| 1 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for laying pipes or foundation etc. or for shafts, wells, cesspits, manholes, pier holes etc. n.exc 10sqm on plan and getting out in any type of soil, complete all as specified and directed. |
| 2 | Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm in any type of soil, complete all as specified and directed. |
| 3 | Removing excavated material (soil) to a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point, complete all as specified and directed. |
| 4 | M&L for rectification of existing defective run lead joints including burning and removing the old defective lead joints and providing new lead joints with all required materials and testing the joints for leakages for the following sizes of CI/DIpipes complete all as specified and directed.(Note: Earth work shall be measured separately) |
| 5 | 80 mm bore |
| 6 | 100 mm bore |
| 7 | 150 mm bore |
| 8 | 200 mm bore |
| 9 | Supply and replace sluice valve spindle made out of EN-8 steel with check nut made out of brass/bronze material including replacing perished gland packing, rubber gasket, bolts and nuts suitable for the following sizes of sluice valves complete all as specified and directed. :- |
| 10 | 80 mm dia sluice valve |
| 11 | 100 mm dia sluice valve |
| 12 | 150 mm dia sluice valve |
| 13 | 200 mm dia sluice valve |
| 14 | S&F in replacementfor Cl sluice valve, non-rising type conforming to IS-14846, suitable for 200 mm bore pipe consisting ofSS spindle as per IS 6603, Cast iron Body, Dome & Wedge as per IS 210,greasy jute type gland packing, fasteners as per IS 1367, Natural rubber gasket, CI manual hand wheeletc. completedouble end flanged and drilled,ofClass PN-1.6 ( ISI marked) including all jointing materials such as rubber gasket insertionsheet nut ,bolts and washers etc. complete all as specified and directed. |
| 15 | All as per item No.6 here-in-before but size 150 mm dia |
| 16 | All as peritem No.6 here-in-before but size 100 mm dia |
| 17 | All as peritem No.6 here-in-before but size 80 mm dia |
| 18 | M&L for attending break down of pipe line bursting/cracks including excavation in hard/ dense soil with the use of Earthmoving machinery/ labour and taking out oldCI/ GI /MSdefective/ misaligned water pipe line of size 200/150/100/80 mm dia bore carefully after disconnection of joints to a length up to 8 mtr and create bund with excavated earth and dewatering/ bailing out water complete with diesel engine driven pump set and positioning the pipe line after repairs, returning filling and removal of surplus soil/ excavated material with the help of excavator/ proclainer all as directed by Engineer-in-Charge. |
| 19 | NOTE: (a)M/L for LeadJoints/ spares / CI /GI specials will be measured and paid separately.(b)M/L for CI / GI/MS pipe, Specials, lead joints etc. will be measured and paid separately under relevant Schedule Items(c)The rate is deemed to include Cost for tool and plant and transportation required for attending the repair work.(d)Disconnecting / dismantling/ cutting the existing pipe line is included in the quoted rate .(e) The rate is inclusive of earth work complete including returning & refilling in any type of strata complete. (f) The breakdown shall be attended within 4 Hrs. of intimation round the clock and time of restoration shall be maximum of 8 Hours. The additional manpower required to complete the job in quoted rate is deemed to be included in the quoted. |
| 20 | M & L for CI fittinglike tees, bend, sockets ,collars of any typewith rubber gaskets and jointing material complete all as specified for sizes upto 100 mm dia DI pipe line complete all as specified and directed. |
| 21 | S&F in repair High density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 for the following size laid in trenches/ on floor/ walls etc. complete all as specified and directed including dismantling old defectivepipe lines. Note: The rate quoted deemed to be inclusive of all fittings necessary for fixing the pipe to GI pipes wherever required, complete all as specified and directed. |
| 22 | 20 mm bore |
| 23 | 25 mm bore |
| 24 | 40 mm bore |
| 25 | Supply, fixing, testing connecting air release valve of size 80 mm dia with 1 air outlet Kinetic design with isolating valve as per IS 14845 including dismantling of unserviceable Air release valve on150 to 200 mm dia CI/DI pipeline complete all as specified and directed. |
| 26 | Supply and fixing gun metal gate valve with iron wheel head screwed both ends for iron pipe of following size including dismantling old one, complete all as specified and directed. |
| 27 | 15 mm bore |
| 28 | 20 mm bore |
| 29 | 25 mm bore |
| 30 | 40 mm bore |
| 31 | 80 mm bore |
