| 1 | Description of Items : |
| 2 | Electrical Work:- Providing and fixing 630 A rating, 50KA breaking capacity, and FPMCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 3 | Providing and fixing 250 A rating, 36KA breaking capacity, and FPMCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 4 | Providing and fixing 100 A rating, 30 KA breaking capacity, and FPMCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 5 | Laying of one number PVC insulated and PVCsheathed / XLPE power cable of 1.1 KV grade of 10 sq.mm size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 6 | Supply and Installation of 630A 4 Pole Manual change over switch |
| 7 | Supply and Installation of 250A 4 Pole Manual change over switch |
| 8 | Supply and Installation of multi function meter along with fixing of suitable size CT |
| 9 | Supply and Installation of RYB Indication Lamps along with wiring |
| 10 | Supplying, fabrication, and fixing the suitable size Alumnium busbars for all phases and neutral |
| 11 | Supplying, fabrication, powder painting and fixing the suitable dimensions of 2 mm & 1.6 mm CRCA sheet steel Panel Board including required number of partitions for housing switchgear along with suitable dimensions baseframe for housing the Panel including the required quantity and size of lugs, Glands, etc |
| 12 | Supply of 10 sq.mm, 4-Core, Aluminium Conductor, XLPE Insulated, PVC Inner Sheathed, Galvanized Steel Armoured, PVC Outer Sheathed Underground Cable, 1.1 kV grade, conforming to IS:7098 (Part 1) latest with ISI marking. Conductor: stranded aluminium as per IS:8130 Class 2, XLPE insulation with colour coding as per IS, cores laid up in concentric formation, inner sheath of extruded PVC Type ST2 as per IS:5831, armouring with galvanized steel strip/wire as per IS:7098, outer sheath of extruded PVC Type ST2 black in colour, UV/moisture/heat/chemical resistant, with manufacturer’s name, size, voltage grade and ISI mark printed at regular intervals. Cable shall be suitable for direct burial in ground, ducts or outdoor laying. Routine/acceptance tests as per IS:7098 to be carried out. Supply only, including manufacturer’s test certificates, with warranty of minimum 18 months from supply or 12 months from commissioning, whichever is earlier. |
| 13 | Supplying, installation, testing, and commissioning of outdoor-type powder coated IP-65 GI boxes for street light cable connections |
| 14 | Supplying, installation, testing and commissioning of energy efficient 70W LED street light luminaires with pressure die-cast aluminium housing, IP65 protection, toughened glass cover, high power SMD/COB LEDs (minimum efficacy 130 lm/W, system lumen output not less than 9000 lm), electronic driver (PF ≥ 0.95, THD < 10%, surge protection min. 4kV internal & 10kV external), suitable for 140–270V AC operation, mounted on existing pole arms with all accessories, connections, earthing, and making good of disturbances complete as required, conforming to IS:10322 (Part 5/Sec 3) and tested as per LM-79 & LM-80 standards. (Make: Bajaj / Crompton / Havells / Philips / Wipro / equivalent approved). |
| 15 | Supplying, installation, testing and commissioning of energy-efficient, eye-friendly 70W LED Flood light luminaire (halogen model design) with pressure die-cast aluminium housing, toughened clear or diffused glass cover, glare-free optical system, IP65 protection, high power SMD/COB LEDs (minimum efficacy 130 lm/W, system lumen output not less than 9000 lm), electronic driver (PF ≥ 0.95, THD < 10%, surge protection min. 4kV internal & 10kV external), suitable for 140–270V AC operation, mounted on existing pole arm with all accessories, wiring, connection, and earthing complete as required, conforming to IS:10322 (Part 5/Sec 3) and tested as per LM-79 & LM-80 standards. (Make: Philips / Bajaj / Havells / Crompton / Wipro / equivalent as approved by the Engineer In-charge). |
| 16 | Civil Work:- Earth work in excavation by mechanical means (Hydraulicexcavator)/manual means over areas (exceeding 30cm in depth,1.5m width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50mand lift upto 1.5m, disposed earth to be levelled and neatly dressed. All kinds of soil. All kind of soil |
| 17 | 15 mm cement plaster on the rough side of single or half brick wall of mix 1:4 (1 cement: 4 fine sand) |
| 18 | Brick work with clay fly ash F.P.S. (non modular) bricks of class designation 7.5 super structure above plinth level up to floor V levelin. Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 19 | Structural steel work in single section, fixed with or without connecting plate, including cutting hoisting, fixing in position and applaying a primimg coat of approved steel primer . |
| 20 | Providingand layinginposition cement concrete of specified gradeexcludingthe cost of centring and shuttering - Allworks upto plinth level. 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) |
| 21 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. Of area 3 sq. metres and below. cement motar |
| 22 | Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : Of area 3 sq. metres and below |
| 23 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. Nominal concrete 1:3:6 or richer mix (including equivalent design mix) |