| 1 | Taking down carefully copper/aluminium point wiring (light, fan socket or power) complete including fittings and fixtures such as switches, ceiling roses,pendants, regulators, sockets, light fittings etc removing material to store for keeping in safe custody or for taking credit ( credit for above items should be made as per condition seperately)andmaking good disturbed surface of walls, floors etc complete all as per the existing finish and as directed. |
| 2 | Material and labour forpoint wiring for light/fan/exhaust fan point controlled by one switchin casing & caping of suitable size but not less than 20mm including all fittings such as elbow, bends, junction boxes, saddles, etc. on surface with and including ISI marked two runs of PVC insulated unsheathed multistranded copper conductor cable (FRLSH) 1.5 sqmm nominal cross sectional area, 1100 volts grade and including one run of 1.5 sqmm (green colour) ISI marked PVC insulated unsheathed multistranded (FRLSH) copper conductor cable as earth wire to be terminated in and incl PVC rectangular block of suitable size for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover for one light point or one fan point controlled by one switch including making good the disturbed wall and painting the same with matching to existing wallall as specified and as directed. |
| 3 | Description all as per srl item No 2 above but point wiring for 5 pin switch socket outlet 5 Amps on independent board controlled by one switch. |
| 4 | Description allas per srl item No 2 above but point wiring for 5 pin switch socket outlet 5 Amps on same board controlled by one switch. |
| 5 | Description allas per srl item No 2 above butfor 2.5 sqmm point wiring for 5 pin switch socket outlet 15 Amps onindependentboard controlled by one switch. |
| 6 | Material and labour forpoint wiring for light/fan/exhaust fan point controlled by one switch inPVC conduit of suitable size but not less than 20mm including all fittings such as elbow, bends, junction boxes, saddles, etc. on surface with and including ISI marked two runs of PVC insulated unsheathed multistranded copper conductor cable (FRLSH) 1.5 sqmm nominal cross sectional area, 1100 volts grade and including one run of 1.5 sqmm (green colour) ISI marked PVC insulated unsheathed multistranded (FRLSH) copper conductor cable as earth wire to be terminated in and incl PVC rectangular block of suitable size for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover for one light point or one fan point controlled by one switch including making good the disturbed wall and painting the same with matching to existing wallall as specified and as directed. |
| 7 | Description all as per srl item No 6 above but 5 pin switch socket outlet 5 Amps on independent board controlled by one switch. |
| 8 | Description allas per srl item No 6 above but 5 pin switch socket outlet 5 Amps on same board controlled by one switch. |
| 9 | Description all as per srl item No 6 above but for for one 6 pin switch socket outlet 15 Amps/AC Point on independent board controlled by one switch in PVC conduit. |
| 10 | Material and labour for point wiring completeas specified with 1100 V grade4 Sqmm single core PVC insulated unsheathed multistranded copper conductor cable FR grade, conforming to relevant IS drawn through and including PVC casing and caping with all accessories fixed on surfaces of wall, ceiling, incl PVC rectangular block of suitable size for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover including 4 Sqmm single core PVC insulated and unsheathed copper conductor cable FR grade as earth continuity wire connected to common earthand earth dolly including testing complete all as specifiedand as directed.for one 6 pin switch socket outlet 15 Amps/AC Point on independent board controlled by one switch. |
| 11 | Description all as per srl item No 10 above but for for one 6 pin switch socket outlet 15 Amps/AC Point on independent board controlled by one switch in PVC conduit. |
| 12 | Supplying and fixing ceiling rose PVC/polycarbonate, isolated body, three terminals, complete all as specified and asdirected . |
| 13 | Supply and fix switch socket combination 2 in 1, 5 pin, 5 Amp flush type universal complete all as specified and asdirected. |
| 14 | Supply and fix switch socket combination 2 in 1, 3 pin, 5 & 15 Amp flush type universal complete all as specified and asdirected. |
| 15 | Supply and fix switch piano flush type single pole, one way 5 Amp complete all as specified and asdirected. |