| 32 | Supply and laying in trenches/on roof/ on wall/ steel water tubing galvanised medium grade with all fittings of following sizes, complete all as specified and directed. |
| 33 | 15 mm bore |
| 34 | 20 mm bore |
| 35 | 25 mm bore |
| 36 | 40 mm bore |
| 37 | 50 mm bore |
| 38 | 80 mm bore |
| 39 | Taking up and down old/unserviceable GI tubing with fittings of following size complete all as specified and directed. (Earth work will be measured and paid under respective items of sch \"A\"). |
| 40 | 15 mm bore |
| 41 | 20 mm bore |
| 42 | 25 mm bore |
| 43 | 40 mm bore |
| 44 | 50 mm bore |
| 45 | 80 mm bore |
| 46 | Laying only / Refixing only GI tubingincluding fittingssuch as bends, elbows sockets, unions etc. as required bore dia complete all as specified and directed. |
| 47 | 15 mm bore |
| 48 | 20 mm bore |
| 49 | 25 mm bore |
| 50 | 40 mm bore |
| 51 | 50 mm bore |
| 52 | 80 mm bore |
| 53 | M&L for carrying out physical, chemical & Bacteriological analysis all as per IS 10500:2012 for Drinking water sample of the Fresh water from Pump Houses at various locations from approved laboratory, complete all as specified and directed.Note : The rate quoted deemed to inclusive of collecting water sample in Sterilized bottle/PVC container & submitting the same for testing. |
| 54 | Repair to GI pipe lines of size 15 to 25 mm bore dia and repair to leaked joints of pipe line complete including replacement of GI fitting i.e. union, nipple & sockets if required including excavation and taking up & down required cutting & threading refixing in position in trenches, complete all as specified and directed. |
| 55 | All as per serial item No. 19 here-in- before but size 40 to 80 MM bore. |
| 56 | M&L for Dismantling of old U/S valve pit and making new of size 120x120x90 Cm ( internal dimensions of the chamber)including and removingthe debrisat a distance not exceeding 50 Mtr and M/L for brick masonry with cement mortar with 1: 6 , 23 cm and flush pointing externally work proceeds in the same mortar complete ( using 30% old bricks & 70% New bricks) complete with the following specifications and as directed by Engr-in-Charge.Note :-(i) 10mm thick plaster internally in CM 1:6.(ii) Flooring 40mm thick in PCC 1:2:4 type B-1 over 75mm thick hard coreofguage not exc 63mm thick. (iii)Angle ironframe40X40X6mm thick for cover and mild steel 3mm thick cover with locking arrangement, handle and necessary hinges etc., (iv) PCC 1:3:6 type C-2 100mm thick in foundation .(v) Two coat of synthetic enameled paint to cover internally and externally over a paint of Red Oxide primer. |
| 57 | All as per serial item No. 21 here-in-before butof size 100x100x105 cm |
| 58 | All as per serial item No. 21 here-in-before butof size 90x90x105cm |
| 59 | All as per serial item No. 21 here-in-before butof size 60x60x60 cm |
| 60 | Supply and fixing in repair Rubber gasket joint suitable for 200 mm bore cast iron/DI pipes all as specified and directed. |
| 61 | Supply and fixing in repair Rubber gasket joint suitable for 150 mm bore cast iron/DI pipes all as specified and directed. |
| 62 | Supply and fixing in repairRubber gasket joint suitable for 80 mm bore cast iron/DI pipes all as specified and directed. |
| 63 | S&F in repair Cl swing check NRV conforming to IS-5312, suitable for 100 mm bore pipe consisting Cast iron Body, door as per IS 210, Bronze body ring as per IS 318, natural rubber door face, hinge pin SS ASTM A276 type 410, fasteners as per IS 1367, Natural rubber gasket,etc. completedouble end flanged and drilled,ofClass PN-1.6 ( ISI marked) including all jointing materials such as rubber gasket insertionsheet nut ,bolts and washers etc. complete all as specified and directed. |
| 64 | S&F in repair Cl swing check NRV conforming to IS-5312, suitable for 150 mm bore pipe consisting Cast iron Body, door as per IS 210, Bronze body ring as per IS 318, natural rubber door face, hinge pin SS ASTM A276 type 410, fasteners as per IS 1367, Natural rubber gasket,etc. completedouble end flanged and drilled,ofClass PN-1.6 ( ISI marked) including all jointing materials such as rubber gasket insertionsheet nut ,bolts and washers etc. complete all as specified and directed. |
| 65 | Dismantling old defective water meters and M & L for CI water meter Woltman type Magnetic Drive Class-B Flanged end of size 150 mmcomplete all as specified and directed. |
