| 1 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel / PVC conduit as required. |
| 2 | 3x1.5 sqmm |
| 3 | 3 x 2.5 sq.mm |
| 4 | 3 x 4 sq.mm |
| 5 | 3 x 6 sq.mm |
| 6 | Supplying and fixing following size/modules GI box along with modular base and cover plate for modular switches in recess etc as reqd. |
| 7 | 3 Module (100mmX75mm) |
| 8 | 6 Module (200mmX75mm) |
| 9 | 8 Module (125mmx125mm) |
| 10 | 12 Module (200mmX150mm) |
| 11 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 12 | 5/6 amps switch |
| 13 | 3 pin 5/6 amps socket outlet |
| 14 | 15 /16 amps switch |
| 15 | 6 pin 15/16 amp socket outlet |
| 16 | Supplying and fixing suitable size G.I. box with modular plate and cover in front or in recess including providing and fixing 25A modular socket outlet and 25A modular SP MCB \"C\" curve including connections, painting etc. as required. |
| 17 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel /PVC conduit including dismantling as required. |
| 18 | Group C |
| 19 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 20 | Group C |
| 21 | Supplying and fixing of Heavy duty class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 22 | 25 mm dia |
| 23 | Supplying and fixing 2 module stepped type fan regulator on the existing modular plate switch box including connections but excluding modular plate etc as reqd. |
| 24 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB’s (but without MCB’s and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 12 way (4 + 24), Double door |
| 25 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 26 | Single Pole |
| 27 | Providing and fixing following rating and breaking capacityand pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 28 | 100 Amp , 16 KATPMCCB |
| 29 | 250 amps 36 KA , FPMCCB |
| 30 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 4 X 10 sq. mm + 2 X 6sq. mm earth wire |
| 31 | Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, refilling the trench etc as required. |
| 32 | Above 35 sqmm to upto 95 sqmm |
| 33 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 34 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of XLPEinsulated and PVC sheathed aluminium conductor cable of 1.1 KV grade as required. 3.5cx50 sqmm |
| 35 | Supply, Installation, testing and commissioning of pre-wired, single box fitting with one no. LED tube of frosted cover design, 18 Watt, 2100 lm, 50000 burning hours, size 1200 mm complete i/c all accessories etc. directly on ceiling/wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor cable and earthing etc. as required. fitting equivalent to Philips Make, Cat No. TMC 502 1xT-LED 22W, Tube equivalent to Philips Make, Cat No. Mas LEDTube 1200mm 18W 865 T8I-2100lm |
| 36 | Supply, Installation, testing and commissioning of one no. LED tube of frosted cover design, 18 Watt, 2100 lm, 50000 burning hours, size 1200 mm in existing single box or double box fittings complete as required. Tube equivalent to Philips Make, Cat No. Mas LEDTube 1200mm 18W 865 T8I-2100lm |
| 37 | Supplyingof one number of xlpe insulated and PVC sheathed/ aluminium cond. Power cable of 1.1 KV grade of following size 3.5c x 50 sqmm |
| 38 | Supplying and fixing of 63Amp, Four pole, (three phase and neutral), 415 V, residual current Breaker with overlaod protection(RCBO)having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. Equivlant to make legrand Cat. Nos 4113 74 |
| 39 | Supply, Installation,testing and comissioning of 15 inch heavy duty, AC, Single Phase 230 Volt, 50 Hz, 1350 RPM, steel body exhaust fan in the existing opening, including, making good the damage, cable connection etc. as required |
| 40 | Supply, Installation, testing and commissioning of pre wired 2\"x2\" recess mounted 36 watts LED fitting square shape, Commercial grade with luminaire with diffuser complete with all accessories i/c connection with 1.5 sqmm FRLS PVC copper conductor Cable with mounting 4 nos clutch wire /G.I. chain for mounting from true ceiling etc. as required. Make Philips, Model No. - FullGlow G6Cat No. RC380B LED36S-6500 G6 L60W60 PSU OD S1 or equivalent model of Thorn/Trilux |
| 41 | Supplying and Fixing of snap-on DLP trunking of size 105mm x 50 mm with cover and including accessories such as cover, Flat angle, end caps, internal/external angle support etc. on the wall/surface complete all as requied. |
| 42 | Replacement of condenser of 2.5/3.15 mfd for ceiling fan including making necessary connections etc. complete as required |