| 1 | Excavation in trenches n .exc 1.5 mtr wide and not exec 1.5 mtr depth and getting out in loose/soft soil complete all as specified |
| 2 | Returing filling in incl spreading leveling, watering and well ramming in layer not less than 25 cum each layer all as specified. |
| 3 | Removing excavated material to a distance not exc 50M anddepositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified |
| 4 | M&L filling of dry sand under and around LT cable to provide sand cushioing and in sub stn ducts/trenches complete all as directed. |
| 5 | M/Lfor brickwell burntlocallyavailablesubclass \"B\" laid over sand cushioningtocableintrencheskeepingwidthofbrickparalleltothelengthofcable complete allasspecifiedanddirected. |
| 6 | M&L PCC 1:4:8 type D 2 using 40 mm graded stone aggregate forfoundation of pole & stay complete all as directed |
| 7 | M&L PCC 1:3:6 type C 2 using 40 mm graded stone aggregate for fillingof pole & stay complete all as directed |
| 8 | M&L PCC 1:2:4 type B2 using 20 mm graded stone aggregate for copining of pole complete all as directed |
| 9 | Taking out old unserviceable PCC/steel tubular poles 9 mtr long and supply and erection of steel tublar swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts, screws as specified type 410 SP-31 (9.0 mtr long) and shifting of conductors and insulators etc incl painting the exposed portion of the pole with two coats of aluminium paint over a coat of red oxide primer and internally through out plus embedded portion with two coats of black bituminous paint over a coat of red oxide primer. Marking of pole number with black paint in yellow circle all as specified and directed by Engr-in-Charge. |
| 10 | Taking out old UNSV cable of any sizeand supply, laying, jointing and testing ofcableXLPE 16 sqmm 2 core insulated, armoured, heavy duty LT under ground cable 1100 Volts gradewith aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area for following sizes, including taking down old, complete, all as specified and directed. ) |
| 11 | Taking out old UNSV cable of any sizeand supply, laying, jointing and testing ofcableXLPE 16 sqmm 4 core insulated, armoured, heavy duty LT under ground cable 1100 Volts gradewith aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area for following sizes, including taking down old, complete, all as specified and directed. |
| 12 | Taking out old UNSV cable of any sizeand supply, laying, jointing and testing ofcableXLPE 25 sqmm 3.5 core insulated, armoured, heavy duty LT under ground cable 1100 Volts gradewith aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area for following sizes, including taking down old, complete, all as specified and directed. |
| 13 | Taking out old UNSV cable of any sizeand supply, laying, jointing and testing ofcableXLPE 35 sqmm 3.5 core insulated, armoured, heavy duty LT under ground cable 1100 Volts gradewith aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area for following sizes, including taking down old, complete, all as specified and directed. |
| 14 | Taking out old UNSV cable of any sizeand supply, laying, jointing and testing ofcableXLPE 50 sqmm 3.5 core insulated, armoured, heavy duty LT under ground cable 1100 Volts gradewith aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area for following sizes, including taking down old, complete, all as specified and directed. |
| 15 | Taking out old UNSV cable of any sizeand supply, laying, jointing and testing ofcableXLPE 70 sqmm 3.5 core insulated, armoured, heavy duty LT under ground cable 1100 Volts gradewith aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area for following sizes, including taking down old, complete, all as specified and directed. |
| 16 | Taking out old UNSV cable of any sizeand supply, laying, jointing and testing ofcableXLPE 95 sqmm 3.5 core insulated, armoured, heavy duty LT under ground cable 1100 Volts gradewith aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area for following sizes, including taking down old, complete, all as specified and directed. |
| 17 | Supply and fixing of moulded case circuit breaker Four pole 400Amps 35 KA capacity 415V 50Hz with adjustable thermal and magnetic relay, Ics=100% Icu, 75% Icu incl taking out the old unserviceable complete all as specified and directed by Engr-in-Charge. |
| 18 | Supply and fixing of moulded case circuit breaker Four pole 250Amps 35 KA capacity 415V 50Hz with adjustable thermal and magnetic relayincl taking out the old unserviceable complete all as specified and directed by Engr-in-Charge. |
| 19 | Supply and fixing of moulded case circuit breaker Four pole 200Amps 25 KA capacity 415V 50Hz with adjustable thermal and magnetic relayincl taking out the old unserviceable complete all as specified and directed by Engr-in-Charge. |
| 20 | Supply and fixing of moulded case circuit breaker Four pole 160Amps 25 KA capacity 415V 50Hz with adjustable thermal and fixed magnetic relay incl taking out the old unserviceable complete all as specified and directed by Engr-in-Charge. |
