| 1 | Assembling, installation, testing and commissioning of MCB DB enclosure already embedded in the wall including supply of Engraved Circuit Identification Plate and Danger Board as per the detailed specification for the following size of MCB DBs. (Refer Sec VI, Clause No.15.3). |
| 2 | SPN, 12 Way Distribution Board |
| 3 | Supply fixing testing and commissioning of the following RCCBs & MCBs on Distribution Boards as per the detailed specification. (Refer Sec VI, Clause No.14.2). |
| 4 | RCCB DP 63A sensitivity 30mA, TYPE Hpi |
| 5 | 6-32 Amps SP MCB (Type-C) |
| 6 | Supply and fixing following Modular front cover plate on existing modular metal/plastic boxes etc. as required. (Refer Sec VI, Clause No.15.7). |
| 7 | One / Two Module (Suitable for 1 / 2 Module Box ) |
| 8 | 3 Module. (Suitable for 3 Module Box) |
| 9 | 4 Module. (Suitable for 4 Module Box) |
| 10 | 6 Module.(Suitable for 6 Module Box) |
| 11 | 1 Modular dummy plate (White) |
| 12 | EIGHT Module Dummy Front Modular Plate (Suitable for 8 Module Box) |
| 13 | TWELVE Module Dummy Front Modular Plate (Suitable for 12 Module Box) |
| 14 | 1 No 10A Switch on modular plate and termination of wires to the Switches |
| 15 | 1 No. of 1 Module, 10 A, 1Way, Single PoleBuzzer / Calling Bell Switch. |
| 16 | 1 No 6A 3 Pin shuttered type Socket on modular plate and termination of wires to the switches |
| 17 | 2 Module Step type Fan regulator on modular plate and termination of wires to the switches |
| 18 | ONE Module Front Modular Plate along with 1 No. of 1 Module TV Co-axial Socket Outlet. |
| 19 | TWO Module Front Modular Plate along with 2 Nos of RJ11 Telephone Socket with Shutter. |
| 20 | THREE Module Front Modular Plate along with 1 No. of 6 A Modular Switch and 1 No. of 6 A, 3 Pin, Shuttered Socket as per the detailed specification.(P Point) |
| 21 | THREE Module Front Modular Plate along with 1 No. 16A Modular Switch and 1 No. of 6/16 A, 3 Pin, Combined Socket as per the detailed specification.(A Point) |
| 22 | Two Module Front Modular Plate along with 1 No.10/25A Heavy Duty 3 Pin combined shuttered Socket,1 No, 16A, 3 Pin heavy duty plug top with indicatorincludingtermination of wires to the switches (GeycerPoint) |
| 23 | TWO Module Front Modular Plate along with 1 No. 20A, SP,Mini MCB, \"C\" series, 1 No. One Module,6 A, Indicator Lamp for Geyser Control as per detailed specification. (Geyser Control) |
| 24 | Supply, installation, testing and commissioning ofLED Lamps/ as per detailed specification and as directed by Engineer in Charge. |
| 25 | Supply, installation, testing and commissioning of1 x 25 W, 4 feetLED Pattenalong with supply of necessary fabricated brackets to mount the light fitting and supply and fixing of 6 A, 240 V, 3 Plate, Ceiling rose as per detailed specification and as directed by Engineer in Charge. |
| 26 | Supply, transportation, installation, testing and Commissioning ofWall (surface) mounted 6 W Bulk Headluminaires.- Catalogue No : WT202W LED6S CW PSU S2 PC or equivalent and Lamp Type LED. (Refer Sec VI, Clause No.16.1). |
| 27 | Supply, installation, testing and commissioning of 6 A, 240 V, 3 Plate, Ceiling rose with PVC Junction Linker as per detailed Specification and as directed by Engineer-in-charge. |
| 28 | Supply and installation of 6 A, 230 V, Angle Lamp Holder along with PVC Junction Linker as per detailed Specification and as directed by Engineer in Charge. |
| 29 | Supply and installation of Electronic Calling Bell as perthe detailed specification and as directed by Engineer in Charge. |
| 30 | Supply, installation, testing and commissioning of following sizes of Wall Mounting Exhaust Fans including supply of3 Core, 1.0 Sq.mmPVC insulated & FRLS sheathed copper flexible cable of required length as per the detailed specification. (Refer Sec VI, Clause No.17.2). |
| 31 | 230 mm dia Medium duty, Double ball bearing exhaust fan |
| 32 | Supply, Installation, testing and commissioning of following sizes of ceiling Fans and safety steel rope with 3 Core, 1.5 Sq.mmflexible copper cable including earth connection. Supply and fixing of regulator is not included in the scope of this item. (Refer Sec VI, Clause No.17.1). |
| 33 | 1200mm Sweep AC ceiling fan. |
| 34 | 1400mm Sweep AC ceiling fan. |
| 35 | Supply and Installation of following sizes of PVC trunking (casing & capping) on walls/Ceiling for routing of Power, Lighting and Telephone wires including all the required accessories like JBs, Coupling, External & Internal Bends, Elbows and end cap as per the detailed specification.(Refer Sec VI, Clause No.29) |
| 36 | 32 x 12mm size of PVC Mini trunking |
| 37 | 25 x 12 mm size of PVC Mini trunking |
| 38 | 20 x 12 mm size of PVC Mini trunking |
| 39 | Wiring for lights / fans /sensors/ Power point with 1100V grade FRLS insulated copper conductor wires in existing concealed/ Exposed PVC / ERW / Flo-coated Metal conduits as per the detailed scope of work, including supply of Wires, termination of copper wires at either end by crimping including supply of PVC Sleeves/Ferrules, Copper Crimping Lugs and connecting the wires to various switches, sockets, etc. including testing and commissioning as per the detailed specification.(Refer Sec VI, Clause No.18) |
| 40 | Wiring with 2 Runs of 6.0 Sq.mm Copper wires for Phase, Neutral and 2 Runs of 2.5 Sq.mm Copper wires for Earth from Energy Meter Distribution Boards to SPN Distribution Boards. |
| 41 | Wiring for Power Points with 2 Run of 4.0 Sq. mm Copper Wire for Phase, Neutral and 1 Run of 2.5 Sq.mm Copper Wire for Earth. |
| 42 | 3 Runs of 2.5 Sq.mm Copper Wire for Phase, Neutral and Earth. |
| 43 | Wiring with 2 Runs of 1.5 Sq.mm for Phase, Neutral and 1 Run of 2.5 Sq.mm copper wires for Earth. |
| 44 | Wiring for Power Points with 1 Run of 4.0 Sq.mm Copper Wire. |
| 45 | Wiring for Light/Power Points with 1 Run of 2.5 Sq.mm Copper Wire. |
| 46 | Wiring for Light/Power Points with 1 Run of 1.5 Sq.mm Copper Wire. |
| 47 | Wiring and termination for Telephone point with 1 Run of 0.61 mm dia, 250 V grade PVC insulated, twin twisted, single pair, tinned copper wire from Telephone Junction Box to Telephone points in concealed conduit/ PVC Trunking including of supply of Telephone wire. (Refer Sec VI, Clause No.18) |
| 48 | Wiring for Television point including supply of RG-6 Co-axial cable from terminal junction box to the TV pointprovided in the living hall in each Quarter in existing concealed PVC Rigid conduits/Casing & Cappingincluding connecting the same to the socket. as per the detailed Specification. (Quantity indicated is running length of 1 Run of Wire), (Refer Sec VI, Clause No.18) |
| 49 | Supply and Installation ofP3 grade laminated Hylam sheet of 3mm thickness over the boxes and as per the detailed specification. |
| 50 | Supply and installation of 63 Amps, 500 Volts 4 way SS stud type Terminal block with DIN railfor mounting and as directed by the Engineer-in-Charge. |
| 51 | Retrieval of the already laid one number 1100 Volts Grade XLPE/HRPVC insulated, Stranded Aluminium conductor cables of following sizes in built-in trenches, on walls, poles and from embedded pipes including removal of end termination GI spacer, clamps etc as per the detailed specification. (Refer Sec VI, Clause No.5) |
| 52 | 3/3.5/4 Core upto 25 Sqmm |
| 53 | Relaying of one number 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables of following sizes in built-in trenches on walls, poles and through embedded pipes using the retrieved spacer & clamps as per the detailed specification. (Note: Cable will be supplied by department as free issue item) (Refer Sec VI, Clause No.6) |
| 54 | 3/3.5/4C X Upto 25 Sqmm |
| 55 | End Termination of the following sizes of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. (Refer Sec VI, Clause No.10.1). |
| 56 | 4 Corex 10 Sqmm |
| 57 | Supply, installation, testing and commissioning of the following Raychem make Heat Shrinkable Cable Straight Through Jointing Kits (Crimping type) for 3.5 Core Aluminium Conductor, 1.1 kV (E), PVC/XLPE insulated cables of following sizes as specified. Excavation will be measured separately (Refer Sec VI, Clause No.10.6). |
| 58 | 4C x 10/16 Sqmm Aluminium Cable |
| 59 | Assembling, testing and commissioning of flush mounting 20 Amps, 230 Volts, 2 Pin + Earth, 1 Phase Metal Clad Socket (AC Point)including supply of1 No 20 Amps Single Pole MCB C Seires as per the detailed specification. |
| 60 | Excavation of soil including refilling with excavated earth and disposing surplus earth at places as directed with in a lead of 10 Mtrs. and initial lift upto 1.5 Mtrs. including neat banking as per detailed specification. (Refer Sec VI, Clause No.2) |