| 16 | Dismantling and taking out old unserviceable copper / aluminium sub main wiring/unarmoured cable (used as sub main wiring) from any height of any size and core with all connecting accessories incld. conduit or casing caping and incld. making good to the disturbed wall and painting the same with matching paint as of existing wall including material complete all as specified and asdirected. |
| 17 | Material and labour for sub main wiring at any height with 2 single core PVC insulated, multi stranded copper conductor cable (FRLSH), unsheathed, 1.5 sqmm, 1100 volt grade conforming to IS drawn through and including New 20 mm PVC conduit and including one single core PVC insulated multi stranded unsheathed copper conductor cable, 1.5 sqmm,, FRLSH green in colour as continuous earth wire including all accessories and fixing arrengements, supporting clamps, bends, sockets and connecting items etc.complete all as specified and asdirected. |
| 18 | Description all as per Srl item No 17 above but for casing & capping |
| 19 | Material and labour for sub main wiring at any height with 2 single core PVC insulated, multi stranded copper conductor cable (FRLSH), unsheathed, 2.5 sqmm, 1100 volt grade conforming to IS drawn through and including New 20 mm PVC conduit and including one single core PVC insulated multi stranded unsheathed copper conductor cable, 2.5 sqmm,, FRLSH green in colour as continuous earth wire including all accessories and fixing arrengements, supporting clamps, bends, sockets and connecting items etc. all as specified and as directed. |
| 20 | Description all as per srl item No 19 above but for casing & capping |
| 21 | Material and labour for sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, conforming to IS, FRLSH type, 4.0 Sqmm, 1100 volts grade, drawn through and including New PVCconduit 20 mm dia including connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable,FRLSH type, 4.0 sqmm, 1100 Volts grade,,green in colour as earth contuinity wire all as specified and as directed. |
| 22 | Description all as per srl item No 21 above but for casing & capping |
| 23 | Material and labour for sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, conforming to IS, FRLSH type, 6.0 Sqmm, 1100 volts grade, drawn through and includingincluding New PVCconduit 20 mm dia connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable,FRLSH type, 6.0 sqmm, 1100 Volts grade,,green in colour as earth contuinity wire all as specified and directed. |
| 24 | Description all as per Srl item No 23 above but for casing & capping |
| 25 | Material and labour for sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, conforming to IS, FRLSH type,10.0 Sqmm, 1100 volts grade, drawn through and includingincluding New PVCconduit 20 mm dia connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable,FRLSH type,10.0 sqmm, 1100 Volts grade,,green in colour as earth contuinity wire complete all as specified and asdirected. |
| 26 | Description all as per srl item No 25 above but for casing & capping |
| 27 | Dismantling and drawing out old unserviceable sub main Aluminium/copper wiring from Existing Steel/PVC Conduit of any size and any type from any height with all connecting accessaries (excluding conduit or casing caping) and making good the disturbed wall and painting the same with matching to existing wallincluding material complete all as specified and asdirected. |
| 28 | Material and labour sub main wiring at any height including using two single core PVC insulated copper conductor cable (FRLSH) of size 1.5 sqmm 1100 volt grade conforming to IS drawnthrough existing Steel/ PVC conduit including 1.5 sqmm. PVC multi stranded copper conductor cable (FRLSH)green in colour for continuous earthing complete all as specified and asdirected. |
| 29 | Material and labour sub main wiring at any height including using two single core PVC insulated copper conductor cable (FRLSH) of size 2.5 sqmm 1100 volt grade conforming to IS drawnthrough existing Steel/ PVC conduit including 2.5 sqmm. PVC multi stranded copper conductor cable (FRLSH) green in colour for continuous earthing complete all as specified and asdirected. |
| 30 | Material and labour for sub main wiring at any height with four single core PVC insulated copper conductor cable (FRLSH) of size 6 sqmm 1100 volt grade conforming to IS drawnthrough Existing Steel / PVC conduit including two single core 6.0 sqmm PVC multi stranded copper conductor cable (FRLSH) green in colour for continuous earthing all as specified and directed. Note for item No 28 to 30 : - (a). Two/Four runs ofwiring cable and One/two runs of earth continuity wire shall be measured as one length. |
