| 1 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 2 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required |
| 3 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 4 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm |
| 5 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm |
| 6 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 7 | Supply of PVC insulated and FR PVC Sheathed multicore copper conductor 1.1KV grade, conforming to grade IS 694 as required . 3*1.5 Sq.mm |
| 8 | Supplying and erection of galvanized D-iron complete with shackle insulator (75 x 90 mm ) GI bolt and nut coach screws etc as required. |
| 9 | Supply of XLPE insulated,PVC sheathed Al.conductor Armoured Cable 1.1 KV grade Conforming to IS 7098/1988 of following Sizes 2 X10 SQmm |
| 10 | Supply of XLPEinsulated and PVC sheathed Al conductor un-armoured cable of 1.1KV grade conforming to IS 7098 of following size:-(a) 2x6 sqmm |
| 11 | Drilling and laying i/c HDPE pipe of 40 mm outer dia with PN 4 rating by hand moling /manual methodConfirming to IS 4984. |
| 12 | Dismantling of pole/ street light standard/ strut embedded in brick ballast foundation etc. as required. |
| 13 | Fabrication, supply and erection of7.0 mtr height, 3 mm thick, bottom dia of 130mm and top dia of 70 mm base plate of size 225 x 225 x 12 mm thick flange mounted hot dip galvanized octagonal pole made from HT steel plate, window with flash cover with full vertical window cover at appropriate height from the base plate on existing cement concrete pedestal as required. i/c supplying and fixing of 6 mm thick laminated mounted sheet inside the window mounted on and i/c providing and welding 3 nos. GI strips 4 mm thick of suitable length and having suitable size tapped holes as reqd, terminal block suitable for 25 sq mm conductor- 4 nos. and shorting links on DIN channel i/cpdg and fixing DIN channel of suitable length, 6 Amp. SPMCB\"C\" Curve characteristics, earth stud, cable support clamp suitable for upto 4x25 sqmm cable. Logo/Name of manufacturer shall be either embossed or Rivited plateon the pole. Galvanization as per relevant IS code etc. as required. |
| 14 | Providing and laying in position M25 grade reinforced cement concrete foundation of size 600 mm (L) x 600 mm wide and 1200 mm deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia- 960mm long(approx)-8 nos. and reinforcement of cold twisted bars of 8 mm dia- 1600 mm (approx) -6 nos.(with 150 mm spacing) as required with supplying and positioning of 4 nos. foundation bolts 20 mm dia,700/750 mm long, J type i/c 2 nos. template anchor plates of size 225mmx225mmx3mm and providing DCW HDPE for cable entry and exit as required for 7 m. and 8 mtr pole. |
| 15 | Fabrication, supplying and fixing class B galvanised single overhang arm bracket made out of 250mm long galvanised top tube with cap and 1000mm long 40 mm dia galvanised pipe with tightening bolts complete as required. |
| 16 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP66,IK-10, CRI >80, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 72 watt |
| 17 | Supply and fixing of 32mm dia X 1 meter long G.I. Pipe (Medium Class) bracket for mounting of fluorescent/HPMV/HPSV Street Light fitting on pole including bending the pipe to the required shape , 2 nos 25mm X 6mm flat iron clamps with nuts, bolts and washer , painting the flat iron with primer and finish paint etc. as reqd. |
| 18 | Supplying,installation,testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required. 1 output per phase and suitable for single phase supply. |
| 19 | P/FHot press sheet mouldedcompound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof polebox of innerdimension 300x200x105mm (NS) and outer dimension of 333X233X150 mm high dome complete with suitable arrangement for fixing of 4 nosof 6 to 32 amp single pole MCB & 63 Amp. Doublepole isolator (MCB/Isolator excluded) withneutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plateofsuitable size with danger monogram property printed on the coveretc asreqd. |
| 20 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole |
| 21 | Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required. |