| 66 | M&L for making Feeder system for water line distribution including main pipe of 600mm and outgoing distribution lines from 50-200mm dia of pipe CI/DI/MS including all necessary fitting like all type of valve, elbow, nuts, bolts& welding work if required and other fittings as per site requirement all as specified and directed by Engr-in-Charge.Note:(i) The cost inclusive of necessary T&P of removing vertical turbine/submersible pumpset carefully without any damages to pump, motor, shaft, column pipe and casing. Any damages shall be beared by the Contractor at his own cost. (ii) The cost inclusive of required PCC work and hardstanding for the feeder system |
| 67 | Disconnecting the delivery line and providing dummy plate with nut, bolts to avoid water leakages and M&L for taking out vertical turbine pump /submersible pumpset of any make of capacity20 HP to 35 HP from the tubewell/borewell carefully complete with column pipe for inspecting the condition of column pipe, pumpset &flat submersible cable etc. complete all per site requirement complete all as specified and directed.Note:(i) The cost inclusive of necessary T&P of removing vertical turbine/submersible pumpset carefully without any damages to pump, motor, shaft, column pipe and casing. Any damages shall be beared by the Contractor at his own cost. (ii) The rate inclusive of dismantling of motor of Vertical turbine pump set.(iii) The M/L for repairs to pumpsets/ column pipe/cable if required & measured and paid separately under relevant Schedule. |
| 68 | Lowering vertical turbine pump /submersible pumpset of any make of capacity20 HP to 35HP inside the tubewell/borewell carefully complete with column pipe and other connected parts and including replacement of nut ,bolts, washers, gasket of suitable size all per site requirement and re-connection with delivery line with nut ,bolts, washers, gasket of suitable size allas specified and directed.Note:(i) The cost inclusive of necessary T&P of lowering vertical turbine/submersible pumpset carefully without any damages to pump, motor, shaft, column pipe and casing. Any damages shall be beared by the Contractor at his own cost. (ii) The rate inclusive of re-connection of motor of Vertical turbine pump set. |
| 69 | Taking out electric vertical turbine motor of capacity 20 to 35 HPfrom the existing foundation, transport to workshop for rewinding by using super enameled copper winding wire of existing wire gauge including other allied items such as varnish tape, sleeve, greasing etc. of suitable size for 20 to 30 HP capacity of motor and refixing after testing and commissioning complete all as specified and directed. |
| 70 | S & F in replacement of thrust bearing all as per existing for motor of capacity 20 HP to 35 HP, complete all as specified and directed. |
| 71 | S & F in replacement of ball bearing all as per existing for pump of capacity 20 HP to 35 HP, complete all as specified and directed. |
| 72 | S & F in replacement of ratched plate assembly for vertical turbine pump with suitable coupling with reversible pin, balls, plate & pulley of pump of capacity 20 HP to 35 HP, complete all as specified and directed. |
| 73 | S & F in replacement of oil seal of pump of capacity 20 HP to 35 HP, complete all as specified and directed. |
| 74 | Dismantling rotor shaft of 3 phase electric motor of capacity 20 HP to 35 HP, welding to bearing size of rotor, check nut size of rotor & turning, polishing, threading & grinding etc. upto required size of bearing all as specified and directed. |
| 75 | Turning to bearing size of motor top & bottom covers, providing joinings of new bearing sleeves of CI for bearings no. 7220. 7316,6311,6310 etc. and grinding upto required bearing size all as specified and directed. |
| 76 | Dismantling the bowl assembly of Vertical Turbine Pump any type, capacity and make for carrying out repair and replacement of worn out parts by strip opening of all parts such as impellers, pump shafts, lock collects, bushes, neck rings etc. and machine work such as welding, turning, refacing where required and replacing of defective parts up to and including 11 stages of size 150mm dia for pump capacity of 30 to 50 HP, complete all as specified and directed.Note: - Spare parts and their fixing shall be paid separately under the respective items of schedule \"A\" |
| 77 | S&F in replacement of pump shaft 30 to 38 mm dia of stainless steel suitable for bowl assembly upto 12 stages including threading, cutting to size all as specified and directed. |
| 78 | S&Finreplacement gun metal impellers of suitable size for bowl assembly casing as per site requirement for suction, discharge and intermediate bowls complete all as specified and directed. |
| 79 | S&F in replacement intermediate gun metal bush for bowl assembly of suitable size as per site requirement of make and model as per existing for suction, discharge and intermediate bowls of size 100mm to 150mm complete all as specified and directed. |