| 31 | Dismantling and taking down unserviceable any light fitting from any location/height after disconnecting of electrical connection complete including all connected accessories complete all as specified and asdirected. |
| 32 | Supply and fixing, LED tube light fitting suitable for and including 1x20 W 4 feet long tube with polycarbonate diffuser complete including connecting up to ceiling rosewith suitable size & all accessories for fixing on steel trusses / false / normal ceiling all as specified & directed. |
| 33 | Supply and fixing, 36W 2X2 LED recessed mounting light fitting complete including connecting up to ceiling rose with twin core twisted flexible copper conductor cable with suitable size & all accessories for fixing on steel trusses / false / normal ceiling complete all as specified and asdirected. |
| 34 | Supply and fixing, 36W 2X2 LED surface mounting light fitting complete including connecting up to ceiling rose with twin core twisted flexible copper conductor cable with suitable size & all accessories for fixing on steel trusses / false / normal ceiling complete all as specified and asdirected. |
| 35 | Supply and fixing, CRCA housing box LED Type luminiare suitable for and including 2x20 W 4 feet long complete including tube rod & connecting up to ceiling rose with twin core twisted flexible copper conductor cable with suitable size & all accessories for fixing on steel trusses / false / normal ceiling complete all as specified and asdirected. |
| 36 | Supply and fixing at 5 to 9 mtr height-100W Industrial LED Highbay luminaire with > 100 Lm/W,with complete all accessorieshaving IP 66 degree of protection, power factor >0.95,THD<10%, potted driver, Internal Surge Protection-4KV &complete all as specified and as directed.NOTE :- The quoted rates are deemed to be included the cost of Nut-bolts washars or clamps required to be replaced if old one are found unserviceable. |
| 37 | Supply and fixing at 5 to 9 mtr height-150W industrial LED highbay luminaire with 110Lm/W,with complete all accessorieshaving IP 66 degree of protection, power factor >0.95,THD<10%, potted driver, internal surge Protection-4KV & External Surge Protection-10KV, LED Source including safety chain with i boltcomplete all as specified and as directed .NOTE :- The quoted rates are deemed to be included the cost of Nut-bolts washars or clamps required to be replaced if old one are found unserviceable. |
| 38 | Supply and fix MCCB thermal magnetic releasefour pole 25 KA 63 Ampswith one way metal enclosure and making conections of cables with suitable size nutbolt etc including dismantling the old one and making good the disturbed suface of wall complate all as specified and as directed. |
| 39 | Supply and fix MCCB thermal magnetic release four pole 25 KA 100 Amps with one way metal enclosureand making connections of cables with suitable size nutbolt etc includingincludingdismantling the old one andmaking good the disturbed suface of wall including material complate all as specified and as directed. |
| 40 | Supply and fix MCCB thermal magnetic release four pole 25 KA 160 Ampswith one way metal inclosureand making connections of cables with suitable size nuts, bolt etc includingdismantling the old one and making good the disturbed suface of wall complate all as specified and as directed. |
| 41 | Supply and fix Industrial plug and socket board TP 32 Amps includingplug top and MCB \"C\" curve 10 KA 32 Ampsand making connections of cables with suitable size nuts, bolt etc includingdismantling the old one andmaking good the disturbed suface of wallcomplete all as specified and as directed. |
| 42 | Supply and fix one way metal ednclosure all as per and MCB \"C\" curve TPN 10 KA 32Amps and making conections of cables with suitable size nuts, bolt etc. includingdismantling the old one and making good the disturbed suface of wall complete all as specified and as directed. |
| 43 | Supply, fixing, connecting and testing in replacement of industrial earth plug & socket with sheet metal enclosure of IP 44 protection rating,electric driven, single phase including MCB \"C\" series SP 20 Amps and supplied with neutral linkincludingdismantling the old one and making good the disturbed suface of wall complete all as specified and as directed. |
| 44 | Supply, fixing, connecting and testing in replacement industrial earth Plug & socket with sheet metal enclosure of IP 44 protection rating, electric driven three phase including MCB \"C\" series TP 20 Amps and supplied with neutral linkincludingdismantling the old one and making good the disturbed suface of wall complete all as specified and as directed. |