| 21 | Supply and fixing of moulded case circuit breaker Four pole 125Amps 35 KA capacity 415V 50Hz with adjustable thermal and fixed magnetic relay incl taking out the old unserviceable complete all as specified and directed by Engr-in-Charge. |
| 22 | Supply and fixing of moulded case circuit breaker Four pole 100Amps25 KA capacity 415V 50Hz with adjustable thermal and fixed magnetic relay incl taking out the old unserviceable complete all as specified and directed by Engr-in-Charge. |
| 23 | Supply and fixing of moulded case circuit breaker Four pole 100Amps16 KA capacity 415V 50Hz with adjustable thermal and fixed magnetic relay incl taking out the old unserviceable complete all as specified and directed by Engr-in-Charge. |
| 24 | Supply and fixing of moulded case circuit breaker Four pole 63Amps25 KA capacity 415V 50Hz with adjustable thermal and fixed magnetic relay incl taking out the old unserviceable complete all as specified and directed by Engr-in-Charge. |
| 25 | M & Lfor GI tubelightgrade galvanisedwithallfittingslaidalong the pole/intrenches / underroadorfloorof40mmbore including removing the rusted old one completeallasspecifiedanddirected. |
| 26 | M & Lfor GItubelightgrade galvanisedwithallfittingslaidalong the pole/intrenches / underroadorfloorof50mmbore including removing the rusted old one completeallasspecifiedanddirected. |
| 27 | M & Lfor GI tubelightgrade galvanisedwithallfittingslaidintrenches / underroadorfloorof80mmbore including removing the rusted old one complete allasspecifiedanddirected. |
| 28 | M/L for replacement of Earthing complete with GI earthplate 60x60cmx6mm thick electrode and 4mm dia GI wire as earthing lead.burried directly in ground ( earth pit not less then 2.25 metres deep below ground level ) with top edge of the plate not less then 1.5 metres below normal ground level. connected to GI wire earth lead 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part-I and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade up to 7.5 mtr length of earth wire,charcoal dust and salt etc and connected to earthing test point all as specified and as directed by Engr-in-charge. |
| 29 | M & L for earth continuity conductor using GI strip 32 x 6 mm as earthing lead complete all as directed incl taking down the old unserviceable complete. |
| 30 | Supply and installation of on load change over switch in sheet metal enclosure of capacity 63 Amps, 4 pole complete all as specified and directed. |
| 31 | S & F in replacement of Integral LED street light luminaires complete comprising of epoxy powder coated housing, enclosed with glass cover in front 50W mounted on MCPCB suitable for 50 mm dia pipe in gress protection IP-66 complete all as specified and as directed . |
| 32 | S & F in replacement of Integral LED street light luminaires complete comprising of epoxy powder coated housing, enclosed with glass cover in front 90W mounted on MCPCB suitable for 50mm dia pipe in gress protection IP-66 complete all as specified and as directed . |
| 33 | S & F in replacement of Integral LED street light luminaires complete comprising of epoxy powder coated housing, enclosed with glass cover in front 60W mounted on MCPCB suitable for 50mm dia pipe in gress protection IP-66 complete all as specified and as directed . |
| 34 | S & F in replacement of Integral LED street light luminaires complete comprising of epoxy powder coated housing, enclosed with glass cover in front 70W mounted on MCPCB suitable for 50mm dia pipe in gress protection IP-66 complete all as specified and as directed . |
| 35 | Taking down after disconnection of old UNSV of street/security/road/post toplight fitting and supply and fixing of LED based energy saving & environment friendly long life versatile luminaire made in pressure die cast housing and heat sink with aluminium extruded with IP-65 of 30 watt complete with front toughened glass cover including connection with 2.5 sqmm 3 core PVC insulated copper wire complete all as specified. |
| 36 | Tking down after disconnection of Old UNSV ofhigh mastlight fittings and supply and fixing in replacement of LED based energy saving & enviorment friendly long life versatile flood light Lumos IP-65of 200 W complete with front glass cover complete as specified. |
| 37 | M & L for earth continuity conductor /main earthing lead fixed to wall/batten or recess/chases or buried in ground or drawn in conduit /pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 6mm dia galvanised iron or steel wire. |
| 38 | M & L for Painting of steel tubular pole 9.0 mtr long, by applying one coat of alluminium paint after scraping / brushing and cleaning the rust on pole and cross arms . Alluminium painting will be done on pole above 1.5 Mtr hight from ground level and balance 1.5 mtr from groundlevel will be painted by alternate layer of black and white enammelled paint ( 30 cms each) Pole Nos will be written on pole by black paint in yellow circle of 150mm dia all as directed by Engr in charge. |
| 39 | Notes :- Amount of Credit Schedule for Schedule \"A\" Part-ll shall be deducted from total quoted amount of BOQ to arrive at the contract sum |