| 80 | S&F in replacement cast iron bowl casing of size suitable as per site requirement, any type, make and model as per existing for suction, discharge and intermediate bowls of size 100mm to 150mm dia including studs, nuts, bolts and washers complete all as specified and directed. |
| 81 | S&F in replacement neck ring of bowl casing made out of gun metal/brass for assembly of suitable size as per site requirement, any type, make and model as per existing for suction, discharge and intermediate bowls complete all as specified and directed. |
| 82 | S&F in replacement impeller lock collects for bowl assembly of suitable size as per site requirement any type, make and model as per existing for suction, discharge and intermediate bowls complete all as specified and directed. |
| 83 | S&F in replacement neck ring for impellers made out of gun metal/brass for assembly of suitable size as per site requirement, any type, make and model as per existing for suction, discharge and intermediate bowls complete all as specified and directed. |
| 84 | S&F in replacement rubber bush of bowl assembly of suitable size as per site requirement any type, make and model as per existing for suction, discharge and intermediate bowls complete all as specified and directed. |
| 85 | S&F in replacement studs with nuts, springs, washers complete all as specified and directed. |
| 86 | S&F in replacement spider lock/nut lock complete all as specified and directed. |
| 87 | S & F in repair Mild steel column pipe for vertical turbine pump 150 mm dia, heavy grade and 3 mtr. Long duly threaded on both sides as per site requirement including one mild steel coupling all as specified and directed. |
| 88 | M&L Strip opening of 3 phase AC submersible motor, taking out burnt winding coil complete and re-winding with PVC insulated super quality water proof winding wire including PVC seal (water proof compound) and thrust bearing as per requirement of existing size and make, re-assembling the motor and testing complete of capacity 20 to 35 HP motor. |
| 89 | Taking out worn out bearing/ bush sleeves from the submersible motor of capacity 20 to 35 HP and providing new stainless steel, turning and polishing of bushes complete including checking of alignment complete in all respect all as specified and directed. |
| 90 | S & F in replacement of thrust bearingplate along with disc of motor of capacity 20 HP to 35 HP, complete all as specified and directed. |
| 91 | S & F in replacement of oil seal of motor of capacity 20 HP to 35 HP, complete all as specified and directed. |
| 92 | Dismantling the submersible pumping set bowl assembly/motor of any make for carrying out repair and replacement of worn out parts by strip opening with all parts such as bowl casing, impellers, pump shaft, bushes neck ring etc.and machine work such as welding, turing, re-facing where required and replacing of parts of pump of 4 to 9 stages, size 150mm, of capacity 20 HP to 40 HP capacity complete all as specified and directed.Note: - Spares parts and their fixing shall be paid separately under the respective item of schedule \"A\" |
| 93 | S&F in replacement of pump shaft of stainless steel suitable for submersible pump set up to 9 stages including threading, cutting to required size all as specified and directed. |
| 94 | S & F in replacement of gun metal/Stainless Steel impellers of suitable size for bowl assembly of submersible pumping set as per site requirement for suction, discharge and intermediate bowls complete all as specified and directed. |
| 95 | S & F in replacement ofcast iron casing suction/discharge/ intermediate with studs, all as required at site and directed. |
| 96 | S & F in replacement of shaft seal of rubber all as specified. |
| 97 | S & F in replacement neck ring of bowls suction/discharge/ intermediate all as required at site and directed. |
| 98 | S & F in replacement of gun metal bush of bowls all as required at site and directed. |
| 99 | S & F in replacement of rubber bushes of bowls assembly of suitable, make and model as per existing for suction and discharge bowls all as required at site and directed. |
| 100 | S & F in replacement of shaft coupling with key stainless steel of suitable sizes, type, make and model as per existing, all as required at site and directed. |
| 101 | S & F in replacement of stainless steel middle/distance bush of suitable size all as required at site and directed. |
| 102 | S & F in replacement of stainless steel impeller key all as specified and directed. |
| 103 | S & F in replacement of studs with nuts all as directed. |
| 104 | Supply and fixing in repair of mild steel column pipe coupling 150 mm dia, heavy duty 3.0 Mtr long threaded or flanged all as specified and directed. |
