| 1 | Providing and fixing of 160 Amp , 4 Pole MCX 32power contractorin existing cubicle panel boardetc as required. Make -L&T code No.CS97020, or its compitable to Havells / Indoasian/ Standard/ legrand/ ABB. |
| 2 | Providing & fixing MCCB, 160 amps, 4 pole, breaking capacity 36 KA, with suitable operating mechanism extended rotary handle in existing cubicle panel board including drilling holes in cubicle panel, making connections and dismantling of existing Switch gears etc. as required. compitable to L&T make type DU-250, cat. No.CM98065OONO. make Havells/ Indoasian/Standard /legrand/ schneider/ABB/Seimen. |
| 3 | Providing & fixing of 250 amps, 415 volt, type FN(TPN) switch disconnector fuse unit open execution with suitable for Bolted fuse link, size A4, Fr 3, conf. to IS/IEC 60947-3 for fixing in existing Sheet Steel enclosure with door inter lock & pad lock facility, drilling holes i/c 03 Nos bolted fuse link cat. No.ST30781 and complete with connections, testing and commissioning and dismantling of existing fuse switch units (disconnectors) etc. as required. make L&T cat. No. SK90472 or its compitable to Havells/Indoasian/Standard /legrand/ schneider/C&S. |
| 4 | Providing & fixing of 125 amps, 415 volt, type FN(TPN) switch disconnector fuse unit open execution with suitable for Bolted fuse link, size A4, Fr 2, conf. to IS/IEC 60947-3 for fixing in existing Sheet Steel enclosure with door inter lock & pad lock facility, drilling holes i/c 03 Nos bolted fuse link cat. No.ST30769 and complete with connections, testing and commissioning and dismantling of existing fuse switch units (disconnectors) etc. as required. make L&T cat. No. SK90497 or its compitable to Havells/Indoasian/Standard /legrand/ schneider/C&S. |
| 5 | Providing & fixing of 63 amps, 415 volt, type FN(TPN) switch disconnector fuse unit open execution with suitable for Bolted fuse link, size A1L, Fr 1, conf. to IS/IEC 60947-3 for fixing in existing Sheet Steel enclosure with door inter lock & pad lock facility, drilling holes i/c 03 Nos bolted fuse link cat. No.SK95704 and complete with connections, testing and commissioning and dismantling of existing fuse switch units (disconnectors) etc. as required. make L&Tor its compitable to Havells/Indosian/Standard/ Legrand/ Schneider/C&S. |
| 6 | Providing & fixing of 32 amps, 415 volt, type FN(TPN) switch disconnector fuse unit open execution with suitable for Bolted fuse link, size A1L, Fr 1, conf. to IS/IEC 60947-3 for fixing in existing Sheet Steel enclosure with door inter lock & pad lock facility, drilling holes i/c 03 Nos bolted fuse link cat. No.SK95518 and complete with connections, testing and commissioning and dismantling of existing fuse switch units (disconnectors) etc. as required. make L&Tor its compitable to Havells/Indoasian/ Standard/ Legrand/Schneider/C&S. |
| 7 | Providing & fixing of 125 amps, 415 volt, Bolted fuse link suitable for 125 amps disconnector fuse unit, size A4, conf. to IS/IEC 60947-3 and testing, commissioning and dismantling of existing fuse etc. as required. make L&Tcat. No.ST30769 or its compitable to Havells/Indoasian/ Standard /legrand/schneider/C&S. |
| 8 | Providing & fixing of 63 amps, 415 volt, Bolted fuse link suitable for 63 amps disconnector fuse unit, size A1L, conf. to IS/IEC 60947-3 and testing, commissioning and dismantling of existing fuse etc. as required. make L&Tcat. No.ST35828 or its compitable to Havells/ Standard /legrand / schneider/C&S. |
