| 1 | Supplying, Installation, Testing, Fixing & Commissioning of Multifunction Meter Flush Mounting 96 X 96 mm size including cutting of CRCA sheet steel doors to fix Multifunction Meter on LT Panel having specifications: LED meter Accuracy Class:1.0 / 0.5 with RS485, Input Voltage Measurement Range 50-520VAC(P-P),Auxiliary Supply 80-300 VAC/DC,CT Secondary Site Selectable 1A/5A, CT/PT site programmable, True PF or Displacement PF site selectable ,V,A,F,PF, kW, kVA, Old energy, Load hours, site selectable kWh/kVAh. (Make: Lauritz Knudsen: Model WL4400110000, Universal, Rishabh, AE) |
| 2 | Supplying, Installation, Testing & Commissioning of Resin Cast Current Transformer having specifications: Class 0.5, Standard Secondary Current: 5A, HSV/IL:0.66/3KV, Frequency: 50 Hz, Insulation: E Type, ISF<5 of following CT ratio: including disconnection and reconnection of cable / busbar after inserting CT etc as required. (Make: AE, L& T, Kappa, Meco, Marshal, Waco) |
| 3 | CT Ratio:400/5A ,Burden 5 VA: , Class:0.5 |
| 4 | CT Ratio:630/5A ,Burden 15 VA: , Class:0.5 |
| 5 | CT Ratio:1000/5A ,Burden 15 VA: , Class:0.5 |
| 6 | CT Ratio:1600/5A ,Burden 15 VA: , Class:0.5 |
| 7 | Supplying and laying 6 Core X 2.5 sqmm size of FRLS/HFFR PVC insulated copper conductor, multi core flexible cable with PVC tie /PVC clip for dressing etc. as required. (Make: Havells, Polycab, Finolex, KEI, RR Kabel) |
| 8 | Supplying and laying 4 Core X 2.5 sqmm size of FRLS/HFFR PVC insulated copper conductor, multi core flexible cable with PVC tie /PVC clip for dressing etc. as required. (Make: Havells, Polycab, Finolex, KEI, RR Kabel) |
| 9 | Supplying and fixing of suitable sizes of medium class PVC flexible conduit along with saddle & accessories in surface etc as required. |