| 1 | Excavation in trenches in soft/loose soil n.exc 1.5m wide and not exc 1.5m depth for laying of cable, errection of poles, stay andpipe line,and getting out complete all as specified and directed. |
| 2 | Returning & filling including spreading, leveling watering and well ramming in layers not exc 25 cm thick in any type of soil complete all as specified and directed. |
| 3 | Removal of excavated soil to a distance not exc 50 m above the starting point complete all as specified and directed. |
| 4 | Supply & laying double walled corrugated (DWC) HDPEfull rounded pipe in 6 mtr lenght conforming to IS 16205 Pt-24 of approved colour complete with fittings for cable protection of size 160 mm outer dia and 135 mm inner dia completed all as specified and directed. |
| 5 | Supply & laying double walled corrugated (DWC) HDPEfull rounded pipe in 6 m lenght conforming to IS 16205 Pt-24 of approved colour complete with fittings for cable protection of size 75 mm outer dia and 63 mm inner dia complete all as specified and directed. |
| 6 | Supply & laying double walled corrugated (DWC) HDPEfull rounded pipe in 6 m lenght conforming to IS 16205 Pt-24 of approved colour complete with fittings for cable protection of size 63 mm outer dia and 50 mm inner dia complete all as specified and directed. |
| 7 | M & L for drilling suitable dia horizontal bore holes for insertion/ laying of 50 to 350 mm bore GI/HDPE tubing of any description below/ under road surface/ floors etc with using mechanical or manual devices as required at site complete all as specified and directed. |
| 8 | Supply , laying & testing XLPE LT UG cable PVC insulated, beddedarmoured heavy duty electric cable 1100 volts grade with aluminum conductor of of cable 400 Sqmm 3.5 Core, including taking down the unserviceable UG cablecomplete all as specified and directed. |
| 9 | All as per item No-8 above but 150 Sqmm 3.5 Core |
| 10 | All as per item No-8 above but 120 Sqmm 3.5 Core |
| 11 | All as per item No-8 above but 70 Sqmm 3.5 Core |
| 12 | All as per item No-8 above but 50 Sqmm 3.5 Core |
| 13 | All as per item No-8 above but 25 Sqmm 4.0 Core |
| 14 | All as per item No-8 above but 16 Sqmm 4.0 Core |
| 15 | M&L for replacement of existing old unsv earthing with steelearth plate electrode ofsize 60cmx60cmx6mm thick buried directly in ground to a depth not less than 3.25mtr deep below normal ground level with top edge of the earth plate not less than 2.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full lenght of earth plate,40mm dia GI tubing light grade protection pipe upto test point, 20mm dia GI watering pipe with funnel and wire mesh, PCC pit 1:3:6 with pit cover of size 30X30cm made of RCC 1:3:6 with suitable handle,angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate,removal of surplus soil and returning filling in all as required at site including test point made out of steel plate of size 75x75x6mm fixed to wall all as specified in plate No 3 of SSR Part-I complete all as specified and directed. |
| 16 | M&L for preparation of steel surface of electric pole upto 11 Mtr longextension portion, apply one coat of aluminum paint over full length and marking of pole number and five strips as per approved colour by the departmetnusing synthetic enamel paint all as per existing complete all as specified and directed. |
| 17 | Supplying & fixing of energy-efficient 70watt LED street light fitting with pressure die-cast aluminum housing, IP65/IP66 protection, and suitable for operation on 120V– 270V AC, 50Hz. The luminaire should include high-power LEDs with suitable optics for road illumination, inbuilt electronic driver, and surge protection (minimum 10kV). The fitting shall be mounted on existing 9 mtr pole arms using standard clamps, nuts, bolts, and wiring connections,complete all as specified and directed. |
| 18 | Supplying & fixing of energy-efficient 60-watt LED street light fitting with pressure die-cast aluminum housing, IP65/IP66 protection, and suitable for operation on 120V– 270V AC, 50Hz. The luminaire should include high-power LEDs with suitable optics for road illumination, inbuilt electronic driver, and surge protection (minimum 10kV). The fitting shall be mounted on existing 9 mtr pole arms using standard clamps, nuts, bolts, and wiring connections,complete all as specified and directed. |
| 19 | Supplying & fixing of energy-efficient 45-watt LED street light fitting with pressure die-cast aluminum housing, IP65/IP66 protection, and suitable for operation on 120V– 270V AC, 50Hz. The luminaire should include high-power LEDs with suitable optics for road illumination, inbuilt electronic driver, and surge protection (minimum 10kV). The fitting shall be mounted on existing 9 mtr pole arms using standard clamps, nuts, bolts, and wiring connections,complete all as specified and directed. |
| 20 | Supplying & fixingof high-performance 120-watt LED flood light fitting, suitable for outdoor installation on poles or high masts. The luminaire shall be constructed from pressure die-cast aluminum housing with efficient heat dissipation fins, equipped with high-power LEDs and precision optics/lens for wide and uniform light distribution. The unit shall have IP66 ingress protection, inbuilt high-efficiency electronic driver, and minimum 10kV surge protection. It shall operate on 140–270V AC, 50Hz supply. The fitting shall be mounted securely on pole brackets or high mast arms using appropriate clamps, bolts, nuts, and wiring complete all as specified and directed.Note: All civil, electrical, and mechanical works required for the complete installation shall be included in the item rate |
| 21 | M & L for servicing of 415 Volt electrical panel indoor /outdoor type for for cleaning of dust particle inside the panel like MCCB , relay/contactor with help of blower etc and tightening of all electrical connection and complete testing and replacement of burnt lugs etc complete all as specified and directed. |