| 105 | Supply and fixing in repair of mild steel column pipe coupling 125 mm dia, heavy duty 3.0 Mtr long threaded or flanged all as specified and directed. |
| 106 | Supply and fixing in repair of mild steel column pipe coupling 100 mm dia, heavy duty 3.0 Mtr long threaded or flanged all as specified and directed. |
| 107 | Supply and fixing in repair of mild steel column pipe coupling 80 mm dia, heavy duty 3.0 Mtr long threaded or flanged all as specified and directed. |
| 108 | Supply and fixing in repair line shaft bearing retainer of gun metal with rubber bushes for column pipe 150 mm dia all as specified and directed. |
| 109 | Supply and fixing of stainless steel shaft sleeve of size 25 mm to 31 mm dia all as required at site and directed. |
| 110 | Cutting and removing worn out threaded portion of mild steel column pipe heavy duty and re threading the same up to specified length to match with socket of size 150 mm dia. |
| 111 | Cutting and removing worn out threaded potion mild steel/stainless steel line shaft of any dia, length and rethreading the same up to specified length to match with existing coupling all as specified and directed. |
| 112 | S & F in repair new bolts with nuts and washers in places of existing worn out/unserviceable bowl bolts. |
| 113 | Dismantling of Vertical Turbine motor 30 to 45 HP including discharge head and top shaft, stuffing box. Replacement of gun metal bushes, filling of gland packing, Replacement of studs of discharge head and top shaft of length up to 10 ft including top nuts and locking nuts. |
| 114 | Supply and fixing submersible cable 16 Sqmm copper 3 core all as specified and directed by Engr-in-charge. |
| 115 | M& L for chlorination treatment with high stable Calcium based granular disinfectant for water treatment, more stable than Chlorine Gas, and stronger than bleaching powder, and sodium Hypochlorite) packing in 45 kg drum complete all as specified and directed by Engr-in-Charge. |
| 116 | S&F in repair chlorination dosing system booster pump of capacity S/D size 1\"x1\"(5 HP) 4 stage with suitable coupling asdirected. |
| 117 | S&F in repair chlorination dosing system motor 3 phase 400/440 volts 50 c/s of 5 HP capacity all as directed. |
| 118 | S&F in repairs submersible pump controller fully automatic type in sheet enclosure for maximum motor output 30 HP/22.5 KW with relay max range 28 to 42 Amps suitable for AC -3 duty, 415 V 50 Hz, 3 Phase AC supplywith overload, Single Phasing,Phase imbalance, auto restart features, IP 54 enclosure complete withLED indication lamps, push buttons etc. complete. |
| 119 | S&F in repairs submersible pump controller oil immersed type in sheet enclosure for maximum motor output 30 HP/22.5 KW with relay max range 28 to 42 Amps suitable for AC -3 duty, 415 V 50 Hz, 3 Phase AC supplywith overload, Single Phasing,Phase imbalance, auto restart features, IP 54 enclosure complete withLED indication lamps, push buttons etc. complete. |
| 120 | S&F in repair single phase preventor relaywith timer for auto restart option with protection features against single phasing, phase reversal, phase unbalance etc. complete with control wiring all as directed. |
| 121 | S&F in repair electronic timers suitable for fully automatic star delta starter panel suitable for 240/360/415 V AC supply operation with timer range 3 to 30 Sec, 12 to 120 Sec complete with control wiring all as directed. |
| 122 | S&F in repair Multifunction meter for measuring Volt/ Amp/ frequency meter with inbuilt selector switch class 0.5/1.0 , 230 V AC Aux supply 96x96 Sqmm size suitable for 5A CT. |
| 123 | S&F in repairDigital Ammeter for measuring Amps with inbuilt selector switch class 0.5/1.0 , 230 V AC Aux supply 96x96 Sqmm size suitable for 5A CT all as required at site and directed. |
| 124 | S&F in repairDigital Voltmeter for measuring Voltage with inbuilt selector switch class 0.5/1.0 , 230 V AC Aux supply 96x96 Sqmm size all as required at site and directed. |
| 125 | M&L forcleaningto chambers internal surfaces of RCCoverheadreservoir capacity50000 glns, 18 mtr staging or above of any type by removing bleachingpowder/Al-Tock residue, silt sand, mud, fungus etc. withsteelwirebrushandgetting out.Cleaning, washingandflushing including writing date of cleaning and due date of cleaning withsyntheticenameledwhite paint on black back ground (Black back ground shall be painted with synthetic enameled black paint) letter n.exc. 10cm inheight including all T&P required. Three Photographs of inside surface of tankof each OH Tanks should be taken before cleaning & after cleaning and submitted to Engineer-in-charge in coloured hard copy complete all as specified and directed. Note:- (i) Rates are to be including charges of hiring T&P.(ii) Contractor shall be responsible for care and safety of person deployed for cleaning to off reservoir. |
