairing of existing unserviceable PCC coping of LT/HT pole by breaking completely and material and labour for PCC 1:2:4 type B1, (using 20mm graded crushed stone aggregate) of size 600X600X300mm including form work and applying two coats of cement base paint complete all as specified and directed. |
| 90 | Material & Labour for Chemical spray (DC 2.26 contact cleaner) in container of 415 ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricants, displaces and seals out moisture release rusted mechanisum cleanese etc complete all as specified and directed. |
| 91 | Material and labour in replacement of Bus bar box outdoor type of size not less than 590 x 590 x 500 cm totally enclosed dust and vermin proof duly fixed on angle iron frame, double door, front and back opening with hinged doors and locking arrangement fabricated with 3.15 mm thick including cable glands, cable connection with lugs, grouting the angle-04 Nos in below ground level PCC 1:3:6 and over ground with the PCC 1:4:8 and including bolts,nuts,washers , digital voltmeter , ampere meter with suitable size oc CTs and selector switch etc, complete all as specified and directed.Note: Bus bar box comprises the following items: -(a) Incoming - MCCB 4 pole,415 Volts, 63 Amps, Adjustable thermal and magnetic release with breaking capacity of 25 KA - 01 No(b) High grade aluminium bus bar of capacity 100 Amps-04 Nos(c) LED lamps for RYB indication - 01 set. |
| 92 | Supply & fix in replacement MCCB TPN 400 Amps, 415 Volts, 36 KA,4 pole complete connection complete all as specified and directed. |
| 93 | All as per Srl Item No 92.00 here-in-before but of 250 Amp, 415 Volts, 36 KA. |
| 94 | All as per Srl Item No 92.00 here-in-before but of 160 Amp, 415 Volts, 25 KA. |
| 95 | All as per Srl Item No 92.00 here-in-before but of 125 Amp, 415 Volts, 16 KA. |
| 96 | All as per Srl Item No 92.00 here-in-before but of 100 Amp, 415 Volts, 25 KA. |
| 97 | All as per Srl Item No 92.00 here-in-before but of 40 Amp, 415 Volts, 10 KA. |
| 98 | Supply & fix in replacement ofLED street light fitting 45 watts made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded toughened glass having TOP Opening seperate driver compartment with IP 66 protection and impact resistance of IK07 consisting of suitable number of LEDs with sealed toughened glass cover, 5700K, LED efficiency >110 lm/Watt and system efficiency 110 lm/W, 240 Volts AC, 50 Hz, CRI>70% operating voltage range 140 V-270 V, Power factor> 0.95, mains current 0.270A, working temperature range -10ºC to 50ºC, built in surge protection of more than 10 kV, better optics for uniform distrubution with multiple LEDs not less than 2 watt each and having optical grade polycarbonate lens with all accessories, suitable for side entry, pole mounting with bracket arm OD 40 mm, incl proper fixing and testing of street lights on 9/11 mtr long steel tubular pole incl make proper connection of new and existing light fittings complete with cutting, welding, drilling holes, nut bolts, washer, GI Reducer, threading of GI pipe etc required to fix on existing bracket complete all as specified and directed. Note :-PVC heavy duty conduit pipe along with 3/1 run of 1.5/2.5 sqmm PVC insulated unsheathed/ sheathed copper multistranded conductor from MCB box to streetshall be measured and paidfor separately. |
| 99 | All as per Srl Item No 98.00 here in before but for 60 Watts |
| 100 | All as per Srl Item No 98.00 here in before but for 70/72 Watts |
| 101 | All as per Srl Item No 98.00 here in before but for 90 Watts |
| 102 | Supply & fix in replacement of nature switch 10 to 25 amp and operation should be based on natural light lux level, required illuanance level for switching on is <30 Lux and for switching off >10 lux , the sensor should also have part night operation facility of min 4 hrs to max 12 hrscomplete all as specified and directed. |
| 103 | Material and labour in replacement of earthing chamber cover of size 0.45 x 0.45x .04 m or size as per site with RCC 1:2:4 type B1 with 20 mm graded stone complete all as specified and directed. |
| 104 | Material and labour in replacement of broken earth pit of size 300x300x300 mm madeof PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate, and earth pit cover made out of RCC 1:2:4 type B1, cover reinforced with 8 mm dia TMT bars @ 100 mm centre to centre both ways with handle made out of 8 mm dia bar, watering arrangement with funnel and wire mesh and including reconnecting of earth lead of any type with new nuts, bolts and washers as required at site with testing result complete all as specified and directed. |
| 105 | Supply, installing, testing & commissioning of outdoor type cubical panel board of size 1.5mX1.2mX.5m, outer shell made out of3.0 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform block type 60 cm above ground level and 30 cm grouting in ground,frame factory fabricated with front and back openable double door system and cable alley(Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open ablewith arrangement of pad locking on both doors incl 2 no. of pad locks of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, incl Aluminium bus bar of 600 A ,tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011Part-1 andpart -2 type test certificate with not less thanIP-56and breaking capacity 65 KA including taking down u/s panel comprising of the following :-INCOMING:-(a) MCCB400 Amps, 50 KA 4 pole 415 Volts AC, adjustable type, Microprocessor with int release - 01 No.OUTGOING:-(a) MCCB250 Amp, 415 volt, 4 pole, breaking capacity 25 KA -03 Nos.(b) MCCB100 Amp, 415 volt, 4 pole, breaking capacity 16 KA -03 Nos.(c) RYB indication LED type, 22.5 mm dia, protected with MCB SP 2 Amp showing 3 phase supply -03 Nos(d) Multi function meter for reading Volt, Amp, KWH, Frequency etc including CT coil complete.- 01 No.(e) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc complete are included in quoted rates. |
| 106 | Supply and spray chemical (Round up) to remove unwanted vegitation/grass at various locationscomplete all as specified and directed. |
| 107 | Supply & fix in repair test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed. |
| 108 | Trimming of Tree branches around the sub station, solar plant area or falls into OH lines of HT/LT & minimum clearance of 3 Mtrfrom branches , proper shutdown will be taken and maintained in the register including any type of T & P requiredcomplete all as specified & directed. |
| 109 | Note:-Amount of credit ofRs. 108643.00 for retrieved materials is mentioned in Schedule of Credit of tender documents in pdf form which will be deducted offline while acceptance of tender. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy