Generator Protection Relay for DG sets: Type: Flush mounted type, Digital, CTR 1600/5A, PTR: (415/√3) / (110/√3), Voltage Operated Current with following features:1. High Set Active/Reactive Reverse Power.2. Earth Fault3. Over Current & Earth Fault with high set4. Over Voltage & Under Voltage5. Loss of Excitation6. Over frequency & Under frequency7. Current unbalance8. PT Fuse failure9. Breaker failure protectionModel: MG-30I or P342 or equivalent, Auxiliary Voltage-24VDC, Frequency: 50/60Hz. Panel Cutout size: 113x142mm, Standard: IEC 60255, 61850, EN/IEC 61000, EN 50081, 50263, 50082, 55022 and IEEE C37 along with their latest amendments.Note:• Only OEM or their authorized dealers should be allowed to take participation in the bidding process and OEM/Firm supplying relay shall also provide support and service for at least next 10 years.• Item to be supplied by firm should be equivalent to the existing generator Protection relay i.e. MG-301 of make L&T installed at 880 KVA,415 VAC DG Set Alternators,DCRTPP,Yamuna nagar. Photo of existing GeneratorProtection relay i.e. MG-301 of make-L&T and 880KVA,415VAC Alternator attached with this indent.However,firm may depute their representative for collecting data,dimensions of existing relay at DCRTPP,Yamuna nagar.• For carrying out technical vetting,bidders while submitting their bids may be asked to submit technical datasheets of the offered items in the format attached with this indent as Annexure-A. Please Enable Macros to View BoQ information