| 45 | Disconnecting and taking down olddistribution box with MCB/fuse grip TPN/SPN DB 2 Way to 12 Way old type DB including taking out all cable connections of any description and in any position and making good the disturbed surface of walls, to match with the existing surfaces complete all as specified and as directed. |
| 46 | Supply and fixing, connecting & testing of VTPN DB of 12 way suitable for MCCBup to 160A as a incomer & SP / TP MCB as a outgoings with IP 43 -IK09 as conforming to IEC 61439-3 & made of high quality CRCA sheet shall have integrated door earthing system, shall have reversible door facility, ergonomic design with rounded corners to protect against damage like bending, peeling of paint hence preventing rusting. DB shall be with Insulated Busbar with withstand capacity of 36kA, shrouded neutral bar, Door earthing, corner safe. wiresets, shrouded Neutral bar, earth bar & wire ties, all as specified and as directed. NOTE :- MCCB , MCBwill be measured and paid separately under relevant item of this schedule. |
| 47 | Supply and fixing, connecting & testing of VTPN DB of 8 way suitable for MCCBup to 160A as a incomer & SP / TP MCB as a outgoings with IP 43 -IK09 as conforming to IEC 61439-3 & made of high quality CRCA sheet shall have integrated door earthing system, shall have reversible door facility, ergonomic design with rounded corners to protect against damages like bending, peeling of paint hence preventing rusting. DB shall be with Insulated Busbar with withstand capacity of 36kA, shrouded neutral bar, door earthing, corner safe. wiresets, shrouded Neutral bar, earth bar & wire ties, all as specified and as directed. NOTE :- MCCB, MCBwill be measured and paid separately under relevant item of this schedule. |
| 48 | Supply and fixing, connecting & testing of VTPN DB of 4 way suitable for MCCBup to 160A as a incomer & SP / TP MCB as a outgoings with IP 43 -IK09 as conforming to IEC 61439-3 & made of high quality CRCA sheet shall have integrated door earthing system, shall have reversible door facility, ergonomic design with rounded corners to protect against damages like bending, peeling of paint hence preventing rusting. DB shall be with Insulated Busbar with withstand capacity of 36kA, shrouded neutral bar, Door earthing, corner safe. wiresets, shrouded Neutral bar, earth bar & wire ties, all as specified and as directed. NOTE :- MCCB , MCBwill be measured and paid separately under relevant item of this schedule. |
| 49 | Supply and fixing, connecting & testing SPN DBs of 8 way for using MCBs / MCB isolators suitable for single pole and neutral, with IP 43 -IK09 as conforming to IEC 61439-3 & made of high quality CRCA sheet shall have integrated door earthing system, shall have reversible door facility, ergonomic design with rounded corners to protect against damages like bending, peeling of paint hence preventing rusting. DB shall be with Insulated Busbar with withstand capacity of 10kA, shrouded neutral bar, door earthing, corner safe. wiresets, shrouded Neutral bar, earth bar & wire ties, all as specified andas directed. |
| 50 | Supply and fixing, connecting & testing SPN DBs of 12 way for using MCBs / MCB isolators suitable for single pole and neutral, with IP 43 -IK09 as conforming to IEC 61439-3 & made of high quality CRCA sheet shall have integrated door earthing system, shall have reversible door facility, ergonomic design with rounded corners to protect against damages like bending, peeling of paint hence preventing rusting. DB shall be with Insulated Busbar with withstand capacity of 10kA, shrouded neutral bar, Door earthing, corner safe. wiresets, shrouded Neutral bar, earth bar & wire ties, all as specified and as directed. |
| 51 | Supply only MCCB FP, 16kA, 63 AMPS with thermal magnetic release,including spreader Terminals, disc onnecting and dismantling old unserviceable MCCB to the complete satisfaction all as specified and as directed.NOTE :-1.The MCCB must be compatible with lever/switch as per site requirements .2-All the addition/alterations for fixing MCCB with switch/lever is included in the above rate. |
| 52 | Supply only MCCB FP, 25kA, 100 AMPS with thermal magnetic release, including spreader Terminals, disconnecting and dismantling old unserviceable MCCB to the complete satisfaction all as specified and as directed. NOTE :-1.The MCCB must be compatible with lever/switch as per site requirements .2-All the addition/alterations for fixing MCCB with switch/lever is included in the above rate.. |