| 126 | All as per Srl item No. 90 here-in- before but upto 25000 gallons complete all as specified and directed. |
| 127 | M&L for preparation and painting the external surface of over head reservoir wire having staging 18 mtr capacity25000 to 50000 glns with two coats of exterior grade weather proof Cement base paint After Priming plastered and other surfaces with alkali resistant priming paint and painted to over head tank, railing and iron ladder ,doors with super synthetic, heat resistant paint complete all as specified and directedincluding all existing writing works with enameled paint complete all as specified and directed. Note:- (i) Rates are to be including charges of hiring T & P.(ii) Contractor shall be responsible for care and safety of person deployed for cleaning to off reservoir.(iii) The paint of incoming and outgoing pipes as per colour coding. |
| 128 | Disconnecting / Removing existing U/S scale type water level indicator and S&F dial type water level indicator suitable for Over Head Storage tank of height 15 m to 21 m staging complete with central movement plate, counter weight, centre dividing wheels, MS/CRCA enclosure, float and connecting control wire system from tank to indicator etc. complete grouted in PCCall as directed including testing and commissioning all as directed. |
| 129 | Note for item No 90 to 93: The rate quoted inclusive of all safety equipments, T&P for carrying out the repair/working on OH tanks and insurance to persons deployed for cleaning the over head tank. Any unforeseen incidents/accidents due to lack of safety norms shall be beared by the Contractor on \" No cost basis\"without any extra claim from department. |
| 130 | S&F 4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA, 250 A complete all as specified and directed by Engr-in-Charge. |
| 131 | S&F 4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA, 200 Acomplete all as specified and directed by Engr-in-Charge. |
| 132 | S&F 4 Pole MCCB, 415 V, Adjustable type with breaking capacity 16 KA, 160 Acomplete all as specified and directed by Engr-in-Charge. |
| 133 | S&F 100 Amps, 4 pole, 415 V MCCB, 16KA rating, complete all as specified and directed by Engr-in-Charge. |
| 134 | Supply and laying ductile iron pipe, S/S including specials, Class\"K-7\", with all fittings of following sizes, complete all as specified and directed. |
| 135 | 150 mm bore |
| 136 | 200 mm bore |
| 137 | M&L for fixing in repair Solar Panel alongwith connected items i.e inverter, UPS of capacity - 1475 VA, DC voltage - 24 VDC, Output voltage - 240 +- 5V, Single Phase and batteries 150/200 AH at pump houses of Kandrori and Mirthal area complete all as specified and directed by Engr-in-Charge. |
| 138 | Dismantling old defective flow meter and Supply, install, testing and commissioning of electromagnetic flow meter of size 80 mm dia bore with approx minimum flow range 5.4 Cum per Hr , maximum flow range 217.10 cum per Hr, hastealloy C-4 electrodes material, CS flange with ANSI 150, PTFE lining , digital display suitable for operation on 100 to 230 V AC 50 HZ supply with output 4 to20 mA DC for measuring water fluid complete all as specified and directed by Engr-in-Charge. |
| 139 | Dismantling old defective flow meter and Supply, install, testing and commissioning of electromagnetic flow meter of size 100 mm dia bore with minimum flow range 8.4 Cum per Hr , maximum flow range 339.20 cum per Hr, hastealloy C-4 electrodes material, CS flange with ANSI 150, PTFE lining , digital display suitable for operation on 100 to 230 V AC 50 HZ supply with output 4 to 20 mA DC for measuring water fluid complete all as specified and directed by Engr-in-Charge. |
| 140 | Note for item No.1 to 102: The work involves of various areas of AGE E/M (S) Pathankot. TheContractor shall depute manpower on daily basisattending and rectifying the job in time. If any breakdowns/complaints simultaneously occurred in any areas shall be attended simultaneously by deputing additional manpower/T&P for rectification of defects. The rate quoted deemed to be included for the same. Recovery for non attending of any type rectification/complaint/breakdowns shall be at the rate of Rs 2500 per day irrespective nature of complaint/defect. |
| 141 | Note: (i) In case the tenderer quotes different rates for similar item then lowest rate shall only be applicable for payment and contractor shall not have any claim on this account.(ii) The Schedule of Credit amount shall be deducted from the total of this schedule (BoQ) to arrive at Contract Sum. |