| 9 | Providing & fixing of 32 amps, 415 volt, Bolted fuse link suitable for 32 amps disconnector fuse unit, size A1L, conf. to IS/IEC 60947-3 and testing, commissioning and dismantling of existing fuse etc. as required. make L&Tcat. No.ST34529 or its compitable to Havells/Indoasian/ Standard /legrand/schneider/C&S. |
| 10 | SITC of outdoor type feeder pillar, having canopy at top, double door made out of 16 SWG CRAC sheet, CPRI approved of size 1000x1200x500 mm deephaving 200 Amp, 04 nos. insulated aluminium bus bars, and to accommodate following accessories front & back door openable and P&F of internal connection with suitable size of CU wires, & angle iron frame of size 1000 mm x 500 mm with 600 mm long legs made out of 50 mm x 50 mm x 5 mm thick & grouting the same in suitable cement concrete foundation, arrangement for incoming/ outgoing cabling/ cable termination,locking, interconnection etc as required. i) 125 Amp SDF unit - 01 Nos. ii) 100 Amp 4 pole, Contactor -01 nos iii) 63 Amp SDF unit - 03 Nos. iv) Digital Voltmeter - 01 nos. v) RY LED indicator 415 V make L&T - 02 Nos. vi) B LED indicator 415 V make L&T - 01 Nos. vii)Bolted fuse link for 125A SDF -04 nos. cat no. ST30769 viii) Bolted fuse link for 63A SDF - 12 Nos. cat no. ST30761 ix) Current transformer of suitable ratio as required. |
| 11 | SITC of outdoor type feeder pillar, having canopy at top, double door made out of 16 SWG CRAC sheet, CPRI approved of size 700x1000x500 mm deephaving 200 Amp, 04 nos. insulated aluminium bus bars, and to accommodate following accessories front & back door openable and P&F of internal connection with suitable size of CU wires, & angle iron frame of size 700 mm x 500 mm with 600 mm long legs made out of 50 mm x 50 mm x 5 mm thick & grouting the same 7in suitable cement concrete foundation, arrangement for incoming/ outgoing cabling/ cable termination,locking, interconnection etc as required. i) 63 Amp SDF unit - 01 Nos ii) 32 Amp SDF unit - 03 Nos. iii) Bolted fuse link for 63A SDF -04 nos. cat no. ST30761 iv) Bolted fuse link for 32A SDF - 12 Nos. cat no. ST30753 |
| 12 | Providing and fixing Digital 3 phase multifunction meter in existing cubicle panel board including, making connections etc.as required. Make L&T code no.WL441010OOOOOr its compatible Havells/Stadard/ Legrand/ C&S. |
| 13 | Providing, Installation, Testing and commissioning of spare coils (for four pole MCX 32 contactors) 240 volt, AC, cat. No.CS94196 L& T make. Etc. as required. |
| 14 | Supplying & fixing of 3 Nos LED indicator 16 mm surface mounted low power consumption,surge & low voltage glow protection cat. no.SIL, in the Red, yellow and Blue colours, L&T make, including connections with 0.75 sqmm FR LS single core copper conductor cable etc. as reqd. |
| 15 | Providing and fixingof AC Control relays NONC Switch( MX0 22E( 2NO+ 2NC)suitable for 415 Volt ,50 Hz, inductive load and proper operation of power auto contactorcomplete withconnections, testing and commissioning etc. as required. Make L&T,Havells/Indosian/Standard/legrand/schneider/ C&S |
| 16 | Providing & fixing of spreader terminals 4P,suitable for 160 amps MCCB, 4 pole, breaking capacity 36 KA, making connections etc. as required.compitable to L&T make cat. No. CM92007OOOOmake L&T/Havells/Indosian/Standard/legrand/schneider/ C&S. |
| 17 | PITC ofAVR SR7/6-PH (200/250 S/250 MFr) for 100 KVA DG sets including making connectionas required. makeGreaves cotton or its equivalent. |
| 18 | Add Labour cess @1% on total of item 1 to 17 |