| 53 | Supply only MCCB FP, 25kA, 160 AMPS with thermal magnetic release,includingspreader Terminals, disconnecting and dismantling old unserviceable MCCB to the complete satisfaction all as specified and as directed.NOTE :-1.The MCCB must be compatible with lever/switch as per site requirements .2-All the addition/alterations for fixing MCCB with switch/lever is included in the above rate. |
| 54 | Supply only MCCB FP, 25kA, 200 AMPS with thermal magnetic release, includingspreader terminals, disconnecting and dismantling old unserviceable MCCB to the complete satisfaction all as specified and as directed.NOTE :-1.The MCCB must be compatible with lever/switch as per site requirements .2-All the addition/alterations for fixing MCCB with switch/lever is included in the above rate. |
| 55 | Supplying and fixing MCB 6 to 32 Amps, single pole and neutral, \"C\" curve10 kA breaking capacity with integrated label holder,sliding bottom clamp, color coded On/Off indication on dolly complete all as specified and as directed. |
| 56 | Supplying & fixingMCB 6 to 32 Amps, single pole, 10 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly,complete all as specified and as directed. |
| 57 | Dismantling of MS top covers of exisiting trunking bus bars (at a height of appx. 30 feet above GL ), scrapping the inside of the bus bar chamber to remove all dust particles and rusted iron particles, etc., vaccuming out all the dust particles inside the busbar chamber using a suitable vaccum cleaner and tightening of inter connections between copper bus bars within the trunking bus bar complete, including refixingthe covers andtesting of the same after completion of the job for the full satisfaction complete all as specified and as directed. |
| 58 | Dismantling of over head trunking bus bar of any capacity/rating including all connected outgoing cables and plug in boxes at a height of upto 10 mtr GL complete all as specified and as directed. |
| 59 | Supply installation, testing and commisioning of 1000 Amps aluminium bus bar sandwich type 3P+N , operating voltage 415V,insulation voltage 1.1kV rated short time current 18kA for 1SecIP54,certified complete all as specified and as directed.NOTE :- (i) Cost of any material and labour required for fixing of new bus bar in homogeneous with the existing old trunking bus bar is deemed to be included in the quoted rate. (ii) Fabrication of plug point on busbar as per directed by engineer in charge. |
| 60 | Description all as per serial item No.59 above but for bus bar trunking capacity of 630 Amps. |
| 61 | Description all as per serial item No.59 above but for bus bar trunking capacity of 400 Amps. |
| 62 | Description all as per serial item No.59 above but for Bus bar trunking capacity of 250 Amps. |
| 63 | Labour only for fabrication of flange endon busbar complete all as specified and as directed. |
| 64 | Dismantling of end feed unit with switchgear of any capacity including all connected accessories complete all as specified and as directed. |
| 65 | Supply and fix end feed unit with switchgear of250 Amps MCCB 4P, 25kAsuitable for sandwich type bus bar trunking system with complete all as specified and as directed. |
| 66 | Supply and fix end feed unit with switchgear of400 A MCCB 4P 36kAsuitable for sandwich type bus bar trunking system with complete accessories all as specified and as directed. |
| 67 | Supply and fix end feed unit with switchgear of630 A MCCB 4P 36kAsuitable for sandwich type bus bar trunking system with complete accessories all as specified and as directed. |
| 68 | Supply and fix end feed unit with switchgear of1000 A MCCB 4P 36kAsuitable for sandwich type bus bar trunking system with complete accessories all as specified and as directed. |
| 69 | Dismantling ofreducerwith switchgear of any capacity including all connected accessories complete all as specified and as directed. |
| 70 | Supply and fix reducerfor 1000 Amps to 630 Amps suitable for sandwich bus bar trunking system (of any rating) complete all as specified and as directed. |
| 71 | Supply and fix reducerfor 630 Amps to 400 Amps suitable for sandwich bus bar trunking system (of any rating) complete all as specified and as directed. |
| 72 | Supply and fix reducerfor 400 Amps to 250 Amps suitable for sandwich bus bar trunking system (of any rating) complete all as specified and as directed. |
| 73 | Supply and fix end cover suitable for sandwich type trunking bus bar system (of any rating) complete all as specified and as directed. |
| 74 | Dismantling of old plug in box, supply and fix rust proof steel sheet plug in box with hinged door housing four pole 32 Amp MCB \"C\" curve 10 KA ratingfully insulated plug in points which should be easily plugged in live bus bars of 32 Amps rating complete all as specified and as directed. |
