| 1 | Taking up/down under ground cable 11000 Volt grade of size 120 Sqmm, 3 core from trenches, ducts, floor, pipes and removing materials from site of work complete all as directed by Engineer-in- Charge.(Note: Excavation and earth work shall be measured separately) |
| 2 | Supply , laying & testing HT UG cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured electric power cables (heavy duty ) with stranded aluminium conductor 11000 volts (Earthed), grade of size 120 Sqmm 3 core all as specified and directed.Make: Polycab/ KEI/ Grandley |
| 3 | Supply and fix cable jointing kit for 11 KV grade for indoor termination end Cold shrink type jointcomplete with jointing material and accessories suitable for 3 core XLPE armoured Aluminiumconductor cable of size 120 Sqmm to 185 sqmm all as specified and directed.Make: 3M/ M Seal/ Raychem |
| 4 | Supply, fixing and testing cold shrinkable type, straight through cable jointing kit, outdoor type suitable for XLPE insulated cable, 120 Sqmm to 185 sqmm size 3 core, 11 KV, as fixed in repairs complete all as specified and directed.Make: 3M/ M Seal/ Raychem |
| 5 | Excavation in trenches in soft/loose soil not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide and getting out complete all as specified and directed |
| 6 | Excavation in trenches in hard dense soil/ road cutting/ PCC not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide and getting out complete all as specified and directed |
| 7 | Supply and laying un-reinforced precast conctere cable cover,class HVP, type 2 with peak size of 450 X 180 X 40 mm.Make: Mehtab tiles/ National tiles or equivelent |
| 8 | M & Lfor dry screened river bed sand cushioning 8cm before laying the cable and 15cm after laying the cable and further hand punned to form a uniform all as directed by Engr-in-Charge. |
| 9 | Returning and filling in, including spreading, leveling, watering and well ramming in layers not exc 25cm |
| 10 | Removing excavated material n exc 50m and depositing where directed at a level n exc 1.5m above Cum the starting point in rocks. |
| 11 | M & L for PCC 1:3:6, type C-2, (using 40mm graded stone aggregate) as in foundation filling and mass concrete complete as specified and directed |
| 12 | S&F of HDPE type pipe, PN-10, 100 mm dia for laying in ground, road crossing etc for cable protection including necessary fittings for wall and ducting with required clamps and supports, etc. all as directed by Engineer in Charge. Note: Required Clamps and supports (PCC) shall be fixed on wall with distance 1.00 RM as directed by Engr- in- Charge.Make: FINOLEX/ TIRUPATI/ SUPREME/ DUPLON (RELIANCE) |
| 13 | S & F cable route indicator made out of 50x50x6mm angle iron, 150mm long embedded in PCCblock of suitable size with the letter \"HT CABLE\" suitable inscribed on Cl circular plate plate 8mm thick, 100mm dia complete as specified and directed. |
| 14 | Renewal of broken/wornout earth pit including M & L for earthing chemical with copper plated 50 mm dia pipe 3 mtr long(100 microns) including Electrodite 50 Kg buried directly in ground including earth bore hole work (earth bore not less than 3 Mtr deep below normal ground level and connected to copper earth strip of size 20×3 mm by means of copper nuts bolts with washers and connected as per following specifications completeall as directed by Engineer-in-Charge.(a) Product Model: ASEEL 19 CP, 3 meter long (Copper Plated) – 100 microns .Fast Electrode, Model FE 80 mm 3 mtr (Pure Copper Single Pipe), Outer Dia is 80 mm with a wall thickness of 2 mm, Inner Dia is 26 mm with a wall thickness of 2.6 mm, Overall Length is 3000 mm,External Corrosion Protection: Copper Plated (100+ microns), Internal Corrosion Protection: In addition to Copper Plated (100+ microns), a ground breaking corrosion resistant Crystalline Conductive Compound is filled and compacted in the cavity within the pipes to enhance the electrodes performance. Conforms to IS: 3043 - 1987 i.e., Code Of Practice For Earthing (+ 10%) variations in dimensions applicable. (b) Electrodite backfill: Fast Electrode Earth Enhancement Compound, Manufactured using Eco - Friendly minerals, Blended homogeneously with conductive carbon(s), Resistivity: < 5 ohm-metre (In ideal moist conditions); > 5 ohm-metre (Dry Conditions), Ph Value: 7.0 - 8.5, High water retention capacity, Hygroscopic, Ionic & Electronic conduction, Swells when it comes in contact with water thereby engaging constant contact between the electrode surface & soil which is a crucial aspect in the performance of an earthing system. Packing Size : 2 Bags of 25 kilograms,Recommended for normal soil conditions. Confirms to IS : 3043 – 1987.(c)Installation of earthing with bore well machine complete for bore exceeding upto 4.5 meter below ground level complete all as specified and directed by Engr-in-Charge. |
| 15 | Earth continuity conductor or main earthing lead of size 20x3mm copper strip fixed to wall on battenor recess or chases or buried inground or drawn in conduit/pipe orfixed to poles or any other indicatedsituation for loop earthing etc. as required |
| 16 | S&F HT rubber insulsted mat suitable for 11KV panel 3 mm thickness Claas\"B\" having fire retardant, insulation water resistance of size 1m X 10m X 3mm confirming ISI 15652:2006 |
| 17 | S&F Self-amalgamating high voltage electrical insulation tape suitable for 11 KV AC supply of size not less than 50 mm wide x 0.8mm thick x10 Mtrs (EPR Rubber)having property of Moisture seal for all water- proofing needs for insulating protection of bus bars, cable lugs, terminations, transformers other power distribution equipment also incl corona ozone resistance and UV resistance confirming IS 7809:1 (1975)Make: 3M/ Scapa or equivalent |
| 18 | S&F CTC solution for for removing carbon on electrical equiments, each bottle not less than 400 ml solution |
| 19 | Supply and install in repairs AFO (Auto fire off) fire extinguisher ball 150 mm dia (standard orange) with stand complete all as specified and directed. |
| 20 | Supply HT Earth discharge rod suitable for 11 KV equipped with FRP/rubber insulator to increase creepage distance, Excellence dielectric strength, Fiberglass tube manufactured from high quality epoxy resin including canvas bag confiming ISI standard |
| 21 | S&F HT rubber gloves suitable for 11 KV madeup of Bi-polymer coating is a blend that combines the best properties of nitrile and PU (polyurethane) having meet or exceed ASTM D120 and IEC EN60903 StandardsMake: Honeywell/ The top gloves/ Or equivelent |
| 22 | S&F 1st Aid box with including all essential 1st aid medicine (minimum 32 medicine) of size 5D x 20W x 10H Centimeters, 4 Partition for medicines organize with lock Inlcuding feature ofwall mounting box made from galvanize Metal with 7 Way Processed Powder Coating complete all as specified and directed. |
| 23 | S&F high power torch strong beam suitable for long range, single high power LED with 2 mode light switch having USB type charging port. Operating on 3.7 V DC,battery supply >4000 mAhMake: Phillips/ Eveready/ or equivelent to Phillips |