| 22 | supply and fixing in replacement of 4 pole MCCB, 36 KA ,3 phase, 50 Hz suitable for operation on 415 V with Thermal Magnetic Release of capacity 400 Amps along with all accessories as requiredfor connction ,including dismantling and removal of old unserviceable MCCB , complete all as specified and directed. |
| 23 | supply and fixing in replacement of 4 pole MCCB, 16 KA ,3 phase, 50 Hz suitable for operation on 415 V with Thermal Magnetic Release of capacity 125 Amps along with all accessories as requiredfor connction ,including dismantling and removal of old unserviceable MCCB , complete all as specified and directed. |
| 24 | supply and fixing in replacement of 4 pole MCCB, 36 KA ,3 phase, 50 Hz suitable for operation on 415 V with Thermal Magnetic Release of capacity 200 Amps along with all accessories as requiredfor connction ,including dismantling and removal of old unserviceable MCCB , complete all as specified and directed. |
| 25 | supply and fixing in replacement of 4 pole MCCB, 36 KA ,3 phase, 50 Hz suitable for operation on 415 V with Thermal Magnetic Release of capacity 160 Amps along with all accessories as requiredfor connction ,including dismantling and removal of old unserviceable MCCB , complete all as specified and directed. |
| 26 | Dismantling and removing of defective transformer removing to workshop for repair, opening up and taking out coil, core and core assembly for estimation of repair and damaged parts cleaning/washing of tanks and romoving the dust from all parts including cores, tanks, cooling tubes, removal of damaged parts making connection and assembling complete in all respects after repair/ replacement of coils, gasket, sheet, nuts and bolts, refilling of transformer oil, installation and testing on full load fortesting for 11 KV capacity from 63 KVA to750KVA complete all as specified and directed.Note: 1. Spare parts and winding coils as mentioned under respective items of schedule shallbe measured and paid for separately as supply only. These shall be identical to those specified by original manufacturer. |
| 27 | Dismantling carefullty and material and labour for rewinding the LT/HT side (primary winding/ Secondary windings) of the transformer withcopper winding (wire/strip )of suitable gauge or to match the existingincluding refixing, connecting, testing and commissioning the transformer complete all as specified and directed. |
| 28 | Supply and fix in repair HT bushing rod complete with insulator and packing suitable for out door/Indoortype 63 KVA to 1250 KVA transformers confirming to IS-334 complete with nut bolts brass studs and gasket of synthetic rubber bonded cork sheet complete all as specified and directed. Note : 1. Rates quoted by the contractor shallbe deem to include for opening of top plate of transformer/decanning of oil from transformer up the level as per requirement and assemble the same after replacement of bushing rod.2. Bushing rod shall be replaced at site transformer will not be allowed to send to workshop at any cost and all bushing replacement work shall be executed at site only. |
| 29 | Supply and fix inrepair LT bushing complete with insulator and packing suitable1100 volt grade complete with nut bolts, brass studs, insulator and gasket etc suitable for 63 to 1250 KVA out door/Indoortransformer complete all as specified and directed. Note : 1. Rates quoted by the contractor shallbe deem to include for opening of top plate of transformer/decanning of oil from transformer up the level as per requirement and assemble the same after replacement of bushing rod.2. Bushing rod shall be replaced at site.transformer will not be allowed to send to workshop at any cost and all bushing replacement work shall be executed at site only. |
| 30 | Cleaning of bushes/small plants upto root level around and surroundings areas E/M installations (i.e. Two Pole/ Four structures, outdoor-substation yards & other Misc E/M installations etc.) soft and loose soilincluding surface dressing n.exc 15 cm deep and removing debris to a distance not exc 50m complete all as specified and directed. |
| 31 | M & L for checking and finding out pin point location of fault in HT 11 KV undergroung cable with the help of fault locating machine complete all as specified anddirected.Note:- (i) Rate for the rent of fault locating mobile machine, charges for operator, engineer, electrician etc are deemed to be included in the quoted rate.(ii) Checking and finding fault upto 03 places of same route of the cable will be considered as one job. |
| 32 | M & L cable jointing kit for11 KV (Earthed) grade XLPE cable for straight through cold shrinkable type joint complete with jointing material and accessories suitable for120 - 240 sqmm, 3 core XLPE armoured aluminium conductor cable complete all as specified and directed. Note:- (i) Rate quoted including necessary excavation, returning filling, removal etc for taking out loop/ cutting of burnt cable for required length for making straight through joint. |
| 33 | M & L cable jointing kit for11 KV (Earthed) grade XLPE cable for indoor end termination cold shrinkable type joint complete with jointing material and accessories suitable forsizes 120 Sqmm 3 Core to 240 Sqmm 3 Core including testing after jointing complete all as specified and directed. Note:- (i) Rate quoted including necessary excavation, returning filling, removal etc for taking out loop/ cutting of burnt cable for required length for making end joint. |
| 34 | S& fixing in replacement 1100 volts grade heavy duty PVC insulated aluminium conductor, bedded unarmoured cable of size 10 Sqmm 2 core fixed on wall/floor/poles complete all as specified and directed. |
| 35 | S&fixing in replacement 1100 volts grade heavy duty PVC insulated aluminium conductor, bedded unarmoured cable of size 4 Sqmm 2 core fixed on wall/floor/poles including 15mm PVCpipe with clamps complete all as specified and directed. |