| 75 | Dismantling of old plug in box, supply and fix rust proof steel sheet plug in box with hinged doors housing four pole 40 Amp MCB \"C\" curve 10 KA ratingfully insulated plug in points which should be easily plugged in live bus bars of 40 Amps rating complete all as specified and as directed. |
| 76 | Dismantling of old plug in box, supply, fix, test and commissioning rust proof steel sheet plug in box with side hinged doors housing 63 Amps, TPN, MCCB 25 kA,insulated pin-on contacts with provision of gland plates for cable entry, having fully insulated plug in points which should be easily plugged in bus bars of 63 Amps rating complete all as specified and as directed. |
| 77 | Dismantling of old plug in box, supply, fix, test and commissioning rust proof steel sheet plug in box with side hinged doors housing 100 Amps, TPN, MCCB 25 kA, insulated pin-on contacts with provision of gland plates for cable entry, having fully insulated plug in points which should be easily plugged in bus bars of 63 Amps rating complete all as specified and as directed. |
| 78 | Dismantling of old plug in box, supply, fix, test and commissioning rust proof steel sheet plug in box with side hinged doors housing 160 Amps TPN MCCB 25kA, insulated pin-on contacts with provision of gland plates for cable entry, having fully insulated plugin points which should be easily plugged in bus bars of 160 Amps rating complete all as specified and as directed. |
| 79 | Dismantling of old plug in box, supply, fix, test and commissioning rust proof steel sheet plug in box with side hinged doors housing250 Amps TPN MCCB 36kA, insulated pin-on contacts with provision of gland plates for cable entry, having fully insulated plugin points which should be easily plugged in sandwitch type bus bars system complete all as specified and as directed. |
| 80 | Dismantling of old plug in box, supply, fix, test and commissioning rust proof steel sheet plug in box with side hinged doors housing 400 Amps TPN MCCB 36 kA, insulated pin-on contacts with provision of gland plates for cable entry, having fully insulated plugin points which should be easily plugged in sandwitch type bus bars systemcomplete all as specified and as directed. |
| 81 | Dismantling of old plug in box, supply, fix, test and commissioning rust proof steel sheet plug in box with side hinged doors housing 630 Amps TPN MCCB 36 kA, insulated pin-on contacts with provision of gland plates for cable entry, having fully insulated plugin points which should be easily plugged in sandwitch type bus bars systemcomplete all as specified and as directed. |
| 82 | Material and labour for cross arms, bracings, supports, clamps and back plates fabricated from rolled structural steel sections including nuts, bolts, washers, welding, bending colt or hot, drilling holes for bolts, at any height, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint for mounting of bus bar trunking including fixing arrangements complete all as specified and as directed. |
| 83 | Disconnecting and taking out burnt XLPE aluminium conductor cable of any description and in any position from walls / steel structure / laid in floors any size any core complete all as specified and as directed. |
| 84 | Supply and laying in trenches / laid in floors /ducts / roof/trays XLPE insulated PVC beddedarmoured heavy duty electric cable 1100 voltsgrade with aluminum conductor of cross sectional area4 core, 16 sq.mm all as specified and as directed . |
| 85 | Supply and laying in trenches / laid in floors /ducts / drawn through conduit XLPE insulated PVC beddedarmoured heavy duty electric cable 1100 voltsgrade with aluminum conductor of cross sectional area3.5 core, 25 sq.mm all as specified and as directed . |
| 86 | Supply and laying in trenches / laid in floors /ducts / drawn through conduit XLPE insulated PVC beddedarmoured heavy duty electric cable 1100 voltsgrade with aluminum conductor of cross sectional area3.5 core, 35 sq.mm all as specified and as directed . |
| 87 | Supply and laying in trenches / laid in floors /ducts / drawn through conduit XLPE insulated PVC beddedarmoured heavy duty electric cable 1100 voltsgrade with aluminum conductor of cross sectional area3.5 core, 50 sq.mm all as specified and as directed . |
| 88 | Supply and laying in trenches / laid in floors /ducts / drawn through conduit XLPE insulated PVC beddedarmoured heavy duty electric cable 1100 voltsgrade with aluminum conductor of cross sectional area3.5 core, 70 sq.mm all as specified and as directed . |